Plan Review Details - Permit 05121117
Plan Review Stops For Permit 05121117
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 13:54 Rev Time 0.50
Received By alange Date 2006-01-06 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 07:59 Rev Time 0.00
Received By dpalmer Date 2005-12-29 Time 07:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-30 Cont ID  
Sent By nmccray Date 2005-12-30 Time 10:35 Rev Time 0.00
Received By nmccray Date 2005-12-30 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 14:12 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 14:12 Sent To M
Notes
2006-02-06 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 13:55 Rev Time 0.00
Received By alange Date 2005-12-28 Time 08:41 Sent To  
Notes
2005-12-28 00:00:00TO "BOB"#7

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-02-07 Cont ID  
Sent By tgordon Date 2006-02-07 Time 11:11 Rev Time 0.20
Received By tgordon Date 2006-02-07 Time 11:11 Sent To  
Notes
2006-02-07 00:00:00MECH. PLANS VOIDED AND WILL BE SUBMITTED
 AT A LATER DATE SO MASTER PERMIT WILL GO
 THROU. NO MECH. PERMIT NUMBER APPLIED
 FOR AT THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-04 Cont ID  
Sent By pkrauss Date 2006-01-04 Time 13:28 Rev Time 0.00
Received By pkrauss Date 2006-01-04 Time 13:28 Sent To  
Notes
2006-01-04 00:00:00DENIED:
 1.RETURN AIR FROM BATHROOM AREAS SHALL
 NOT BE RECIRCULATED PER 2004 FMC 407.1.
  
 2.PLAN SHEET 7 OF 8 INDICATES 150 CFM
 OF EXHAUST FROM THE MENS RESTROOM/SHOWER
 AREA.PER 2004 FMC TABLE 403.3, A TOTAL
 OF 200 CFM IS REQUIRED FROM THE MENS
 ROOM.
  
 3.PROVIDE MANUFACTURER INFORMATION OR
 SPECIFICATIONS FOR THE EXHAUST FAN.
 PLANS DOES NOT INDICATE IF THE EXHAUST
 FAN IS NEW OR EXISTING.
  
 4.PLAN SHEET 7 OF 8 INDICATES SUPPLY
 AND RETURN AIR DUCT GOINX DOWN TO THE
 1ST FLOOR IN AN EXISTING OPENING.
 PLEASE CLARIFY IF THIS PENETRATION IS
 RATED.SHOW COMPLIANCE WITH 2004 FMC
 607.6.1 & 607.8 OR 607.6.3.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.
  
 6.PLAN SHEET 8 OF 8, DETAIL FOR THE
 AHU SHOWS A "SAFE-T-SWITCH" ON THE
 AUXILIARY DRAIN LINE.PLEASE INDICATE
 IF THE AHU HAS A BOTTOM RETURN.PLEASE
 INDICATE IF THE RETURN AIR IS A DUCTED
 BOTTOM RETURN OR SHOW COMPLIANCE WITH
 2004 FMC 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By tgordon Date 2006-01-03 Time 11:34 Rev Time 0.45
Received By tgordon Date 2006-01-03 Time 11:45 Sent To  
Notes
2006-01-03 00:00:00*** DENIED ***
 1) RETURN AIR CAN NOT COME FROM A PUBLIC
 RESTROOM, PER 2004 FBC/M 407.1 .
  
 2) PLEASE PROVIDE FOR SUPPLY VENTILATION
 AIR, PER 2004 FBC/M 403.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-01-04 Cont ID  
Sent By tgordon Date 2006-01-03 Time 11:45 Rev Time 0.50
Received By jleech Date 2006-01-04 Time 10:14 Sent To  
Notes
***NONE***