Plan Review Details - Permit 05121091
Plan Review Stops For Permit 05121091
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By shill Date 2006-04-11 Time 11:24 Rev Time 8.00
Received By shill Date 2006-04-04 Time 09:30 Sent To  
Notes
2006-04-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)A-1, DECLARE OCCUPANCY FBC3.THIS
 IS A MIXED USE BUILDING.DECLARE
 OCCUPANCY FOR THE FIRST FLOOR OFFICE
 AREA, FIRST FLOOR ART STUDIO, FIRST
 FLOOR WORKSHOP, SECOND FLOOR APARTMENTS.
  
  
 4.)ON THE AREA CALCULATIONS, INCLUDE
 EXISTING AREA, PROPOSED NEW, AND NEW
 TOTAL.THERE IS AN ADDITION FOR THE
 FIRST FLOOR SHOWN ON THE PLAN.
  
 5.)AS1, GOVERNING CODE IS FBC2004,
 FBC2004 EXISTING BUILDING CODE.
  
 6.)AS1, INCORRECT ASCE7 REFERENCE,
 FBC35.
  
 7.)AS1, ACCESSIBLE PARKING, CANNOT
 WALK BEHIND PARKED CARS AND IS TO BE ON
 AN ACCESSIBLE ROUTE MINIMUM 44IN.
 FBC11-4.6.2(1), FBC FIGURE 11-9(A).
  
 8.)AS1 SHOWS THE SIGNAGE FOR THE
 ACCESSIBLE PARKING ON ANOTHER PROPERTY.
 ALTHOUGH THERE IS AN EASEMENT, THE
 EASEMENT IS REVOCABLE WITH 30 DAYS
 WRITTEN NOTICE BY EITHER PARTY AND ALSO
 UNDER OTHER CONDITIONS.THE SIGN IS
 REQUIRED AND MUST BE ON THE SAME PARCEL
 AS THE PARKING SPACE.
  
 9.)AS1, PARKING STRIPING TO COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS,
 SEE ATTACHED.
  
 10.)AS1, DECLARE BUILDING TYPE
 ACCORDING TO FBC2004 CHAPTER 6.ALSO
 NOTE WHETHER THIS BUILDING IS FULLY
 SPRINKLED OR UNSPRINKLED.NO SPRINKLER
 PLANS SUBMITTED AND NO INFORMATION
 PROVIDED ON THE PLAN.
  
 11.)SHOW COMPLIANCE WITH FBC TABLE 602
 AND FBC704.8.THE EAST SIDE IS LESS
 THAN 10' FROM THE PROPERTY LINE, WEST
 SIDE IS AT THE PROPERTY LINE.SHOW FIRE
 RESISTANCE RATING OF THE WALL AND
 OPENINGS IF APPLICABLE.
  
 12.)SHOW FINISHED FLOOR ELEVATION ON
 BOTH SIDES OF THE REAR ENTRANCE DOOR AND
 THE MAXIMUM SLOPE AT THE FRONT ENTRANCE
 DOOR A-A6, FBC11-4.1.6(1).
  
 13.)SHOW THE PROPERTY LINE A-A6.THE
 FOOTER CANNOT ENCROACH THE PROPERTY
 LINE.
  
 14.)DECLARE LEVEL OF ALTERATION, FBC
 EXISTING BUILDING CODE.
  
 15.)ARE THERE MULTIPLE TENANTS OR ONE
 TENANT ON THE FIRST FLOOR?
  
 16.)PROVIDE INFORMATION IN REGARDS TO
 WHAT MATERIALS WILL BE STORED IN THE ART
 STUDIO AND WORKSHOP, FBC 3.
  
 17.)THE PARTITION LEGEND SYMBOL FOR
 THE EXISTING CONCRETE BLOCK WALL IS NOT
 CONSISTENT WITH THE FLOOR PLAN.
  
 18.)S2, BEAM B2, SPECIFY WIDTH.ONLY
 QUANTITY AND HEIGHT IS SHOWN.
  
 19.)SEMCO IS NO LONGER IN BUSINESS.
 SPECIFY AVAILABLE CONNECTORS, 4-A7.
 CHECK ALL DETAILS (OTHERS ARE ALSO
 SPECIFY SEMCO).
  
