Plan Review Details - Permit 06010156
Plan Review Stops For Permit 06010156
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-19 Cont ID  
Sent By shill Date 2006-04-19 Time 17:02 Rev Time 0.00
Received By shill Date 2006-04-19 Time 17:02 Sent To  
Notes
2006-04-19 00:00:00PROVISO - SUBMIT SOIL LETTER BEARING
 >2000 PSF

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-17 Cont ID  
Sent By shill Date 2006-04-17 Time 08:15 Rev Time 0.00
Received By shill Date 2006-04-14 Time 18:28 Sent To  
Notes
2006-04-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)IT IS NOT CLEAR WHICH LOT THE
 PARTIALLY SUBMERGED PARCEL BELONGS TO.
 THE SURVEYOR SHOWS THE TWO PARTIALLY
 SUBMERGED PARCELS AS ONE LOT, AND LOTS
 (PARTIAL) 20 THROUGH 27 AS ONE LOT.
 PROPERTY APPRAISER SHOWS THIS AS TWO
 LOTS, EACH INCLUDING A PARTIALLY
 SUBMERGED PIECE OF LAND IN ADDITION TO
 THE PLATTED LOTS.PLEASE HAVE THE
 SURVEYOR CONTACT ME TO ADDRESS THIS
 BEFORE THE PERMIT CAN BE ISSUED.
  
 PLEASE NOTE THAT BOTH THE SURVEY AND THE
 ARCHITECTURALS ARE IN CONFLICT WITH THE
 PROPERTY APPRAISER RECORDS.
  
 2.)THE NOTICE OF COMMENCEMENT IS NOT
 CORRECT.THE IT REQUIRED TO INCLUDE A
 LEGAL DESCRIPTION AND IS TO HAVE THE
 PRINTED NAME OF THE OWNER.TRG WORTH
 FLAGLER VENTURE IS AN ENTITY, AND AN
 INDIVIDUAL SIGNS ON BEHALF OF THE
 ENTITY.THE PRINTED NAME OF THE
 INDIVIDUAL WHO SIGNED SHOULD BE ON THE
 NOC.THE LEGAL SHOULD INCLUDE ALL
 PARCELS AFFECTED BY THIS IMPROVEMENT,
 NOT ONE ADDRESS.
  
 3.)ADDITIONAL FEES DUE.THIS WAS A
 RESUB, NOT A SUBMITTAL.
  
 4.)THE PERMIT WILL BE ISSUED WITH A
 PROVISO, SEE BELOW.
  
 * * * * * * * * * * * * * * * * * * *
  
  
2006-04-14 00:00:00****PROVISO****
  
 SUBMIT LETTER FROM SOILS ENGINEER
 SHOWING SOIL BEARING PRESSURE OF 2000PSF
 MINIMUM AT FIRST INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-07 Cont ID  
Sent By shill Date 2006-04-07 Time 08:40 Rev Time 0.00
Received By shill Date 2006-04-07 Time 08:40 Sent To  
Notes
2006-04-07 00:00:00****CORRECTIONS****
 ****SECOND REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, NUMBERING REMAINING
 THE SAME FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THIS IS REQUIRED PRIOR TO PERMIT PICKUP.
  
 2.)ADDRESSED.
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1808.2.
  
 THIS WAS ADDRESSED; HOWEVER, THE SOILS
 REPORT GIVES FOUNDATION RECOMMENDATIONS
 FOR THE FUTURE GARAGE AND HIGH RISE.
 THERE IS NO RECOMMENDATION FOR THE SALES
 TRAILER TIE DOWN, AND THE ENGINEER FOR
 THE SALES TRAILER FOUNDATION DOES NOT
 REFER TO ANY SOILS ENGINEERING IN HIS
 PLAN.
  
