Plan Review Details - Permit 06010091
Plan Review Stops For Permit 06010091
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status N Date 2007-06-12 Cont ID  
Sent By mjacobs Date 2007-06-12 Time 09:09 Rev Time 0.00
Received By mjacobs Date 2007-06-12 Time 09:09 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-06-11 Cont ID  
Sent By mjacobs Date 2007-06-11 Time 14:43 Rev Time 0.00
Received By mjacobs Date 2007-06-11 Time 12:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-04-03 Cont ID  
Sent By rbrown Date 2007-04-03 Time 19:55 Rev Time 0.00
Received By rbrown Date 2007-04-03 Time 19:55 Sent To  
Notes
2007-04-03 19:56:45STRUCTURAL SUBMITTAL ON 3/14/07 FOR STRUCTURAL
 ENGINEER'S CALCULATIONS AND REINFORCING DETAILS AND
 SPEC FOR 7TH FLOOR BEAMS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-27 Cont ID  
Sent By mjacobs Date 2007-01-27 Time 06:35 Rev Time 0.00
Received By mjacobs Date 2007-01-27 Time 05:34 Sent To PC
Notes
2007-01-27 09:52:52PROVISOR:
  
 THESHIELDING SPECIFICATIONS REPORTS SHALL BE
 ORIGINALY SIGNED BY THE PERSON WHO IS RESPONSIBLE.
 THESE REPORTS SHALL THEN BE APPROVED BY THE ARCHITECT
 OR ENGINEER OF RECORD WITH THEIR SEAL AND SIGNATURE.
 EACH SHEET SHALL BE SIGNED OR A COVER SHEET REFERENCING
 EACH SHEET SHALL BE PROVIDED WITH THE RREPORT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-03 Cont ID  
Sent By alange Date 2006-10-03 Time 12:14 Rev Time 0.00
Received By alange Date 2006-10-03 Time 12:14 Sent To  
Notes
2006-10-03 00:00:00DENIED
  
 1.BUILDING REVIEW OK.
  
 2.SEE ELECTRICAL REVIEW NOTE #2.
 THESE ITEMS ARE REQUIRED ON THE PLANS
 PRIOR TO PERMITTING.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By alange Date 2006-07-07 Time 13:39 Rev Time 0.00
Received By alange Date 2006-07-07 Time 13:39 Sent To  
Notes
2006-07-07 00:00:00DENIED
  
 1.BUILDING REVIEW OK.SEE THE
 FOLLOWING INFORMATION REQUIRED ON PLANS
 FOR REVIEW.
  
 2.2004 FBC 106.1
 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART I, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTE. IF THE
 DESIGN PROFESSIONAL IS A LANDSCAPE
 ARCHITECT REGISTERED UNDER THE LAWS OF
 THIS STATE REGULATING THE PRACTICE OF
 LANDSCAPE ARCHITECTURE AS PROVIDED FOR
 IN CHAPTER 481, FLORIDA STATUTES, PART
 II, THEN HE OR SHE SHALL AFFIX HIS OR
 HER SEAL TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 DEFINED IN SECTION
 481.303(6)(A)(B)(C)(D), FS.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-06 Cont ID  
Sent By alange Date 2006-04-06 Time 15:40 Rev Time 6.00
Received By alange Date 2006-04-06 Time 14:26 Sent To  
Notes
2006-04-06 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ROOM 123 LEAD LINED WALLL NOT SHOWN
 CONTINUOS BEHIND BATHRROM 126.
 FBC 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER
 VERTICAL BARRIERS REQUIRED FOR PERSONNEL
 PROTECTION SHALL EXTEND WITHOUT BREACH
 FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET.
  
 3.DOOR FOR ROOM 118 NOT THE SMAE
 RATING AS THE WALL.
 FBC 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW
 FRAMES SHALL HAVE THE SAME LEAD
 EQUIVALENT SHIELDING AS THAT REQUIRED IN
 THE WALL OR OTHER BARRIER IN WHICH THEY
 ARE INSTALLED.
  
 4.FBC 435.5.1.3
 PRIOR TO CONSTRUCTION, THE FLOOR PLANS
 AND EQUIPMENT ARRANGEMENT OF ALL NEW
 INSTALLATIONS, OR MODIFICATIONS OF
 EXISTING INSTALLATIONS, UTILIZING X-RAY
 ENERGIES OF 200 KEV AND ABOVE FOR
 DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL
 BE SUBMITTED TO THE DEPARTMENT OF HEALTH
 FOR REVIEW AND APPROVAL. IN COMPUTATION
 OF PROTECTIVE BARRIER REQUIREMENTS, THE
 MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE
 POTENTIAL FOR RADIATION EXPOSURE FROM
 OTHER SOURCES SHALL BE TAKEN INTO
 CONSIDERATION.
  
 5.5 OF A-6 RECEPTION COUNTER, IS
 SUPPORT BRACKET BLOCKING ACCESSABLITY TO
 COUNTER?
  
 6.SEE ELECTRICAL REVIEW NOTES
 REGARDING SIGNING AND SEALING OF PLANS.
  
 7.SUBMIT LOAD CALCULATIONS SHOWING
 THAT EXISTING FLOOR WILL ACCEPT THIS
 ADDITIONAL LOAD.ALSO SPECIFY IF
 EXISTING FLOORING IS POST TENTIONING.
 SHOW SLAB DETAILS INREGARDS TO CUTTING
 AND TRENCHING AND THAT THE NECCESSARY
 CALCULATIONS HAVE BEEN MADE.
  
 8.FBC 435.5.1.3.1.4 SHOW THE TYPE OF
 OCCUPANCY OF ALL ADJACENT AREAS
 INCLUSIVE OF SPACE ABOVE AND BELOW THE
 ROOM CONCERNED. IF THERE IS AN EXTERIOR
 WALL, THE DISTANCE TO THE CLOSEST AREA
 WHERE IT IS LIKELY THAT INDIVIDUALS MAY
 BE PRESENT.
  