 20.)PROVIDE FLOOR LOADING DESIGN
 CRITERIA, FBC TABLE 1607.1.ALSO
 PROVIDE FLOOR LOADING CERTIFICATION;
 SHOW ON THE PLAN THAT THE EXISTING ROOF
 FRAMING CAN ACCOMMODATE THE FLOOR
 LOADING DESIGN.
  
 21.)THE FIRE RATING AT THE EXIT ON THE
 FIRST FLOOR IS NOT CONTINUOUS.FOR
 INSTANCE, NO FIRE RATING IS SHOWN AT THE
 WORKSHOP, ART STUDIO, COLUMNS.
  
 22.)THE EXIT SHOWN ON THE FIRST FLOOR
 (STAIR AREA) CANNOT HAVE A KITCHEN,
 FBC1013.2.
  
 23.)NO STORAGE ALLOWED UNDER THE
 STAIRS, FBC1019.1.5.
  
 24.)NO OPENINGS OR PENETRATIONS
 ALLOWED IN THE EXIT ENCLOSURE,
 FBC1019.1.2 (THE DOOR TO THE STORAGE
 AREA, THE KITCHEN, DUCTWORK).
  
 25.)FOR EGRESS PURPOSES, DECLARE
 DESIGN OCCUPANT LOADS, A1, FBC1004.1.
  
 26.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.5.
  
 27.)PROVIDE A DETAIL FOR THE UL
 ASSEMBLY, VERTICAL SEPARATION.ONE IS
 SPECIFIED BUT NO DETAIL WAS PROVIDED.
 FBC402.7.2, TENANT SEPARATION.
  
 28.)SMOKE DETECTORS REQUIRED AT
 SLEEPING ROOMS IN ACCORDANCE
 FBC907.2.10.1.2.
  
 29.)SHOW HALLWAY WIDTH BETWEEN THE
 STAIR AND ART STUDIO, FIRST FLOOR.
  
 30.)HORIZONTAL SEPARATION REQUIRED,
 FBC 302.3, FBC TABLE 302.3.2, OCCUPANCY
 SEPARATION.SPECIFY UL ASSEMBLY OR
 CALCULATED FIRE RESISTANCE.
  
 31.)THE ASTM REFERENCES ON S2 ARE
 OUTDATED.YOU HAVE SPECIFIED VERSIONS
 WHICH ARE OVER TEN YEARS OLD.REVISE TO
 A MORE CURRENT STANDARD.
  
 32.)THE EXIT STAIR IS TO BE ENCLOSED,
 FBC1019.1.
  
 33.)NO FIRE RATING IS SHOWN FOR THE
 ELEVATOR SHAFT, FBC707.14.NOTE ALL
 FIRE RATING REQUIREMENTS ON THE FLOOR
 PLAN TO AVOID CONFUSION WITH OTHER
 TRADES.
  
 34.)SPECIFY FIRE RATING FOR DOORS, FBC
 TABLE 715.3.
  
 35.)THE ELEVATOR IS TO BE IN
 CONFORMANCE WITH ASME A17.1, FBC3001.2.
 NOTE ON THE PLAN.
  
 36.)THE DOOR AT THE ELEVATOR (FIRST
 AND SECOND FLOORS) AND THE DOOR AT THE
 MEN?S RESTROOM BLOCK THE EGRESS,
 FBC1005.2.
  
 37.)PROVIDE A DETAIL FOR THE BREAKROOM
 SINK, FBC11-4.24.SHOW CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 38.)SHOW MANEUVERING CLEARANCE PULL
 SIDE, FBC11-4.13.6, FBC FIGURE 11-25.
 FOR THE DOOR AT THE END OF THE HALLWAY
 LEADING TO THE EXIT ENCLOSURE, FIRST
 FLOOR.NOTE THAT NORMALLY FOR
 COMMERCIAL PLANS DOORS AND ROOMS ARE
 NUMBERED TO ASSIST IN REFERENCE.
  
 39.)THE MASONRY OPENING SIZES FOR THE
 EAST ELEVATION ARE NOT CONSISTENT WITH
 THE ELEVATION OR THE FLOOR PLAN, A4.
  
