Plan Review Details - Permit 06010060
Plan Review Stops For Permit 06010060
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-09 Cont ID  
Sent By alange Date 2006-11-09 Time 09:04 Rev Time 0.00
Received By alange Date 2006-11-09 Time 09:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-22 Cont ID  
Sent By alange Date 2006-08-22 Time 08:31 Rev Time 0.00
Received By alange Date 2006-08-22 Time 08:31 Sent To  
Notes
2006-08-22 00:00:00STRUCTURAL REVISIONS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-06 Cont ID  
Sent By alange Date 2006-07-06 Time 11:16 Rev Time 1.00
Received By alange Date 2006-07-06 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-08 Cont ID  
Sent By alange Date 2006-05-08 Time 15:41 Rev Time 1.00
Received By alange Date 2006-05-08 Time 15:40 Sent To  
Notes
2006-05-08 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PRODUCT APPROVALS REQUIRED FOR STORE
 FRONT SYSTEM AND EXTERIOR DOORS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 6.SHOW GUARDRAIL SPECIFICATIONS
 COMPLYING WITH 1012.3 FOR OPENINGS AND
 1607.1.1 FOR LOADS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By alange Date 2006-04-07 Time 14:29 Rev Time 3.00
Received By alange Date 2006-04-07 Time 13:39 Sent To  
Notes
2006-04-07 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PRODUCT APPROVALS REQUIRED FOR STORE
 FRONT SYSTEM.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 6.SHOW GUARDRAIL SPECIFICATIONS
 COMPLYING WITH 1012.3 FOR OPENINGS AND
 1607.1.1 FOR LOADS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 11:18 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 11:07 Sent To  
Notes
2006-06-24 00:00:00**ELECTRICAL STAMPED.
  
 10% RESUB FEE ADDED AS PLANS ARE IN
 REVIEW FOR THE 3RD TIME.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-01 Cont ID  
Sent By dpalmer Date 2006-05-01 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2006-05-01 Time 19:25 Sent To  
Notes
2006-05-01 00:00:00********* UNSAT *************
  
 1) NOTE: PLEASE SEE NEW SHEET 1.2 AND
 2.1 NOT SIGNED , DATED AND SEALE DBY THE
 SAID ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221.
 THIS IS THE ONLY COMMENT FOR ELECTRICAL
 REVIEW. TECHNICAL COMMENTS ADDRESSED.
 PLEASE KNOW, "IF" ALL COMMENTS FROM ALL
 OTHER REVIEWS ARE PASSED AND THE ONLY
 COMMENT IS FOR ARCHITECT TO SIGN AND
 SEAL PLANS, PLEASE CALL TO SET UP AN
 APPOINTMENT FOR ARCHITECT TO COME DOWN
 AND DO SO. IF THERE ARE ANY OTHER
 COMMENTS FROM OTHER TRADES, PLEAS HAVE
 THE ARCHITECT SIGN, DATED AND SEAL PLANS
 AT THAT TIME.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 15:18 Sent To  
Notes
2006-03-29 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE SEE NOTE MENTIONS "NEW
 LIGHT" ? HOWEVER NO NEW LIGHTS WERE
 FOUND ON PLANS??
 PLEASE CLARIFY NEW EGRESS LIGHTING PER
 NFPA-101 7.8,7.9.
 PLEASE KNOW, BATTERY BACK UP FIXTURE OF
 SOME SORT WILL BE REQUIRED TO ILLUMINATE
 EGRESS TO THE PUBLIC RIGHT OF WAY. IF
 EXISTING, PLEASE SHOW.
  
 2)NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS FOR NEW 20A CIRCUITS AS NOTED.
 PLEASE SEE NO CONTROL OF FANS, OR WHERE
 "J-BOXES" ARE FED, CONTROLS? LIGHTS? GFI
 ? IF CIRCUITS FOR ALL OF WHAT IS BEING
 SHOWN ARE COMING FROM THESE TWO NEW 20A
 CIRCUITS, THEN, SHOW WHICH CIRCUIT IS
 FEEDING WHICH DEVICE.
 PLEASE INDICATE THE SPARE SPACES AND
 PANEL THESE ARE COMING FROM.
 215.5
  
  
 ** PLEASE SEE COMMENTS FROM BLDG REVIEW,
 AS STRUCTURAL ENGINEER LISTED ON COVER
 SHEET IS NOT THE ENGINEER ON PLANS.
 THIS IS NOT AN ELECTRICAL REVIEW
 COMMENT.
  
