Plan Review Details - Permit 06010130
Plan Review Stops For Permit 06010130
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-14 Cont ID  
Sent By alange Date 2006-03-14 Time 10:47 Rev Time 0.50
Received By alange Date 2006-03-14 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By alange Date 2006-02-08 Time 07:30 Rev Time 0.40
Received By alange Date 2006-02-08 Time 07:26 Sent To  
Notes
2006-02-08 00:00:00DENIED
  
 1.SHOW SLAB DETAIL AND SHOW METHOD OF
 GENERATOR ATTACHMENT TO SLAB.
  
 2.SUBMIT TWO ORIGONAL SEALED SURVEYS,
 FS 472.025
  
 3.PERSON RESPOSIBLE FOR THE DESIGN
 SHALL PRINT THERE NAME AND SIGN PLANS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-30 Cont ID  
Sent By btrobaug Date 2006-01-30 Time 17:29 Rev Time 0.50
Received By btrobaug Date 2006-01-30 Time 17:08 Sent To M
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-02-02 Cont ID  
Sent By jleech Date 2006-02-02 Time 09:28 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-04-18 Cont ID  
Sent By mperson Date 2006-04-18 Time 14:26 Rev Time 0.33
Received By mperson Date 2006-04-18 Time 14:26 Sent To PC
Notes
2006-04-18 00:00:00REVISION: USE GALVANIZED PIPE ABOVE
 GROUND INSTEAD OF PE UNDER GROUND ALONG
 WALL TO DRYER AND TANKLESS WATER HEATER

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-03-10 Cont ID  
Sent By mperson Date 2006-03-10 Time 08:25 Rev Time 0.00
Received By mperson Date 2006-03-10 Time 08:25 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-02-02 Cont ID  
Sent By jleech Date 2006-02-02 Time 09:32 Rev Time 0.33
Received By jleech Date 2006-02-02 Time 09:29 Sent To B
Notes
2006-02-02 00:00:00DENIED;
 ZONING MUST APPROVE LOCATION OF
 GENERATOR BEFORE GAS PLAN CAN BE
 APPROVED.
 GAS PERMIT REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 11:46 Sent To M
Notes
2006-03-06 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 14:27 Sent To Z
Notes
2006-02-28 00:00:00TO 'Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 16:07 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 16:07 Sent To E
Notes
2006-01-28 00:00:00TO "GEN-RES" BOX"E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-08 Cont ID  
Sent By alange Date 2006-02-08 Time 07:43 Rev Time 0.00
Received By alange Date 2006-01-05 Time 13:39 Sent To  
Notes
2006-01-05 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-06 Cont ID  
Sent By tgordon Date 2006-03-06 Time 13:32 Rev Time 0.15
Received By tgordon Date 2006-03-06 Time 13:32 Sent To P
Notes
2006-03-06 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 16:14 Rev Time 0.20
Received By tgordon Date 2006-01-31 Time 16:14 Sent To G
Notes
2006-01-31 00:00:00*** DENIED ***
 1) PLANS OF GENERATOR LOCATION ARE
 DIFFICULT TO READ DUE TO SIZE AND AMOUNT
 OF INFOMATION ON THEM.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-02-02 Cont ID  
Sent By jleech Date 2006-02-02 Time 09:28 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-06 Cont ID  
Sent By mmclean Date 2006-03-06 Time 10:35 Rev Time 0.00
Received By mmclean Date 2006-03-06 Time 10:35 Sent To I
Notes
2006-03-06 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-27 Cont ID  
Sent By mmclean Date 2006-01-27 Time 13:20 Rev Time 0.00
Received By mmclean Date 2006-01-27 Time 13:20 Sent To B
Notes
2006-01-27 00:00:00DENIED,
 1. MUST PROVIDE TWO CURRENT COPY OF
 SURVEY, SHOWING THE LOCATION OF WORK.
 2. SURVEY PROVIDED IS OVER A 1YR OLD.
 (1972).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720