Plan Review Details - Permit 05121266
Plan Review Stops For Permit 05121266
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-18 Cont ID  
Sent By shill Date 2006-01-18 Time 15:14 Rev Time 0.00
Received By shill Date 2006-01-18 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By shill Date 2006-01-09 Time 09:49 Rev Time 0.50
Received By shill Date 2006-01-09 Time 09:49 Sent To  
Notes
2006-01-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)THIS BUILDING WAS DESIGNED AS 145
 MPH, EXPOSURE C.USING FBC TABLE
 1606.2B, THE LIMITATION OF -52.5 DOES
 NOT MEET THE MINIMUM DESIGN PRESSURE
 REQUIREMENT.SELECT A COMPLIANT
 ASSEMBLY AND HAVE THE PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD TO
 CONFIRM THAT DESIGN CRITERIA HAVE BEEN
 MET OR EXCEEDED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-09 Cont ID  
Sent By shill Date 2006-01-09 Time 09:49 Rev Time 0.00
Received By shill Date 2005-12-30 Time 15:47 Sent To  
Notes
2005-12-30 00:00:00TO "SHILL" DESK/NEW ROOF