 ** PLEASE SEE ANY NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE COMPLETELYREMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 13:56 Sent To  
Notes
2006-07-03 00:00:00IT HAS BEEN NOTED THAT NEW OCCUPANT LOAD
 CALCULATION SUBMITTED INDICATES AN
 OCCUPANT LOAD OF LESS THAN 300.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By mwennerg Date 2006-05-09 Time 10:23 Rev Time 0.00
Received By mwennerg Date 2006-05-09 Time 10:23 Sent To  
Notes
2006-05-09 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT (9) COMMENTS WERE
 ATTACHED TO THE FIRST REVIEW, HOWEVER
 THIS WRITER IS UNABLE TO LOCATE ANY
 RESPONSES. PLEASE SEE THAT I HAVE
 INCLUDED THE FIRST REVIEW WITH THIS
 RESUBMITTAL. PLEASE ADDRESS ALL COMMENTS
 TO HELP EXPEDITE THIS PROCESS.
  
 2) FIRE SPRINKLER DRAWINGS WERE INCLUDED
 WITH THIS RESUBMITTAL. PLEASE NOTE THAT
 SEPARATE PERMITTING IS REQUIRED FOR FIRE
 SPRINKLER REMODEL. UNSEALED PLANS MAY BE
 USED IF WORK INVOLVES LESS THAN (50)
 SPRINKLER HEADS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By mwennerg Date 2006-04-07 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2006-04-07 Time 10:39 Sent To  
Notes
2006-04-07 00:00:00******DENIED******
  
 1) CODE INFORMATION INDICATES AN
 OCCUPANT LOAD OF 308. PLEASE NOTE THAT A
 FIRE ALARM SYSTEM IS REQUIRED IN
 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOAD
 OF 300 OR MORE.
  
 2) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED REGARDING LIFE SAFETY.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR BOTH THE FIRE SPRINKLER
 REMODEL AND FIRE ALARM SYSTEM. FIRE
 ALARM TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR NEW HANDRAILS AND
 GUARDS.
  
 6) PLEASE ILLUSTRATE ALL NEW OR EXISTING
 EXIT LIGHT AND EMERGENCY LIGHT
 LOCATIONS.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL MEET THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 8) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 9) PLEASE PROVIDE MORE INFORMATION/FLAME
 RETARDANT FOR CANVAS ROOF.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 18:07 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 18:07 Sent To B
Notes
2006-11-04 18:08:10TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 10:10 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 10:10 Sent To B
Notes
2006-08-15 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 10:43 Sent To  
Notes
2006-06-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 15:32 Sent To  
Notes
2006-05-01 00:00:00TO "COMM" BD#63
2006-04-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 10:22 Sent To  
Notes
2006-03-24 00:00:00TO COMM BOARD #5

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 08:58 Sent To  
Notes
2006-03-23 00:00:00FROM ZONING ON 3/22/06, WAITING FOR
 COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-02 Cont ID  
Sent By ebowers Date 2006-03-21 Time 14:40 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 10:43 Sent To  
Notes
2006-03-02 00:00:00WAITING FOR "COMM" BD-OK TO SEND THRU
 REVIEW PROCESS PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 08:52 Sent To Z
Notes
2006-02-24 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-01 Cont ID  
Sent By lmartine Date 2006-01-31 Time 17:37 Rev Time 0.00
Received By lmartine Date 2006-01-04 Time 09:32 Sent To  
Notes
2006-01-23 00:00:001/23/06-PLANS ROUTED TO ZONING BY
 "LMARTINEZ"
2006-01-04 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-21 Cont ID  
Sent By sgraham Date 2006-01-23 Time 15:41 Rev Time 0.00
Received By ebowers Date 2006-03-21 Time 14:39 Sent To I
Notes
2006-03-21 00:00:00PASSED PER NADINE BIGBY, PLANNER. PLEASE
 CALL 822-1451 FOR ADDITIONAL QUESTIONS.
2006-01-30 00:00:001/30/06 PLANS RETURNED TO LUIS MARTINEZ,
 BUILDING DEPT.
2006-01-23 00:00:00DENIED, IRONHORSE ASSOC NEED A MAJOR
 AMENDMENT TO THE RPD. PAPERWORK MAY
 BE PICKED AT THE PLANNING DEPT 5TH FLOOR
 OF CITY HALL.