 9.IS THE EXTERIOR R.T SHEILDED WINDOW
 NEW?IF SO SUBMIT PRODUCT APPROVALS PER
 THE FOLLOWING...
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10.DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS.
 FBC 1008.1.2SEE DOOR 182
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 12:42 Rev Time 0.00
Received By dpalmer Date 2007-06-29 Time 10:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-06-04 Cont ID  
Sent By dpalmer Date 2007-06-04 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2007-06-04 Time 10:41 Sent To  
Notes
2007-06-04 12:13:06REV'S FOR E2,3,AND E5.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-02-02 Cont ID  
Sent By dpalmer Date 2007-02-02 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2007-02-01 Time 19:15 Sent To PC
Notes
2007-02-01 19:16:27IN ELECTRICAL FOR REVIEW. NEW SUBMITTALS BROUGHT IN BY
 CONTRACTOR ON 1/30

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-12-20 Cont ID  
Sent By dpalmer Date 2006-12-20 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2006-12-19 Time 18:19 Sent To  
Notes
2006-12-20 18:46:26*** UNSAT 5TH REVIEW ***
  
 ** PLEASE SEE NOTES FROM THE FOUR PREVIOUS REVIEWS AS
 FOLLOWS.
 PLEASE CALL IS THERE ARE ANY QUESTIONS OR COMMENTS.
  
  
 1) NOTE:PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW
 DATED 11/16/06. PLEASE SEE THAT THE MANUFACTURES SPECS
 DO NOT CORRELATE WITH THE SAME INFORMATION AS PROVIDED
 ON PLANS. PLEASE SEE THE SPECIFIC UNIT IS NOT CHECKED,
 MARKED, HIGHLIGHTED OR NOTED FOR THE PARTICULAR UNIT.
 PLEASE SEE THE COMMENTS BELOW.
 PLEASE SEE SPECS FOR THE ATS WHICH ARE ONLY NOW BEING
 SUBMITTED FOR REVIEW WOULD STILL NEED TO INDICATE BEING
 3R LISTED AS WELL AS RISER INDICATING THE SAME. 90.7,
 110.3,
 FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTES BELOW FROM REVIEW#4 DATED
 11/16/06 **
 NO, COMMENT NOT FULLY ADDRESSED. PLEASE SEE SPECS WERE
 SUBMITTED, HOWEVER AS REQUESTED IN THE PREVIOUS REVIEWS
 PLEASE BE SURE ALL EQUIPMENT CORRELATES FOR USE AND
 INSTALLATION ETC.
 PLEASE SEE THE ATS SPECS ARE LISTED AND FOR USE FOR A
 FIRE PUMP AND SPECIFIES MANY ITEMS FOR NFPA-20?? PLEASE
 SEE THIS SYSTEM IS PER NFPA-110, 70 AND EQUIPMENT SHALL
 BE LISTED FOR THE INTENDED USE. PLEASE SEE THE GEN
 SPECS NOW SUBMITTED STATE CLEARLY A MINIMUM OF
 3FT/1METER ON ALL SIDES,, HOWEVER AS STATED REQUIRES
 MORE CLEARANCE WHEN INSTALLED IN A WP HOUSING FOR DOORS
 ETC. PLEASE SEE SPACE AS SHOWN DOES NOT SEEM TO MEET
 THE MINIMUM CLEARANCES FOR UNIT WITH THE WP ENCLOSURE.
 PLEASE SEE AS NOTE ON SPECS MENTIONS TO PROVIDE
 ADDITIONAL SPACE FOR DOORS, THIS INFORMATION IS NOT
 SHOWN ON THE ENCLOSURE SPECS AS SUBMITTED.
 PLEASE SEE OTHER COMMENTS FOR VENTILATION IN SPECS.
 PLEASE SEE SPECS DO NOT INDICATE THE SPECIFIC UNIT AND
 KW RATING, NOTE MENTIONS TO SEE NAMEPLATE, HOWEVER AS
 THIS IS NOT POSSIBLE, THE KW RATING AS SHOWN ON PLANS
 INDICATES 42KW, AND THE NEED TO CORRELATE THE
 MANUFACTURES SPECS AND SIZE OF THE UNIT AND WP IS OF
 THE UTMOST IMPORTANCE.
 PLEASE SEE THE CLOSEST UNIT SIZE AND MODEL IS THE 83"
 LONG, 40" WIDE AND 72" IN HEIGHT.
 PLEASE KNOW AS THE UNIT AND ENCLOSURE IS NOT SPECIFIED
 WE ARE UNABLE TO VERIFY.
 PLEASE ALSO SEE AS SHOWN THE EXHAUST IS STRAIGHT OUT OF
 THE TOP AS SHOWN ON HOUSING AND THE SPACE BELOW THE
 UPPER LEVEL FROM THE PARKING DECK DOES NOT PROVIDE
 CLEARANCE IF THE UNIT IS 72" HIGH.
 PLEASE SEE COMMENTS FROM MECHANICAL, PLUMBING AND FIRE
 AND POSSIBLE BLDG COMMENTS NOW THAT THE SPECS ON
 EQUIPMENT HAVE BEEN SUBMITTED.
 PLEASE SEE OTHER COMMENTS WHICH REQUIRE READY ACCESS.
  
 ** PLEASE KNOW BASED ON THESE COMMENT FOR THE
 GENERATOR, AND THE POSSIBILITY THAT THE GENERATOR MAY
 NOT BE PERMITTED TO BE INSTALLED AT THIS LOCATION DUE
 TO MINIMUM CLEARANCES, ACCESS, VENTILATION, EXHAUST
 ETC, PERHAPS THE PERMIT AND PLANS SHOULD ALL BE REVISED
 TO ONLY INCLUDE BUILD OUT OF THE TENANT SPACE AND ALL
 WILL NOT INCLUDE THE GENERATOR OR ASSOCIATED EQUIPMENT
 AT THIS TIME.
  
  
 ** PREVIOUS REVIEW COMMENT REVIEW #3**
 PLEASE KNOW THE FIRST TIME THE MANUFACTURE SPECS/CUT
 SHEETS FOR THE GEN, ETC WERE SUBMITTED ON THE 3RD
 REVIEW AND NOTHING MATCHED. PLEASE SEE PREVIOUS NOTES
 WHICH MENTIONS SPEC SUBMITTED FOR A GASOLINE GENERATOR
 AND ETC.
 PLEASE SEE GEN SUBMITTED IS NOW A LP/NAT GAS UNIT,
 HOWEVER PLEASE SEE PLEASE SUBMIT THE
 MANUFACTURES SPEC/CUT SHEETS FOR THE GENERATOR, ATS,
 AND WP HOUSING.
 PLEASE SEE THAT THIS 3RD REVIEW AND THIS IS FIRST TIME
 ANY PAPER WORK WAS SUBMITTED HOWEVER THERE IS PAPERWORK
 SUBMITTED WHICH DO NOT APPLY AT ALL TO GEN ETC. PLEASE
 SEE "PARTS LIST" BOOK FOR GASOLINE ENGINES FORM FORD
 MOTOR CORP?
 PLEASE SEE WARRANTY BOOKS; PLEASE SEE MULTIPLE ATS
 BOOKS AND SHEETS AND SOME ARE NOT THE SAME
 EQUIPMENT???
  