 40.)HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF THE STAIR, FBC1009.11.
  
 41.)HANDRAIL EXTENSIONS REQUIRED,
 FBC1009.11.5.
  
 42.)3-A7, SOME DIMENSIONS ARE MISSING,
 SUCH AS THE MINIMUM HANDRAIL DIMENSION,
 DISTANCE FROM WALL.PROVIDE ONLY
 COMPLETE SPECIFIC DETAILS.
  
 43.)THE PLUMBING PLAN IS LABELED AIR
 CONDITIONING PLAN.
  
 44.)DUCTS THROUGH FIRE RATED WALLS ARE
 TO BE PROTECTED, FBC712.4.4.AC1, FIRST
 FLOOR.
  
 45.)FIREBLOCKING REQUIRED, 4-A7,
 FBC717.2.3.
  
 46.)NO FIRE PROTECTION SHOWN FOR THE
 ENCLOSURE UNDER THE STAIR, FBC1019.1.5.
  
 47.)NO CONTINUOUS FIRE RESISTANCE
 SHOWN BETWEEN FIRST FLOOR TENANT AND THE
 COMMON SPACE.NOTE THAT THERE ARE TWO
 FIRE RESISTANCE REQUIREMENTS; ONE FOR
 TENANT (COMMON SPACE) SEPARATION, ONE
 FOR PROTECTION OF THE EXIT WHICH IS THE
 ONLY MEANS OF EGRESS FROM THE SECOND
 FLOOR.
  
 WHEN RESUBMITTING, PROVIDE A RESPONSE
 LETTER STATING HOW EACH ITEM WAS
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By dpalmer Date 2006-02-07 Time 19:35 Rev Time 0.00
Received By dpalmer Date 2006-02-07 Time 17:45 Sent To I
Notes
2006-02-07 00:00:00************ UNSAT ****************
  
 *** PLEASE KNOW, PLANS ARE NOT COMPLETE
 FOR A COMPLETE REVIEW FOR CODE
 COMPLIANCE AT THIS TIME.
 PLEASE SEE NOTES BELOW.
  
 1)NOTE: PLEASE BE SURE TO COMPLETE ALL
 CIRCUITING ON PLANS AND CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULES.
 PLEASE SEE THERE ARE MANY DEVICES WHICH
 DO NOT INDICATE ANY CIRCUITS AND MANY
 CIRCUITS WHICH DO NOT CORRELATE WITH THE
 SUBMITTED SCHEDULES.
  
 2)NOTE: PLEASE BE SURE PLANS REFERENCE
 THE CURRENT CODES IN EFFECT AS LISTED.
 NFPA-101 2003, NFPA-72 2002, NFPA-70,
 2002.
  
 3)NOTE: PLEASE SEE THERE ARE LOCATIONS
 ON PLANS WHICH MAKE REFERENCE TO "FOUR
 APTS"?? PLEASE DECIDE THE USE, AND
 ADJUST PLANS AS NEED. PLEASE SEE OTHER
 COMMENTS WITH RESPECT TO FEEDERS/ LOAD CALCULATIONS
 ETC.
 ** PLEASE KNOW, IF INDEED THERE IS GOING
 TO FOUR APT UNITS, PLEASE SEE THE
 FOLLOWING COMMENT.
  
 4)NOTE: IF 4 APTS?
 PLEASE PROVIDE COMPLETE HEIGHT/DEVICE
 LOCATIONS AS REQUIRED UNDER FAIR HOUSING
 ACT REGULATIONS 24 CFR100.205
  
 5)NOTE:PLEASE SEE NO MAIN OR OCP IS
 SHOWN ON RISER FOR SERVICE. 230.70,
 215.5
  
 6)NOTE: PLEASE SEE NO OCP IS SHOWN FOR
 MAINS/FEEDS TO EACH PANEL. PLEASE SEE
 RISER SHOWS FEEDERS "TYPICAL OF 4"??
 PLEASE INDICATE THE OCP FOR EACH,
 240.4,310.16, 230.70 ETC.
  
