Plan Review Details - Permit 05121267
Plan Review Stops For Permit 05121267
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-30 Cont ID  
Sent By rmcdouga Date 2005-12-30 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2005-12-30 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By rmcdouga Date 2005-12-30 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2005-12-30 Time 13:09 Sent To  
Notes
2005-12-30 00:00:00DENIED
  
 1) SUBMIT ENGINEERED RATIONAL ANALYSIS
 FOR THE INCREASED DESIGN PRESSURES
 REQUIRED AT PERIMETER AND CORNER AREAS
 WHICH EXCEED THE 52.5 DESIGN PRESSURE
 LISTED IN THE FLORIDA PRODUCT APPROVAL.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR
 INSTALLATION OF METAL ROOF OVER EXISTING
 SHINGLES.
  
 3) A PRE-INSPECTION BY THE CITY'S
 BUILDING DEPARTMENT OF THE EXISTING ROOF
 WILL BE REQUIRED BEFORE A ROOF OVER CAN
 BE STARTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  