 ** PLEASE SUBMIT TWO COMPLETE SETS, WITH ONLY PERTINENT
 SHEETS RELEVANT TO THIS INSTALLATION. PLEASE PLACE
 THESE SHEETS INTO SETS BOUND TOGETHER IN A NEAT AND
 ORDERLY FASHION WITH LABELS OR TABS FOR REVIEW AND
 STAMPING.
  
 FBC 106.1, 106.1.2, 110.3, 90.7 ETC.
  
 2) NOTE: PLEASE SEE REVIEW NOTE #3 FROM THE PREVIOUS
 REVIEW.
 PLEASE SEE NOT ENERGY CALCULATIONS/LIGHTING POWER
 DENSITIES FOR CODE COMPLIANCE WERE SUBMITTED. PLEASE
 SEE NOTE BELOW WHICH SPEAKS OF THE "BLOCK" LOCATED ON
 PLANS WHICH DID NOT PROVIDE THE INFORMATION AS NEEDED
 AND REQUIRED PER 13-415.1.AB.1, 13-415.2.
  
 *** PREVIOUS REVIEW NOTE REVIEW, REVIEW #4DATED
 11/16/06**
 NO, PLEASE SEE SAME NOTE AS PREVIOUSLY STATED. THIS
 WAS REQUIRED AND STATED ON THE FIRST AND ORIGINAL
 REVIEW ON 02/15/06. PLEASE SEE NOTE #10. PLEASE SEE
 REVIEW #2, IT WAS THOUGHT THE CALCULATIONS REQUIRED
 WERE SUBMITTED AND IN PACKAGE, HOWEVER COULD NOT BE
 LOCATED IN 3RD SUBMITTED SETS OR PACKAGE? PLEASE SEE
 THAT THIS WAS PREVIOUSLY STATED ON PREVIOUS REVIEW.
 PLEASE SEE NOW THE RESPONSE IS SHOWING A SMALL BOX WITH
 A FIGURE SHOWN FOR THIS HOWEVER THIS AS SHOWN IS NOT
 ENOUGH AND PLEASE SEE SECTIONS AS PREVIOUSLY
 REFERENCED.
 PLEASE SEE NOTE BELOW WHICH WAS FROM PREVIOUS REVIEW(S)
 AND SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING CALCULATIONS FOR LIGHTING POWER
 DENSITIES, PER FBC
 2004, 13-.AB.1, 13-415.2, 13-415.2.ABC.1, TABLES
 415.2.C.1/415.2.B.1. IT WAS THOUGHT THESE WERE
 SUBMITTED FOR COMPLIANCE WITH THE PREVIOUS REVIEW
 COMMENTS FOR CHAPTER 13, HOWEVER THESE COULD NOT BE
 LOCATED IN PACKAGE. IN EITHER CASE, PLEASE SUBMIT.
  
  
  
 ** NEW NOTE FOR REVIEW NUMBER 5***
  
 1) NOTE: PLEASE CORRELATE PLANS AND LAYOUT OF
 MAINS/PANELS AND DISCONNECTS ON RISER WITH THAT OF THE
 LAYOUT SHOWN ON E-5.
 PLEASE SEE THE MAIN DISCONNECT FOR THE SECONDARY SIDE
 OF THE TRANSFORMER COULD NOT BE CLEARLY LOCATED.
  
 2) NOTE: PLEASE SEE AS PLANS ARE NOW INDICATING THE
 LOCATION OF ALL EQUIPMENT BEING MOVED TO THE NEW
 LOCATION PLEASE CLARIFY THIS AS THE SUBMITTAL BOOKS FOR
 THE NEW STRUCTURAL MEZZANINE LEVEL FROM PREVIOUS
 SUBMITTED PLANS ARE STILL BEING SUBMITTED. PLEASE SEE
 ANY BUILDING REVIEW COMMENTS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-20 06:52:55REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-06 Cont ID  
Sent By dpalmer Date 2006-11-06 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2006-11-06 Time 07:10 Sent To I
Notes
2006-11-06 10:40:53*** UNSAT 4TH REVIEW ***
  
 ** PLEASE SEE NOTES FROM THE THREE PREVIOUS REVIEWS AS
 FOLLOWS.
  
  
 1) NOTE:NO, COMMENT NOT FULLY ADDRESSED. PLEASE SEE
 SPECS WERE SUBMITTED, HOWEVER AS REQUESTED IN THE
 PREVIOUS REVIEWS PLEASE BE SURE ALL EQUIPMENT
 CORRELATES FOR USE AND INSTALLATION ETC.
 PLEASE SEE THE ATS SPECS ARE LISTED AND FOR USE FOR A
 FIRE PUMP AND SPECIFIES MANY ITEMS FOR NFPA-20?? PLEASE
 SEE THIS SYSTEM IS PER NFPA-110, 70 AND EQUIPMENT SHALL
 BE LISTED FOR THE INTENDED USE. PLEASE SEE THE GEN
 SPECS NOW SUBMITTED STATE CLEARLY A MINIMUM OF
 3FT/1METER ON ALL SIDES,, HOWEVER AS STATED REQUIRES
 MORE CLEARANCE WHEN INSTALLED IN A WP HOUSING FOR DOORS
 ETC. PLEASE SEE SPACE AS SHOWN DOES NOT SEEM TO MEET
 THE MINIMUM CLEARANCES FOR UNIT WITH THE WP ENCLOSURE.
 PLEASE SEE AS NOTE ON SPECS MENTIONS TO PROVIDE
 ADDITIONAL SPACE FOR DOORS, THIS INFORMATION IS NOT
 SHOWN ON THE ENCLOSURE SPECS AS SUBMITTED.
 PLEASE SEE OTHER COMMENTS FOR VENTILATION IN SPECS.
 PLEASE SEE SPECS DO NOT INDICATE THE SPECIFIC UNIT AND
 KW RATING, NOTE MENTIONS TO SEE NAMEPLATE, HOWEVER AS
 THIS IS NOT POSSIBLE, THE KW RATING AS SHOWN ON PLANS
 INDICATES 42KW, AND THE NEED TO CORRELATE THE
 MANUFACTURES SPECS AND SIZE OF THE UNIT AND WP IS OF
 THE UTMOST IMPORTANCE.
 PLEASE SEE THE CLOSEST UNIT SIZE AND MODEL IS THE 83"
 LONG, 40" WIDE AND 72" IN HEIGHT.
 PLEASE KNOW AS THE UNIT AND ENCLOSURE IS NOT SPECIFIED
 WE ARE UNABLE TO VERIFY.
 PLEASE ALSO SEE AS SHOWN THE EXHAUST IS STRAIGHT OUT OF
 THE TOP AS SHOWN ON HOUSING AND THE SPACE BELOW THE
 UPPER LEVEL FROM THE PARKING DECK DOES NOT PROVIDE
 CLEARANCE IF THE UNIT IS 72" HIGH.
 PLEASE SEE COMMENTS FROM MECHANICAL, PLUMBING AND FIRE
 AND POSSIBLE BLDG COMMENTS NOW THAT THE SPECS ON
 EQUIPMENT HAVE BEEN SUBMITTED.
 PLEASE SEE OTHER COMMENTS WHICH REQUIRE READY ACCESS.
  