 7)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR TO EACH PANEL.
 250.110,250.122 ETC.
  
 8)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM MENTIONS TO ATTACHED TO FOOTER
 STEEL? PLEASE KNOW,IN AN EXISTING
 BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE
 TO THE STRUCTUAL
 INTEGRITY OF THE EXISTING STEEL/FOOTER.
 PLEASE KNOW HOWEVER THIS IS PERMITTED,
 AND IF SHOWN ON RISER , IT WILL BE
 REQUIRED.
 250.50
  
 9)NOTE: PLEASE SEE 250.66 FOR SIZING OF
 GROUNDING ELECTRODE CONDUCTOR AS THIS IS
 CURRENTLY SHOWN AS A "6/0"? PLEASE KNOW,
 THIS IS NOT A RECOGNIZED AMERICAN WIRE
 GAUGE STANDARD.
 PLEASE ADJUST AS NEED BASED ON SERVICE
 ENTRANCE CONDUCTORS WHICH WILL BE BASED
 ON LOAD CALCULATIONS."NOTE: PLEASE SEE
 COMMENTS BELOW FOR LOAD CALCS AS SEC'S
 MAY CHANGE.
 215.5
  
 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 ** PLEASE SEE NOTE #20 ON NOTES WHICH
 MENTIONS THE USE OF FUSES, HOWEVER NONE
 ARE SHOWN?
  
 11)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE THIS IS A MIXED USE.
 PLEASE SEE THE RESIDENTIAL LOAD
 CALCULATIONS ARE BEING USED FOR THE
 COMMERICAL SPACE AND ONCE AGAIN THE LOAD CALCULATIONS
 MAKE REFERENCE TO THE
 INSTALLATION OF"4-APTS" AND DERATING
 IS TAKEN FROM TABLE 220.32??
 PLEASE ADJUST ALL LOAD CALCULATIONS AND
 SEEOTHER COMMENTS WHICH WILL AFFECT
 LOADS AS SHOWN.
  
 12)NOTE: PLEASE SHOW ALL PANEL LOCATIONS
 FOR VERIFICATION OF CODE COMPLIANCE.
 110.26,240.24 ETC.
  
 13)NOTE: PLEASE CORRELATE PANEL
 SCHEDULES AND RISER, PANELS SHOWS TWO
 PANEL "A"'S? (MISPRINT)
 215.5
  
 14)NOTE: PLEASE CORRELATE ALL LOAD FOR
 A/C SYSTEMS, AS MECHANICAL PLANS
 INDICATE 10KW UNITS, LOAD CALCUALTIONS
 INDICATE BOTH 9KW LOAD AND 5KW LOAD AND
 PANEL SCHEDULES INDICATE 5KW HEAT FOR
 ALL??
 PLEASE ADJUST LOAD CALCS ETC 215.5
  
 15)NOTE: PLEASE SEE 424.3B WHICH
 REQUIRES ALL MIN OCP FOR AHU'S HEAT TO
 BE SIZED AT A MIN OF 125%.
 PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6
 AWG ON 5KW UNITS.
 ** PLEASE KNOW, THERE IS ALSO A MAX OCP.
  
 16)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS
 WHICH DO NOT SEEM TO
 INDICATE THE REQUIRED NEUTRAL CONDUCTOR
 PER 250.140
  
 17)NOTE: PLEASE VERIFY ALL CONDUCTORS
 LISTED ON PANEL SCHEDULE(S).
 PLEASE SEE MANY ARE SHOWING 15A OCP ON
 #12 AWG. PLEASE ALSO SEE NOTES WHICH
 MENTIONS THE MIN SIZE AWG SHALL BE #12?
 PLEAS KNOW, #12 IS PERMITTED ON 15A OCP.
  
 18)NOTE: PLEASE SEE AN ELEVATOR IS SHOWN
 ON PLANS, HOWEVER THERE IS NO INDICATION
 ON ANY PLANS OF THIS EQUIPMENT??
 215.5
  
 19)NOTE: PLEASE SEE 620.23 WHICH
 REQUIRES A DEDICATED BRANCH CIRCUIT FOR
 PIT LTS/GFI RECEPT.
  