 AS DISCUSSED, PLEASE HAVE THE ENGINEER
 CALL ME.A LETTER OR A PLAN REVISION
 REFERENCING THE SOILS REPORT WILL BE
 REQUIRED.PLEASE NOTE THAT I HAVE
 ATTEMPTED REACHING THE ENGINEER, WILLIAM
 MCCANN PE, CLEARWATER, AND THE TELEPHONE
 NUMBER ON HIS TITLE BLOCK IS
 DISCONNECTED.
  
 IN THE LETTER OR PLAN REVISION, THE
 ENGINEER IS TO ADDRESS THE TWO ISSUES OF
 BEARING PRESSURE AND UPLIFT RESISTANCE
 FOR THE ANCHORS SPECIFIC TO THE SITE.
 THE FOUNDATION PLAN FD1 DOES NOT REFER
 TO THE JOB SITE IN ANY WAY (JOB NAME,
 ADDRESS OR LEGAL DESCRIPTION) SO I
 CANNOT DETERMINE WHETHER OR NOT THIS IS
 A STANDARD DETAIL OR IF THE ENGINEER IS
 AWARE OF SITE SPECIFIC SOIL CONDITIONS.
  
 ADDITIONALLY, THE FOUNDATION ENGINEER
 HAS DECLARED 140 EXPOSURE B.WHEN
 ADDRESSING SOILS CONDITIONS, ALSO HAVE
 THE ENGINEER ADDRESS SITE CONDITION IN
 REGARDS TO WIND EXPOSURE.
  
  
 THE FOLLOWING COMMENTS REMAIN;
 INFORMATIONAL ONLY TO ASSIST IN PLAN
 REVIEW FOR THE FUTURE SALES TRAILER
  
 4.)THIS FOUNDATION AND TIE DOWN ONLY
 PERMIT WILL BE ISSUED AT THE
 CONTRACTOR'S RISK.BUILDING CODE
 COMPLIANCE FOR THE OTHER ITEMS (SALES
 TRAILER, ACCESSIBLE ROUTE, ETC.) CANNOT
 BE DETERMINED BASED ON THE INFORMATION
 PROVIDED.
  
 5.)THE ARCHITECTURAL SITE PLAN
 CONFLICTS WITH THE CIVILS.THE
 ARCHITECTURAL SITE PLAN SHOWS ONE LOT;
 THE OTHER SHEETS SHOW MULTIPLE LOTS.
 HAS A UNITY OF TITLE BEEN RECORDED?
 NOTE THAT THE FUTURE TRAILER APPEARS TO
 BE LESS THAN 5' FROM THE CURRENT
 PROPERTY LINE AND THAT THE OTHER
 IMPROVEMENTS CROSS OVER THE PROPERTY
 LINES.
  
 THIS COMMENT IS INFORMATIONAL AND DOES
 NOT PREVENT THIS PERMIT FROM BEING
 ISSUED.HOWEVER, BEFORE A BUILDING
 PERMIT FOR THE SALES TRAILER AND OTHER
 IMPROVEMENTS CAN BE ISSUED A RECORDED
 UNITY OF TITLE WILL BE REQUIRED.
  
 6.)THIS PARCEL IS IN A FLOOD ZONE.
 CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B), FINISHED FLOOR MUST BE 6"
 ABOVE BFE AND AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.THIS COMMENT IS
 INFORMATIONAL AND DOES NOT NEED TO BE
 ADDRESSED.
  
 *************************
  
 4/7/6S/W ENGINEER, 727-461-5500

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-06 Cont ID  
Sent By shill Date 2006-04-06 Time 09:26 Rev Time 0.00
Received By shill Date 2006-04-06 Time 09:26 Sent To  
Notes
2006-04-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE APPLICATION DESCRIPTION
 CONFLICTS WITH THE PLANS SUBMITTED.THE
 PLANS FOR THE TRAILER WERE INCLUDED.TO
 AVOID CONFUSION, PLEASE REMOVE.
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1808.2.
  