 ** PLEASE KNOW BASED ON THESE COMMENT FOR THE
 GENERATOR, AND THE POSSIBILITY THAT THE GENERATOR MAY
 NOT BE PERMITTED TO BE INSTALLED AT THIS LOCATION DUE
 TO MINIMUM CLEARANCES, ACCESS, VENTILATION, EXHAUST
 ETC, PERHAPS THE PERMIT AND PLANS SHOULD ALL BE REVISED
 TO ONLY INCLUDE BUILD OUT OF THE TENANT SPACE AND ALL
 WILL NOT INCLUDE THE GENERATOR OR ASSOCIATED EQUIPMENT
 AT THIS TIME.
  
  
 ** PREVIOUS REVIEW COMMENT REVIEW #3**
 PLEASE KNOW THE FIRST TIME THE MANUFACTURE SPECS/CUT
 SHEETS FOR THE GEN, ETC WERE SUBMITTED ON THE 3RD
 REVIEW AND NOTHING MATCHED. PLEASE SEE PREVIOUS NOTES
 WHICH MENTIONS SPEC SUBMITTED FOR A GASOLINE GENERATOR
 AND ETC.
 PLEASE SEE GEN SUBMITTED IS NOW A LP/NAT GAS UNIT,
 HOWEVER PLEASE SEE PLEASE SUBMIT THE
 MANUFACTURES SPEC/CUT SHEETS FOR THE GENERATOR, ATS,
 AND WP HOUSING.
 PLEASE SEE THAT THIS 3RD REVIEW AND THIS IS FIRST TIME
 ANY PAPER WORK WAS SUBMITTED HOWEVER THERE IS PAPERWORK
 SUBMITTED WHICH DO NOT APPLY AT ALL TO THIS GEN ETC.
 PLEASE SEE "PARTS LIST" BOOK FOR GASOLINE ENGINES FORM
 FORD MOTOR CORP?
 PLEASE SEE WARRANTY BOOKS; PLEASE SEE MULTIPLE ATS
 BOOKS AND SHEETS AND SOME ARE NOT THE SAME
 EQUIPMENT???
  
 ** PLEASE SUBMIT TWO COMPLETE SETS, WITH ONLY PERTINENT
 SHEETS RELEVANT TO THIS INSTALLATION. PLEASE PLACE
 THESE SHEETS INTO SETS BOUND TOGETHER IN A NEAT AND
 ORDERLY FASHION WITH LABELS OR TABS FOR REVIEW AND
 STAMPING.
  
 FBC 106.1, 106.1.2, 110.3, 90.7 ETC.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE SAME NOTE AS PREVIOUSLY STATED.
 THIS WAS REQUIRED AND STATED ON THE FIRST AND ORIGINAL
 REVIEW ON 02/15/06. PLEASE SEE NOTE #10. PLEASE SEE
 REVIEW #2, IT WAS THOUGHT THE CALCULATIONS REQUIRED
 WERE SUBMITTED AND IN PACKAGE, HOWEVER COULD NOT BE
 LOCATED IN 3RD SUBMITTED SETS OR PACKAGE? PLEASE SEE
 THAT THIS WAS PREVIOUSLY STATED ON PREVIOUS REVIEW.
 PLEASE SEE NOW THE RESPONSE IS SHOWING A SMALL BOX WITH
 A FIGURE SHOWN FOR THIS HOWEVER THIS AS SHOWN IS NOT
 ENOUGH AND PLEASE SEE SECTIONS AS PREVIOUSLY
 REFERENCED.
 PLEASE SEE NOTE BELOW WHICH WAS FROM PREVIOUS REVIEW(S)
 AND SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING CALCULATIONS FOR LIGHTING POWER
 DENSITIES, PER FBC
 2004, 13-.AB.1, 13-415.2, 13-415.2.ABC.1, TABLES
 415.2.C.1/415.2.B.1. IT WAS THOUGHT THESE WERE
 SUBMITTED FOR COMPLIANCE WITH THE PREVIOUS REVIEW
 COMMENTS FOR CHAPTER 13, HOWEVER THESE COULD NOT BE
 LOCATED IN PACKAGE. IN EITHER CASE , PLEASE SUBMIT.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-06 07:10:31REMOVED FROM INCOMING. IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 14:15 Sent To  
Notes
2006-09-24 00:00:00*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE NOTES FROM THE TWO
 PREVIOUS REVIEW AS FOLLOWS.
  
  
 1) NOTE: PLEASE SUBMIT THE
 MANUFACTURES/SPEC CUT SHEETS FOR THE
 GENERATOR, ATS, AND WP HOUSING.
 PLEASE SEE THAT THIS 3RD REVIEW IS FIRST
 TIME ANY PAPER WORK WAS SUBMITTED,
 HOWEVER THERE IS PAPERWORK SUBMITTED
 WHICH DO NOT APPLY AT ALL TO THIS GEN
 ETC.
 PLEASE SEE "PARTS LIST" BOOK FOR
 GASOLINE ENGINES FORM FORD MOTOR CORP?
 PLEASE SEE WARRANTY BOOKS, PLEASE SEE
 MULTIPLE ATS BOOKS AND SHEETS AND SOME
 ARE NOT THE SAME EQUIPMENT???
  
 ** PLEASE SUBMIT TWO COMPLETE SETS, WITH
 ONLY PERTINENT SHEETS RELEVANT TO THIS INSTALLATION.
 PLEASE PLACE THIS SHEETS
 INTO SETS BOUND TOGETHER IN A NEAT AND
 ODERLY FASHION WITH LABELS OR TABS FOR
 REVIEW AND STAMPING.
  
 FBC 106.1, 106.1.2, 110.3, 90.7 ETC.
  
 2) NOTE: PLEASE SEE THE "S" SHEETS STILL
 DO NOT CONTAIN THE CORRECT INFORMATION
 AS REQUIRED UNDER THE FLORIDA
 ADMINSTRATIVE CODE 61G15-23.002, FLORIDA
 STATUES 471.023.
 THIS IS THE 3RD REVIEW FOR THIS NOTE.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER. PLEASE KNOW, "S"
 SHEETS MAY BE RETAINED BY THIS OFFICE
 AND FORWARDED TO THE FBPE'S.
  