 20)NOTE: PLEASE ALSO SEE 620.24 WHICH
 REQUIRES A DEDICATED BRANCH CIRCUIT FOR
 ANY ELEVATOR EQUIPMENT ROOM /AREA FOR
 SERVICE.
  
 21)NOTE: PLEASE KNOW, ANEMERGENCY
 BATTERY BACK UP TYPE LT FIXTURE WILL BE
 REQUIRED AT ANY ELEVATOR EQUIPMENT
 LOCATION.700.16,LS101 7.8/7.9
  
 22)NOTE: PLEASE SEE WHAT APPEARS TO BE
 OUTSIDE LTS ON 2ND FLOOR LEVEL WHICH
 INDICATES THESE LTS TO BE CIRCUIT B-8
 AND A-8, HOWEVER ALSO INDICATE THESE TO
 BE ON A TC (TIMECLOCK)? PLEASE CORRELATE
 THESE IF INDEED THEY ARE TO BE ON WITH
 THE FIRST FLR OUTSIDE TC CIRCUIT?
  
 23)NOTE: PLEASE SEE THE MISSING REQUIRED
 DEDICATED SIGN CIRCUIT AS PER 600.5
  
 24)NOTE: PLEASE SEE THE NEW FBC 2004,
 CHAPTER 13 (ENERGY CODE) FOR EXPANDED
 REQUIMENTS FOR COMMERCIAL BLDGS.
 13-413,13-415 ETC.
 PLEASE ADJUST AS NEEDED.
  
 25)NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9
 WHICH REQUIRES A MIN OF BATTERY BACK UP
 EM LTS FOR MEANS OF EGRESS TO THE PUBLIC RIGHT-OF-WAY.
 PLEASE SEE FIRE REVIEW
 COMMENTS ALSO FOR THIS.
 PLEASE SEE 7.8.1.3 WHICH NOW REQUIRES A
 MIN OF 10 FT CANDLES (108 LUX) FOR ALL
 LEVELS OF STAIRS DURING NORMAL POWERE
 AND THE PERMITTED DE-RATINGS ALLOWED BY
 7.9.2.2 UNDER EMERGENCY CONDITIONS.
 TO 10.8 LUX.
  
 26)NOTE: PLEASE PROVIDE A FIXTURE
 SCHEDULE AND CORRELATE WITH THE PLANS.
 PLEASE SEE NOTES #24 AND #25 FOR TYPES
 OF FIXTURES.
  
 27)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS. THESE
 SHALL BE CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT SUPPLYINGLIGHTING IN THAT
 AREA.
  
 28)NOTE: PLEASE SEE 210.8A6 WHICH
 REQUIES ALL RECEPTS SERVIING KITCHEN
 COUNTERSPACES TO BE GFI/GFI PROTECTED.
  
 29)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLING UNITS.
  
 30)NOTE: PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH CIRCUITS PER
 210.52D,210.11C3. SHALL BE #12 AND 20.
 PLEASE SEE #14, 15A SHOWN FOR BOTH APTS
 UPSTAIRS.
 ** PLEASE SEE WHAT APPEARS TO BE APT
 WHICH SHOWS A CIRCUIT #8 FOR BATH GFI'S.
 PLEASE KNOW, THE DEDICATED BATH CIRCUIT
 MAY NOT FEED ANY OTHER AREAS.
  
 31)NOTE: PLEASE SEE THE CIRCUIT
 INDICATED ON PLANS FOR WHAT APPEARS TO
 BE A WASHER LOCATION IS SHOWN AS A SPARE
 ON PANEL SCHEDULE??
 PLEASE SEE 210.11C2, 220.16B WHICH
 REQUIRES A LAUNDRY CIRCUIT AND WASHER
 CIRCUIT TO BE A MIN 1500 VA , 20A AND
 #12 AWG.
 PLEASE ADJUST LOAD CALCUALTIONS ETC.
  