 4.)THIS FOUNDATION AND TIE DOWN ONLY
 PERMIT WILL BE ISSUED AT THE
 CONTRACTOR'S RISK.BUILDING CODE
 COMPLIANCE FOR THE OTHER ITEMS (SALES
 TRAILER, ACCESSIBLE ROUTE, ETC.) CANNOT
 BE DETERMINED BASED ON THE INFORMATION
 PROVIDED.
  
 5.)THE ARCHITECTURAL SITE PLAN
 CONFLICTS WITH THE CIVILS.THE
 ARCHITECTURAL SITE PLAN SHOWS ONE LOT;
 THE OTHER SHEETS SHOW MULTIPLE LOTS.
 HAS A UNITY OF TITLE BEEN RECORDED?
 NOTE THAT THE FUTURE TRAILER APPEARS TO
 BE LESS THAN 5' FROM THE CURRENT
 PROPERTY LINE AND THAT THE OTHER
 IMPROVEMENTS CROSS OVER THE PROPERTY
 LINES.
  
 THIS COMMENT IS INFORMATIONAL AND DOES
 NOT PREVENT THIS PERMIT FROM BEING
 ISSUED.HOWEVER, BEFORE A BUILDING
 PERMIT FOR THE SALES TRAILER AND OTHER
 IMPROVEMENTS CAN BE ISSUED A RECORDED
 UNITY OF TITLE WILL BE REQUIRED.
  
 6.)THIS PARCEL IS IN A FLOOD ZONE.
 CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B), FINISHED FLOOR MUST BE 6"
 ABOVE BFE AND AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.THIS COMMENT IS
 INFORMATIONAL AND DOES NOT NEED TO BE
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-03-27 Cont ID  
Sent By dpalmer Date 2006-03-27 Time 15:35 Rev Time 0.00
Received By dpalmer Date 2006-03-27 Time 15:35 Sent To  
Notes
2006-03-27 00:00:00THIS PERMIT IS FOR FOUNDATION/TIE DOWN
 OF FUTURE SALES TRAILERS, NEED TO SUPPLY
 ELECTRICAL RISER DIAGRAM WITH PERMIT
 APPLICATION FOR TRAILER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By dpalmer Date 2006-02-07 Time 17:09 Rev Time 0.00
Received By dpalmer Date 2006-02-07 Time 17:04 Sent To  
Notes
2006-02-07 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE PERMIT IS SUBMITTED
 FOR TIE-DOWN ONLY , HOWEVER WHERE IS THE
 PERMIT APPLICATION FOR THE INSTALLATION
 OF THESE TRAILERS?
  
 2)NOTE: PLEASE SEE THE STATE TRAILERS
 SEEM TO INDICATE CHANGES OTHER THAN THE
 WAY THESE ARE TYPICALLY WIRED FROM THE
 MANUFACTURE. PLEASE SEE PLANS ARE
 PHOTO-COPIES OF PLANS WHICH WERE STAMPED
 FROM THE STATE.
 PLEASE ALSO SEE A TITLE BLOCK ADDED FOR
 ENGINEER. PLEASE SEE THE STATE OF
 FLORIDA WEBSITE DOES NOT LIST THIS
 ENGINEER. PLEASE ALSO SEE THE PLANS
 CONTAINED A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE WHICH VIOLATES FS
 471.025
 PLEASE KNOW THIS IS THE 2ND SUCH PROJECT
 IN WHICH THE SAME SAID THINGSHAVE BEEN
 DONE AND SUBMITTED FOR PERMITTING.
 PLEASE KNOW, THE PLANS MAY BE RETAINED
 AND SUBMITTED TO THE STATE BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW.
 PLEASE CORRECT OR PROVIDE ORIGIANL
 STAMPED, UN-ALTERED STATE APPROVED
 TRAILER PLANS.
  