 3) NOTE: PLEASE SEE MISSING CALCULATIONS
 FOR LIGHTING POWER DENSITIES, PER FBC
 2004, 13-.AB.1, 13-415.2,13-415.2.ABC.1,
 TABLES 415.2.C.1/415.2.B.1. IT WAS
 THOUGHT THESE WERE SUBMITTED FOR
 COMPLIACNE WITH THE PREVIOUS REVIEW
 COMMENTS FOR CHAPTER 13, HOWEVER THESE
 COULD NOT BE LOCATED IN PACKAGE. IN
 EIHTER CASE , PLEASE SUBMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By dpalmer Date 2006-07-02 Time 09:53 Rev Time 0.00
Received By dpalmer Date 2006-07-02 Time 08:42 Sent To  
Notes
2006-07-02 00:00:00*********** UNSAT 2ND REVIEW ***********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO SOME MINOR CHANGED ITEMS.
  
 ** PLEASE KNOW, PLANS/SUBMITTED
 MATERIALS ARE NOT COMPLETE AT THIS TIME
 FOR A COMPLETE REVIEW.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM THE PREVIOUS REVIEW.
  
 ****************************************
  
 1A)NOTE: NO , PLEASE SEE SOME SHEETS IN
 SETS ARE STILL SHOWN WITH SEAL WHICH IS
 NO LONGER VALID. (S-SHEETS).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.001
 WHICH REQUIRED THE RAISED
 SEAL TO CHANGE FROM THE WORDING OF
 "CERTIFICATE" TO "LICENSE" BY 2/5/04,
 HOWEVER AN EXTENSION WAS GRANTED BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 TO DECEMBER 31,2005.
 PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE
 WORDING ON RAISED SEAL AS REQUIRED.
 FS 471.025
 ANY SEALED PLANS SHALL BECOME "VOID".
 PLEASE BE SURE THE NEW RAISED SEAL
 CONTAINS THE "LICENSE" WORDING.
 PLEASE CONTACT THIS OFFICE OR THE FBPE'S
 IF THERE ARE ANY QUESTIONS.
  
 ***************************************
  
  
 1) NOTE; OK, HOWEVER SEE NEXT NOTE.
  
 2) NOTE:OK, HOWEVER PLEASE SEE THAT
 THE 3POLE 125A BRKR ON GEN SHALL BE
 "SHUNT TRIP" TYPE AND THE SHUNT TRIP
 BUTTON SHALL BE GROUPED WITH THE OTHER
 PUSHBUTTONSBEING PROVIDED AT THE FIRST
 FLR GENERATOR ANNUCIATOR PANEL/FIRE
 ALARM PANEL LOCATION.
  
 ** PREVIOUE NOTE **
 PLEASE SEE ALL DISCONNECTING
 MEANS FOR POWER FEEDERS ETC SHALL BE
 GROUPED.
 230.72,225.31.
  
 3) NOTE: OK.
  
 4) NOTE:NO, PLEASE SEE THIS WAS NOT
 DONE AND REVIEW OF THESE ITEMS CAN NOT
 BE DONE AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL SPECS/MANFACTURES CUT
 SHEETS FOR GENERATOR, ATS ETC.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE:OK, HOWEVER PLEASE SEE NEW
 GROUNDING DETAIL FOR TRANSFORMER
 INDICATES THE NEUTRAL BEING BONDED AT
 THE TRANSFORMER? PLEASE SEE 250.24B,
 WHICH REQUIRES THE NEUTRAL TO BE BONDED
 AT THE FIRST MEANS OF DISCONNECT HOWEVER
 IN THE SITUATION IT IS PERMITTED. PLEASE
 SEE THAT BONDING OF THE NEUTRAL IN THE
 TRANSFORMER WILL THEN REQUIRE ALL
 GROUNDS AND NEUTRALS TO BE SPLIT AT THE
 PANEL "P" AND WILL REQUIRE SPECIAL
 SIGNAGE FOR THE NOTIFICATION FOR NOT TO
 BOND THE GRND AND THE NEUTRAL BUS AT THE
 PANEL "P" MCB PANEL. WILL ALSO REQUIRE
 THE SAME SIGNAGE TO NOTIFY PERSON OF THE
 BONDING IN THE TRANSFORMER.
 ** PLEASE KNOW, SIGNAGE AND THE ABOVE
 SHALL BE PROVIDED, OR THE DETAIL SHOULD
 NOT HAVE THE NEUTRAL BONDED AT THE
 TRANSFOMER AND THENEUTRAL AND GRNDS
 ARE BONDED AT THE PANEL "P" WHICH WOULD
 BE THE FIRST MEANS OF DISCONNECT. ** *8
 THIS OFFICE HAS SEEN THE SCENERIO ON
 MORE THAN ONE OCCASION WHERE WORK IS
 BEING PERFORMED IN A PANEL AFTER THE
 TRANSFORMER AND THE BONDING SCREW OR
 BONDIGN JUMPER IS ADDED CREATING AN
 OBJECTIONABLE CURRENT PATH AND
 PARALLELING THE NEUTRAL.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE GROUNDING
 ELECTRODE CONNECTION DETAIL(S) FOR THE TRANSFORMER(S).
 250.30, 250.58.
 PLEASE SEE THE CODE SHALL NOT BE
 REFERENCED IN WHOLE OR IN PART IN LEIU
 OF THE TECHNICAL INFORMATION REQUIRED ON
 SAID PLANS.
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: NO, THIS IS THE SAME NOTE AND
 NOTE 1A STILL APPLIES.
 THESE COMMENTS ARE FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL TITLE
 BLOCKS FOR DESIGNERS OF RECORD CONTAIN
 ALL LICENSING INFORMATION AS REQUIRED
 UNDER FAC 61G15-23.002, FS 471.023, THIS
 COMMENT IS NOT FOR STANDROD ENG.\
 PLEASE SEE "S" SHEETS.
  
 14)NOTE: OK.
  
 ** PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH WILL AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO ALLEAVIATE
 ANY DELAY'S IN PROJECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By dpalmer Date 2006-02-15 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2006-02-15 Time 16:30 Sent To  
Notes
2006-02-15 00:00:00*********** UNSAT ***************
  
 ** PLEASE KNOW, PLANS/SUBMITTED
 MATERIALS ARE NOT COMPLETE AT THIS TIME
 FOR A COMPLETE REVIEW.
  
 ****************************************
  
 1A)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001 WHICH
 REQUIRED THE RAISED SEAL TO CHANGE FROM
 THE WORDING OF "CERTIFICATE" TO
 "LICENSE" BY 2/5/04, HOWEVER AN
 EXTENSION WAS GRANTED BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS TO
 DECEMBER 31,2005.
 PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE
 WORDING ON RAISED SEAL AS REQUIRED.
 FS 471.025
 ANY SEALED PLANS SHALL BECOME "VOID".
 PLEASE BE SURE THE NEW RAISED SEAL
 CONTAINS THE "LICENSE" WORDING.
 PLEASE CONTACT THIS OFFICE OR THE FBPE'S
 IF THERE ARE ANY QUESTIONS.
  