 32)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS AS REQUIRED UNDER NFPA-72
 11.5.1.1.
 MISSING INSIDE AND OUTSIDE ALL SLEEPING
 RMS.
 PLEASE ALSO SEE 11.8.3.5 FOR LOCATIONS
 OF SD'S WHICH ARE REQUIRED TO BE A MIN
 OF 3' FROM KITCHEN AND BATH DOORS AND
 SHALL BE A MIN OF 20' FROM ANY COOKING
 APPLIANCES. (COOKING APPLIANCES WITH
 EXCEPTIONS).
 PLEASE ALSO SEE NOTE ON PLANS WHICH
 MENTIONS SD'S ARE TO BE WIRED AHEAD OF
 THE SWITCHES ON EITHER BATH OR KITCHEN
 LIGHTING CIRCUIT, PLEASE SEE THIS IS OK,
 HOWEVER ARC FAULT PROTECTION WILL THEN
 BE REQUIRED FOR THOSE LIGHTING CIRCUITS,
 PLEASE SEE BATH LTS ARE ALSO WIRED TO BE
 A DEDICATED CIRCUIT FOR EACH BATH RM.
 ** PLEASE SEE COMMENT FOR REQUIRED ARC
 FAULT.
  
 33)NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS AS REQUIRED
 PER 2002 NEC 210.12B
  
 34)NOTE: PLEASE SEE A MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE SHOWN, HOWEVER
 ONLY ONE IS SHOWN FOR KITCHEN. PLEASE
 ADJUST CIRCUITING AS THE MIN OF TWO SM
 APPL CIRCUITS SHALL BE IN KITCHEN. 210.11C1,220.16A,
 215.5 ETC
  
 35)NOTE: PLEASE SEE ELECTRICAL PLANS ARE
 MISSING ALL A?C SYSTEMS?? AHU'S, CU'S.
 PLEASE SHOW ALL DISCONNECTS AS REQUIRED
 PER 440.11, 110.26
  
 36)NOTE: PLEASE SEE 210.63 FOR THE
 SERVICE RECEPT REQUIRED. (GFI) 210.8A
  
 37)NOTE: PLEASE SEE MANY CIRCUITS ON
 PLANS MENTIONS "GEN LTS" GEN RECEPTS"
 PLEASE LIST THESE TO BE SPECIFIC TO THE
 AREAS IN WHICH THEY ARE FEEDING.
  
 38)NOTE: PLEASE LABEL APTS ON PLANS AND
 CORRELATE. PLEASE SEE WHAT APPEARS TO BE
 APT "B".
  
 39)NOTE: PLEASE VERIFY WHAT IS SHOWN AS
 A QUAD RECEPT IN KITCHEN ON FIRST FLR
 WHICH IS SHOWN AS 15AON PANEL
 SCHEDULE?
 PLEASE ALSO SEE PREVIOUS COMMENT WITH
 RESPECT TO GFI PROTECTION.
  
 40)NOTE: PLEASE SEE PLANS WHICH SHOWS A
 CIRCUIT FOR WHAT IS LISTED ON PANEL
 SCHEDULE AS BEING A MICROWAVE # 14,
 HOWEVR NO DEVICE OR LOCATION IS SHOWN ON
 PLANS.
  
 41)NOTE: PLEASE SEE SWITCHES WHICH ARE
 SHOWN WIRED TO A 3-WAY SYSTEM, HOWEVER
 DO NOT INDICATE BEING S3.
 PLEASE SEE REDLINED LOCAITONS.
  
 42)NOTE:PLEASE SEE REDLINED MISSING
 RECEPT PER 210.52, 2' OF WALL.
  
 43)NOTE: PLEASE SHOW THE LOCATION OF THE
 SERVICE ON PLANS/BLDG.
 230.70,240.24,110.26, ETC
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AND THE EXTENT OF COMMENTS,
 PLEASE COMPLETE ALL OF THE ABOVE TO
 ALLEAVIATE FUTHER COMMENTS ON THE
 FOLLOWING REVIEW.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONLY ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE TO GO OVER ANY COMMENTS OR
 QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
2006-01-12 00:00:00SENT TO INCOMING AS BLDG IS MIXED USE
 AND SHOULD BE ON COMMERCIAL BOARD.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By mwennerg Date 2006-02-15 Time 09:13 Rev Time 0.00
Received By mwennerg Date 2006-02-15 Time 09:13 Sent To  
Notes
2006-02-15 00:00:00******DENIED******
  
 1) BUILDING SHALL MEET ALL REQUIREMENTS
 FOR MULTIPLE OCCUPANCIES.
  