 3)NOTE: PLEASE PROVIDE A RISER DIAGRAM
 FOR THE HOOK-UP OF ALL FOUR TRAILERS.
 PLEASE BE SURE TO CORRELATE ALL LOADS AS
 SHOWN.
 215.5
 THE RISER DIAGRAM FOR HOOK-UP MAY BE
 DRAWN BY ELECTRICAL CONTRACTOR. IF
 INDEED THIS IS DONE FOR THIS SCOPE OF
 WORK ONLY, PLEASE HAVE THE CONTRACTOR
 PRINT NAME AND SIGN PLANS. PER FS 489,
 FBC ADMIN SECTION, 106.3.4.3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-02-10 Cont ID  
Sent By mamini Date 2006-02-10 Time 14:17 Rev Time 1.00
Received By mamini Date 2006-02-10 Time 14:17 Sent To  
Notes
2006-02-10 00:00:00PASEED WITH PROVISOS:
  
 1. A SEPARATE R.O.W PERMIT FOR WORK
 WITHIN PUBLIC R.O.W AT NO COST IS
 REQUIRED, PLASE CONTACT WINDEL PALMER AT
 494-1086.
  
 2. INSTALL POLLUTION PREVENTION DEVICES
 IN FIELD PRIOR TO BEGIN WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-05 Cont ID  
Sent By mwennerg Date 2006-04-05 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2006-04-05 Time 13:42 Sent To  
Notes
2006-04-05 00:00:00******APPROVED******
  
 1) PLEASE NOTE THAT PREVIOUS COMMENTS
 AND RESPONSES WILL BE APPLICABLE FOR THE
 BUILDING PERMITTING PROCESS.
  
 2) KNOX BOX APPLICATIONS MAY BE OBTAINED
 FROM THE BUREAU OF FIRE PREVENTION,
 (561) 804-4724.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By mcarsill Date 2006-02-15 Time 17:04 Rev Time 0.00
Received By mcarsill Date 2006-02-15 Time 17:04 Sent To  
Notes
2006-02-15 00:00:001. PROVISIONS MUST BE MADE FOR FIRE AND
 PARAMEDICAL EQUIPMENT THRU THE ROLLING
 GATE.
  
 2. SITE PLAN TO ILLUSTRATE EXISTING OR
 NEW FIRE HYDRANT.
  
 3. PLEASE ILLUSTRATE ALL ILLUMINATED
 EXIT SIGNS, EMERGENCY LIGHTS, AND
 PORTABLE FIRE EXTINGUISHERS.
  
 4. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 16:45 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 16:45 Sent To B
Notes
2006-04-14 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-06 Cont ID  
Sent By shill Date 2006-04-06 Time 09:52 Rev Time 0.00
Received By shill Date 2006-01-06 Time 09:44 Sent To  
Notes
2006-02-01 00:00:00TO "COMM" BD#9
2006-01-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-02-22 Cont ID  
Sent By pkrauss Date 2006-02-22 Time 08:04 Rev Time 0.00
Received By pkrauss Date 2006-02-22 Time 07:54 Sent To  
Notes
2006-02-22 00:00:00SALES TRAILER / MANUFACTURED APPROVED
 THROUGH THE STATE.PAKG UNIT PERMIT
 APPLICATION IS FOR TIE DOWN ONLY.
  
 PLAN REVIEW BY PATTY KRAUSS, MECHANICAL
 PLANS EXAMINER. (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-28 Cont ID  
Sent By mmclean Date 2006-03-28 Time 10:48 Rev Time 0.00
Received By mmclean Date 2006-03-28 Time 10:48 Sent To  
Notes
2006-03-28 00:00:00APPROVING PER ANGELLA JONES-VANN, DEPT
 PLANNING & DIRECTOR 822-1435 MM

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By ebowers Date 2006-01-11 Time 14:50 Rev Time 0.00
Received By ebowers Date 2006-01-11 Time 14:50 Sent To I
Notes
2006-01-11 00:00:00MUST APPLY FOR A MINOR PD AMENDMENT.
 PLEASE SEE EDNASHA BOWERS (561-822-1435
 X 1444)) OR ANGELLA JONES-VANN
 (561-822-1435 X 1441) FOR QUESTIONS.