 ***************************************
  
  
 1)NOTE; PLEASE SEE LOCATION OF GENERATOR
 LOCATED ON THE 6TH LEVEL IS NOT
 PERMITTED BY THIS OFFICE AND FIRE
 MARSHAL'S OFFICE.
 PLEASE ALSO SEE ELECTRICAL COMMENTS
 PERTAINING LOCATION OF DISCONNECTING
 ETC.
  
 2)NOTE: PLEASE SEE ALL DISCONNECTING
 MEANS FOR POWER FEEDERS ETC SHALL BE
 GROUPED.
 230.72,225.31.
  
 3)NOTE: PLEASE BE SURE PLANS REFERENCE
 THE FOLLOWING APPLICABLE CODES, 2002
 NFPA-70, 2003 NFPA-101, 2002 NFPA-72,
 2002 NFPA-110, 1999 NFPA-75
  
 4)NOTE: PLEASE SUBMIT ALL
 SPECS/MANFACTURES CUT SHEETS FOR
 GENERATOR, ATS ETC.
 IF THE EPSS IS GOING TO BE INSTALLED
 UNDER THIS PERMIT, PLEASE INCLUDE.
  
 5)NOTE: PLEASE SEE 645.10,,300.21 FOR
 LOCATION AND SHUT DOWN OF ELECTRICAL
 REQUIRED FOR A/C'S AND ALL ALL EQUIPMENT
 FEEDING IT ROOM.
 PLEASE SEE A/C SYSTEMS.
  
 6)NOTE: PLEASE SEE 645.5D FOR SD'S AND
 DETAILS REQUIRED FOR REVIEW AND
 CONNECTION INTO THE FA SYSTEM.
  
 7) NOTE: PLEASE SHOW AND IDENTIFY AL
 REQUIREMENTS FOR THE IT ROOM AND
 REFERENCE NFPA-75 ON ALL P,M, E,
 ARCHITECTUAL AND STRUCTUAL PLANS.
 ALL CONTRUCTION, FIRE SPRINKLER
 PROTECTION AND OR OTHER EXTINGUISHING
 SYSTEMS SHALL BE PROVIDED.
 PLEASE MAKE REFERENCE TO THE ROOM
 PENETRATIONS AS REQUIRED PER CHAPTER 3.
 ETC
  
 8)NOTE: PLEASE SEE THAT AN EM BATTERY
 BACK LT OF SOME SORT BE PROVIDED IN THE
 ELECTRICAL ROOM.
 700.16, 101,7.8,7.9 ETC.
  
 9)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE CONNECTION DETAIL(S) FOR THE
 TRANSFORMER(S). 250.30, 250.58.
 PLEASE SEE THE CODE SHALL NOT BE
 REFERENCED IN WHOLE OR IN PART IN LEIU
 OF THE TECHNICAL INFORMATION REQUIRED ON
 SAID PLANS.
  
 10)NOTE: PLEASE SEE THE FBC 2004 CHAPTER
 13. PLEASE SEE 13-413.1ABC.1 FOR VOLTAGE
 DROP OF FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1 FOR LIGHTING
 CONTROL OF SPCES.
 TANDEM WIRING PER 13-415.1.ABC.3, .4
 PLEASE SEE ALL OF CHAPTER 13 FOR
 COMMERCIAL SPACES.
  
 11)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH TEH SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE MANY WSH UNITS, A/C 1&2 UNITS
 ETC.
 215.5
  
 12)NOTE: PLEASE PROVIDE IDENTIFICATION
 ON PLANS FOR ALL FIXTURES AND CORRELATE
 WITH THE FIXTURE LEGEND SUBMITTED.
  
 13)NOTE: PLEASE SEE THAT ALL TITLE
 BLOCKS FOR DESIGNERS OF RECORD CONTAIN
 ALL LICENSING INFORMATION AS REQUIRED
 UNDER FAC 61G15-23.002, FS 471.023, THIS
 COMMENT IS NOT FOR STANDROD ENG.\
 PLEASE SEE "S" SHEETS.
  
 14)NOTE: PLEASE SEE THE COMPLETE
 VALUATION FOR SCOPE OF WORK SHALL
 INCLUDE ALL LABOR AND MATERIALS, EVEN IF
 EQUIPMENT IS OWNER SUPPLIED. PLEASE SEE
 ANY SYSTEM PERMANANTLY INSTALLED,
 HARDWIRED , FASTENED IN PLACE SHALL BE
 INCLUDED.
 FBC ADMINISTRATIVE SECTION 108.3. AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH WILL AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO ALLEAVIATE
 ANY DELAY'S IN PROJECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 15:45 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 15:26 Sent To B
Notes
2007-06-11 15:39:46*****APPROVED*****
  
  
 REVISED PLAN SHEETS A3 AND E2 WERE DATED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-01-25 Cont ID  
Sent By mawillia Date 2007-01-25 Time 15:29 Rev Time 0.00
Received By mawillia Date 2007-01-25 Time 15:29 Sent To  
Notes
2007-01-25 15:33:45*****APPROVED*****
  
  
  
 NO ADDITIONAL FIRE PLAN REVIEW NEEDED UNLESS THERE HAS
 BEEN AN ALTERATION OR REVISION TO THE APPLICABLE PLAN
 SHEET.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By mwennerg Date 2006-10-17 Time 09:53 Rev Time 0.00
Received By mwennerg Date 2006-10-17 Time 09:52 Sent To I
Notes
2006-10-17 09:56:14***PROVISO***
  
 1) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 GENERATOR INSTALLATION. PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS AND ALL OTHER APPLICABLE INFORMATION AT THAT
 TIME.
  