 2) PLEASE SEE NFPA 101, 2003 EDITION
 SEC. 24.1.2.2 THAT PROHIBITS THE "SOLE
 MEANS OF EGRESS OF DWELLING UNITS TO
 PASS THROUGH A NON-RESIDENTIAL OCCUPANCY
 IN SAME BUILDING".
  
 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 4) IT APPEARS THAT THE DOOR TO THE
 ELEVATOR MAY OBSTRUCT THE DOOR TO APT.
 #1.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS
 THAT SHALL BE CLASS A,B OR C.
  
 7) IN ADDITION TO PRIMARY ESCAPE,
 DWELLING UNITS TO COMPLY WITH
 REQUIREMENT FOR SECONDARY ESCAPE.
  
 8) INTERIOR STAIRWAYS TOO BE PROVIDED
 WITH ARTIFICAL LIGHTING.
  
 9) SMOKE ALARMS ARE REQUIRED TO BE
 INSTALLED INSIDE AND OUTSIDE SLEEPING
 ROOMS.
  
 10) AN ADDRESS IS REQUIRED ON BUILDING
 THAT SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING TO THE BACKGROUND.
  
 11) WORK TO COMPLY WITH CURRENT BUILDING
 CODES, AND NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By dpalmer Date 2006-02-07 Time 19:33 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 14:03 Sent To  
Notes
2006-01-26 00:00:00TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-11 Cont ID  
Sent By adarroug Date 2006-01-11 Time 09:34 Rev Time 0.00
Received By adarroug Date 2006-01-11 Time 09:34 Sent To E
Notes
2006-01-11 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 09:26 Sent To  
Notes
2005-12-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-17 Cont ID  
Sent By pkrauss Date 2006-02-17 Time 15:33 Rev Time 0.00
Received By pkrauss Date 2006-02-17 Time 15:24 Sent To  
Notes
2006-02-17 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2004 FMC 403.3.
  
 2.INDICATE OUTSIDE AIR DUCT SIZE,
 MATERIAL & LAYOUT.
  
 3.PLAN SHEET AC-1 INDICATES FLEX DUCT
 THORUGH A RATED WALL WITH A FIRE DAMPER.
 PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS
 & FLEX CONNECTORS SHALL NOT PASS THROUGH
 ANY FIRE RESISTANCE RATED ASSEMBLY.
  
 4.PLAN SHEET AC-2 HVAC DESIGN
 REQUIREMENT CHART INDICATES FIRE DAMPERS
 & DUCT SMOKE DETECTORS ARE NOT REQUIRED.
 THIS IS INCORRECT.FIRE DAMPERS ARE
 REQUIRED THROUGH FIRE RATED PARTITIONS.
 PLAN SHEET A-1, FIRST FLOOR ACCORDING TO
 THE PARTITION LEGEND THE FOLLOWING AREAS
 ARE INDICATED AS FIRE RATED PARTITIONS:
 1) BETWEEN THE ART STUDIO & COMMON AREA
 2) BATHROOM AREAS AND THE COMMON AREA
 3) KITCHEN AREA TO THE CONFERENCE ROOM &
 THE CORRIDOR.
  
 PLEASE NOTE, FIRE DAMPERS ARE NOT
 REQUIRED SHOULD PENETRATION MEET ALL THE
 REQUIREMENTS OF 2004 FMC 607.5.3
 EXCEPTION #2 ITEMS 2.1 THROUGH 2.6,
 PLEASE ANNOTATE ON THE PLAN.
  
 5. DUCT SMOKE DETECTORS REQUIRED IN
 SYSTEMS THAT HAVE THE DESIGN CAPACITY TO
 PRODUCE GREATER THAN 2,000 CFM.SYSTEM
 4 HAS THIS CAPACITY.PLEASE INDICATE
 DUCT SMOKE DETECTOR ON THE PLAN IN
 ACCORDANCE WITH 2004 FMC 606.2.1.
  
