Plan Review Details - Permit 05121269
Plan Review Stops For Permit 05121269
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-03 Cont ID  
Sent By dpalmer Date 2006-01-03 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2006-01-03 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 16:25 Sent To PC
Notes
2005-12-30 00:00:00********** UNSAT ***********
  
  
 1)NOTE: PLEASE SUBMIT A PERMIT
 APPLICATION PROPERLY NOTORIZED PER FS
 117.05
  
 2)NOTE: PLEASE SUBMIT A VALUATION FOR
 SCOPE OF WORK BEING PERFORMED OR A VALUE
 WILL BE ASSESSED PER MARSHALL/ SWIFT AS
 ADOPTED UNDER FBC ADMINISTRATIVE SECTION
 108.3
 $2000 FOR ALL CATV, PHONE, AUDIO WIRING
 IS WAY TOO LOW.
  
 3)NOTE: PLEASE SUBMIT TWO COPIES OF
 PLANS, EACH SHALL CONTAIN THE PRINTED
 NAME AND SIGNATURE AS THE ONE SET
 SUBMITTED IS.
 FBC 106.3.4.3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-03 Cont ID  
Sent By ptjomsto Date 2006-01-03 Time 15:32 Rev Time 0.00
Received By ptjomsto Date 2006-01-03 Time 15:32 Sent To  
Notes
2006-01-03 00:00:001ST RESUB GIVEN TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-12-30 Time   Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 16:03 Sent To  
Notes
2005-12-30 00:00:00TO "E" BOX