 2) SOFFITTS SHALL NOT INTERFERE WITH FIRE PROTECTION
 EQUIPMENT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-13 Cont ID  
Sent By mwennerg Date 2006-07-13 Time 11:36 Rev Time 0.00
Received By mwennerg Date 2006-07-13 Time 11:36 Sent To  
Notes
2006-07-13 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT THE FIRE REVIEW IS
 OK, HOWEVER PLEASE SEE OTHER REVIEW
 COMMENTS REGARDING FS AND FAC
 REQUIREMENTS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS TO
 BE MOUNTED AT DISTANCES NOT TO EXCEED
 75' TRAVEL DISTANCE REQUIREMENT. PLEASE
 ILLUSTRATE ON LS-1.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By nmccray Date 2006-03-01 Time 11:15 Rev Time 0.00
Received By nmccray Date 2006-02-27 Time 11:12 Sent To  
Notes
2006-03-01 00:00:00DENIED:
  
 1) THIS PROJECT SHALL COMPLY WITH NFPA
 101 LIFE SAFETY CODE, 2003 EDITION AND
 NFPA 1 UNIFORM FIRE CODE, 2003 EDITION.
  
 2) ON SHEET A1 DOOR #182 SHOULD SWING IN
 THE DIRECTION OF TRAVEL.
  
 3) PLEASE PROVIDE CUT SHEETS AND SPEC'S
 ON EQUIPMENT BEING INSTALLED.
  
 4) THE GENERATOR IS NOT PERMITTED ON 6TH
 FLOOR, PLEASE REFERENCE AND COMPLY WITH
 NFPA 110 STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS, 2002 EDITION, FOR
 LOCATION, INSTALLATION, AND OTHER
 REQUIREMENT.
  
 5) PLEASE REFERENCE AND COMPLY WITH NFPA
 801 STANDARD FOR FIRE PROTECTION FOR
 FACILITIES HANDLING RADIOACTIVE
 MATERIALS, 1998 EDITION. ( X-RAY,
 MAGNETIC, AND NUCLEAR EQUIPMENT )
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-01-16 Cont ID  
Sent By kstevens Date 2007-01-16 Time 18:22 Rev Time 0.00
Received By kstevens Date 2007-01-16 Time 18:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By kstevens Date 2006-08-03 Time 08:13 Rev Time 0.00
Received By kstevens Date 2006-08-03 Time 08:13 Sent To  
Notes
2006-08-03 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. OK
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT GENERATOR SHALL
 VENT OUT OF THE STRUCTURE AND ABOVE THE
 ROOF LEVEL.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO MANUF. SPECIFICATION SHEETS
 SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By kstevens Date 2006-03-13 Time 18:41 Rev Time 0.00
Received By kstevens Date 2006-03-13 Time 18:41 Sent To  
Notes
2006-03-13 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 15:55 Sent To E
Notes
2007-06-28 15:55:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-30 Cont ID  
Sent By adarroug Date 2007-05-30 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-05-30 Time 13:16 Sent To M
Notes
2007-05-30 13:16:31TO "HMOSER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 16:16 Sent To  
Notes
2007-05-22 09:44:49TO "COMM" BD#61
2007-05-10 16:17:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 08:37 Sent To M
Notes
2007-05-08 08:38:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:36 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:36 Sent To  
Notes
2006-12-12 10:00:38TO "COMM" BD#48
2006-11-29 19:37:13WAITING FOR COMMERCIAL BOARD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-06 Cont ID  
Sent By adarroug Date 2006-11-06 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-11-06 Time 10:58 Sent To  
Notes
2006-11-07 14:13:49TO "COMM" BD#39
2006-11-06 10:59:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 11:29 Sent To  
Notes
2006-09-20 00:00:00TO "COMM" BD#38
2006-09-15 00:00:00WAITING FOR "COMM" BD-NEW SHEETS FOR
 ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 09:19 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 09:19 Sent To  
Notes
2006-06-28 00:00:00TO "COMM" BD#38
2006-06-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-06 Cont ID  
Sent By sgraham Date 2006-03-21 Time 09:23 Rev Time 0.00
Received By alange Date 2006-01-06 Time 11:06 Sent To  
Notes
2006-02-02 00:00:00TO "COMM" BD#29/PLANS ON RACK
2006-01-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-05-31 Cont ID  
Sent By hmoser Date 2007-05-31 Time 15:03 Rev Time 0.00
Received By hmoser Date 2007-05-31 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-05-16 Cont ID  
Sent By rregueir Date 2007-05-16 Time 11:30 Rev Time 0.00
Received By rregueir Date 2007-05-11 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-12-13 Cont ID  
Sent By hmoser Date 2006-12-13 Time 13:35 Rev Time 0.00
Received By hmoser Date 2006-12-13 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-10 Cont ID  
Sent By hmoser Date 2006-10-10 Time 12:56 Rev Time 0.00
Received By hmoser Date 2006-10-10 Time 12:56 Sent To  
Notes
2006-10-10 14:06:26PASS PROVISO. ADDITIONAL PERMIT REQUIRED FOR GENERATOR
 .PLEASE PROVIDE EXHAUST ON PLANS,AND EXHAUST
 TERMINATION ON PLANS.PLAN REVIEW BY HAROLD MOSER
 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By hmoser Date 2006-07-20 Time 11:23 Rev Time 0.00
Received By hmoser Date 2006-07-20 Time 11:03 Sent To  
Notes
2006-07-20 00:00:00PLAN DENIED
 1) PLEASE PROVIDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS ON THE
 GENORATOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-09 Cont ID  
Sent By hmoser Date 2006-02-09 Time 17:44 Rev Time 0.00
Received By hmoser Date 2006-02-09 Time 17:44 Sent To  
Notes
2006-02-09 00:00:00PLAN DENIED
 1- PLEASE PROVIDE A UL LISTED FLOOR
 PENETRATION ASSEMBLY FOR THE REFRIGERANT
 LINES ON A/C 1,2.
 2- PLEASE PROVIDE A COPY OF THE
 MANUFACTURERS INSTALLATION INSTRUCTIONS
 FOR THE GENERATOR.
 3- PLEASE PROVIDE ON THE PLANS THE TYPE
 OF FUEL USED FOR THE GENERATOR.LOCATION
 OF FILL PIPE AND VENT LINE. AND LOCATION
 OF FUEL TANK IF THERE IS ONE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 13:21 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 13:21 Sent To  
Notes
2007-06-09 13:22:18REVISION OKSHTS P2 & P4

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-18 Cont ID  
Sent By kstevens Date 2007-01-16 Time 18:22 Rev Time 0.00
Received By kstevens Date 2007-01-16 Time 18:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-11 Cont ID  
Sent By kstevens Date 2006-10-11 Time 18:46 Rev Time 0.00
Received By kstevens Date 2006-10-11 Time 18:46 Sent To  
Notes
2006-10-11 18:50:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. OK
 2. OK - PLANS SHOW TILE TO 4'
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. OK
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT GENERATOR SHALL
 VENT OUT OF THE STRUCTURE AND ABOVE THE
 ROOF LEVEL.
 ****NO RESPONSE, NOT ADDRESSED - SEE
 ATTACHED SHEET CONCERNING THE EXHAUST
 FROM THE GENERATOR FROM THE MANUF. SPECIFICATIONS.
 C.OK
 9.OK
 10. OK
 11. OK
 12. OK
  
