Plan Review Details - Permit 05121146
Plan Review Stops For Permit 05121146
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-27 Cont ID  
Sent By pkrauss Date 2005-12-27 Time 11:43 Rev Time 0.00
Received By pkrauss Date 2005-12-27 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-30 Cont ID  
Sent By pkrauss Date 2005-12-30 Time 14:52 Rev Time 0.00
Received By pkrauss Date 2005-12-30 Time 14:52 Sent To  
Notes
2005-12-30 00:00:00AS-BUILT DRAWING
 PLEASE NOTE, PLAN DOES NOT SPECIFY SIZE
 OF THE TRANSFER GRILLE.PER 2001 FMC
 601.4 EXCEPTION #2, RETURN TRANSFER
 GRILLE SHALL BE HAVE MINIMUM OF 50
 SQUARE INCHES PER 100 CFM OF SUPPLY AIR
 INTO THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-12-27 Cont ID  
Sent By pkrauss Date 2005-12-27 Time 11:44 Rev Time 0.00
Received By pkrauss Date 2005-12-27 Time 11:44 Sent To  
Notes
2005-12-27 00:00:00PROVISO:
 PROVIDE AS BUILT PLANS FOR DUCTWORK
 PRIOR TO ROUGH INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.