 6.PLAN SHEET AC-2 DETAIL FOR THE ROOF
 CURB.IS THIS FOR THE CONDENSER UNITS?
 PROVIDE DETAIL OF HOW THE UNITS WILL BE
 ATTACHED TO THE CURB.TYPICALLY
 CONDENSER UNITS ARE MOUNTED ON STANDS IN
 ACCORDANCE WITH 2004 FBC TABLE 1509.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By kstevens Date 2006-03-09 Time 11:20 Rev Time 0.00
Received By kstevens Date 2006-03-09 Time 11:20 Sent To  
Notes
2006-03-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 RESIDENTIAL
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT AS-1 CODE REFERENCED AS FBC-2001.
 CODE IN EFFECT IS FBC-2004. PLEASE
 DESIGN TO PRESENT CODE AND CHANGE
 REFERENCE.
 2. SHT A-1 KITCHEN SINK TO BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. A TURNING AREA IS REQUIRED.
 3. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 4. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 5. SHT A-2 ROOF PLAN. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FOOTAGE OF THE
 ROOF, AND INCLUDE 1/2 AREA OF ALL
 VERTICAL WALLS IN THE CALCULATIONS. SHOW
 THE LOCATIONS FOR SECONDARY ROOF DRAINS
 OR OVERFLOW SCUPPERS. SCUPPER DETAIL
 REFERENCED CALLS OUT DETAIL 1 SHT A-8.
 SHT A-8 NOT SUBMITTED. PLEASE CLARIFY.
 SECTIONS 106.1.1, 1106, 1107 AND ALL
 SUBSECTIONS. THE SIZING OF THE OVERFLOW
 SCUPPERS CAN NOT BE DETERMINED WITH
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE SHOW CALCULATIONS FOR OVERFLOW
 SCUPPERS ON PLANS PER SECTIONS 1101.7,
 1107.3 AND TABLE 1106.7.
 6. SHT A-2 WATER HEATERS FOR THE
 RESIDENTIAL UNITS ARE NOT SHOWN. PLEASE
 INDICATE THE LOCATIONS OF THE WATER
 HEATERS REQUIRED BY SECTIONS 607.1 AND
 2801.1.
 7. SHT P-1 THE AUTOMATIC CLOTHES WASHER
 FIXTURES SHALL CONNECT TO A BRANCH DRAIN
 OR DRAINAGE STACK A MINIMUM OF 3" IN
 DIAMETER. SECTION 406.3.
 8. SHTS P-1 & P-2 SOME SANITARY RISER
 PIPE SIZES DO NOT REFLECT THE PIPE SIZES
 SHOWN ON THE FLOOR PLAN PIPE LAYOUT.
 PLEASE CORRELATE RISER DIAGRAM SO THAT
 IT REFLECT THE PIPING LAYOUT. SECTION
 106.1.1.
 9. SHT P-2 SANITARY RISER DIAGRAM, A
 TRAP AND A STANDPIPE ARE REQUIRED AT THE
 WASH MACHINES. SECTIONS 1002.1 & 802.4.
 10. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 AND WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. (ICE MAKER, DISH WASHER,
 AND WASH MACHINE). WATER HAMMER
 ARRESTORS TO BE LOCATED IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 11. SECOND SHEET P-2, WATER HEATER
 DETAIL, THERMAL EXPANSION CONTROL
 REQUIRED PER SECTION 607.3.2. INDICATE
 METHOD.
 12. SECOND SHT P-2 EMERGENCY PAN DRAIN
 LINE DIAGRAM SHOWS PAN DRAINING INTO AN
 ABOVE GROUND HUB DRAIN. THIS IS NOT
 SHOWN ON THE SANT. RISER DIAGRAM.
 CORRELATE RISER WITH DETAIL. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-10 Cont ID  
Sent By mmclean Date 2006-01-10 Time 16:25 Rev Time 0.00
Received By mmclean Date 2006-01-10 Time 16:25 Sent To I
Notes
2006-01-10 00:00:00DENIED,
 1. NEED TO APPLY FOR A LEVEL I INFORMAL
 SITEPLAN REVIEW WITH THE PLANNING &
 ZONING DEPT AT 822-1435.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720