 **************NEW COMMENT**************
  
 1B. FROM LOOKING AT THE MSDS SHEETS, A
 EYE WASH/EMERGENCY SHOWER WILL BE
 REQUIRED. SECTION 411.
 ****NO RESPONSE, NOT ADDRESSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-02 Cont ID  
Sent By kstevens Date 2006-08-02 Time 16:19 Rev Time 0.00
Received By kstevens Date 2006-08-02 Time 16:18 Sent To  
Notes
2006-08-02 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A1 ROOM 108 STAFF TOILET SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING THE FOLLOWING:
 FOR THE W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR THE LAV
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 FOR THE TOILET ROOM
 A. 11-4.22.3 A 5' TURNING AREA IS
 REQUIRED.
 ****RESPONSE NOTED, BUT ELEVATIONS
 INDICATED ON SHEET A1, (A7 44, 45), ARE
 NOT ON SHEET A7. PLEASE CLARIFY.
  
 2. SHT A4 SUBMIT INFORMATION ON THE
 VINYL WALL PAPER SHOWING COMPLIANCE WITH
 SECTION 1210.2. WALLS SHALL BE
 NONABSORBENT.
 ****RESPONSE NOTED, BUT CODE SECTION
 1210.2 STATES "WALLS WITHIN 2FT OF
 URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A
 HEIGHT OF 4 FEET ABOVE THE FLOOR. THE
 INTENT OF THE CODE IS ALSO FOR CLEAN UP
 OF THE WALLS. PLEASE SUBMIT A SAMPLE OF
 THE WALL COVERING SO COMPLIANCE CAN BE DETERMINED.
  
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. OK
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT GENERATOR SHALL
 VENT OUT OF THE STRUCTURE AND ABOVE THE
 ROOF LEVEL.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO MANUF. SPECIFICATION SHEETS
 SUBMITTED.
  
 9.OK
 10. OK
 11. OK
 12. OK
  
 **************NEW COMMENT**************
  
 1B. FROM LOOKING AT THE MSDS SHEETS, A
 EYE WASH/EMERGENCY SHOWER WILL BE
 REQUIRED. SECTION 411.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By kstevens Date 2006-03-13 Time 16:42 Rev Time 0.00
Received By kstevens Date 2006-03-13 Time 16:42 Sent To  
Notes
2006-03-13 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A1 ROOM 108 STAFF TOILET SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING THE
 FOLLOWING:
 FOR THE W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR THE LAV
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 FOR THE TOILET ROOM
 A. 11-4.22.3 A 5' TURNING AREA IS
 REQUIRED.
 2. SHT A4 SUBMIT INFORMATION ON THE
 VINAL WALL PAPER SHOWING COMPLIANCE WITH
 SECTION 1210.2. WALLS SHALL BE
 NONABSORBENT.
 3. SHTS A6 & A7 TOILET ROOM DETAILS 7
 THRU 10, 22, 23, 26, 27, 34 THRU 37.
 SHOW THE FOLLOWING:
 FOR THE LAVS
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 4. SHT A6 DETAIL #11 SHOW THE FOLLOWING:
 FOR THE DRINKING FOUNTAIN:
 A. 11-4.15.2 SPOUT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.19.5 CLEARANCES & CLEAR FLOOR
 SPACE.
 5. SHT A7 DETAILS 30 & 32 SHOW THE
 FOLLOWING FOR THE SINKS.
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED. CABINET DOORS TO BE
 REMOVED AS THEY CAN NOT BE IN THE CLEAR
 FLOOR SPACE)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 6. ALL PME SHEETS THAT WILL BE
 RESUBMITTED SHALL HAVE THE NEW SEALS PER
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 RULE. (SEE ATTACHED SHEET).
 7. SHT P1 CODE REFERENCED IS FBC-2001.
 WE HAVE ADOPTED FBC-2004 SINCE 10-01-05
 AND ALL PLANS SHALL BE DESIGNED TO THE
 FBC-2004 AND PLANS SHALL REFERENCE THE
 2004 CODE AS WELL.
 8. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 9. SHT P3 GAS RISER NOTE #1 REFERENCES
 FBC-2001 FUEL GAS CODE. GAS CODE IN
 EFFECT IS FBC-2004 FUEL GAS. PLEASE
 CHANGE REFERENCE, AND DESIGN TO THE
 PROPER CODE.
 10. SHT P4 FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK
 OR A HUB DRAIN IS REQUIRED. SECTIONS
 803.2 AND 802.3.2.
 11. SHT P4 DOMESTIC WATER ISOMETRIC
 RISER. WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9 AT THE WASH MACHINE
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUFACTURE
 INSTALLATION INSTRUCTIONS.
 12. SHT P4 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED AT THE TOP OF
 ALL WATER DOWN-FEED PIPES. SECTION
 606.1(4).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2007-01-12 Cont ID  
Sent By eschneid Date 2007-01-12 Time 12:13 Rev Time 0.00
Received By eschneid Date 2007-01-12 Time 12:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-11-07 Cont ID  
Sent By eschneid Date 2006-11-07 Time 09:32 Rev Time 0.00
Received By eschneid Date 2006-11-07 Time 09:32 Sent To  
Notes
2006-11-07 09:36:16FAILED
  
 THE CONSTRUCTION OF A MEZZANINE LEVEL TO HOUSE THE
 GENERATOR REQUIRES THE ADDITION OF PROPORTIONATE
 PARKING FOR THE NEW SQUARE FOOTAGE.PLEASE PROVIDE A
 REVISED PARKING TABLE WHICH INCLUDES THE MEZZANINE
 SQUARE FOOTAGE.
  
 ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status N Date 2006-10-17 Cont ID  
Sent By rbrown Date 2006-10-17 Time 13:08 Rev Time 0.00
Received By rbrown Date 2006-10-17 Time 13:08 Sent To  
Notes
2006-10-17 13:29:45PER 10/16/06 E-MAIL FROM ERIC SCHNEIDER, NO ZONING
 REVIEW IS REQUIRED BECASE "THE GENERATOR IS INSIDE AND
 DID NOT REMOVE A PARKING SPACE".

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-21 Cont ID  
Sent By sgraham Date 2006-03-21 Time 08:00 Rev Time 0.00
Received By sgraham Date 2006-03-21 Time 09:23 Sent To I
Notes
2006-03-21 00:00:00LOCATION OF GENERATOR OK