Plan Review Stops For Permit 05121022 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-05-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-05-08 |
Time |
19:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-05-08 |
Time |
19:10 |
Sent To |
|
|
Notes |
2006-05-08 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | FROM PREVIOUS REVIEW: | | | | 1.)THE SCOPE OF WORK IS NOT CLEAR. | | THE APPLICATION STATES "EXPANSION", | | WHICH IMPLIES AN ADDITION, BUT A | | FOUNDATION PLAN IS NOT SHOWN.NO SITE | | PLAN WAS PROVIDED.THE PLANS STATE BOTH | | "EXIST CART BARN" AND "NEW LAUNDRY". | | | | SECOND REVIEW - SCOPE OF WORK WAS | | CLARIFIED, BUT CHANGES TO THE PLAN HAVE | | TRIGGERED NEW COMMENTS. | | | | 2.)ONLY A PARTIAL FLOOR PLAN WAS | | PROVIDED.WHAT IS IN THE REST OF THE | | BUILDING?DECLARE OCCUPANCY FOR THIS | | AREA AND ADJACENT AREA, ADDRESSING ANY | | FIRE RATING REQUIREMENTS, IF ANY.SHOW | | NEARBY STRUCTURES. | | | | SECOND REVIEW - BUSINESS OCCUPANCY WAS | | DECLARED.READ FBC 311.THIS IS NOT | | BUSINESS OCCUPANCY, READ FBC304.1. THE | | CART STORAGE AREA IS S1.THE LAUNDRY IS | | EITHER MIXED USE F1 306.2 OR INCIDENTAL | | USE FBC 302.1.1.READ CHAPTER 3 AND | | DECLARE CORRECT OCCUPANCY. IF THIS IS | | MIXED USE, SHOW REQUIRED FIRE SEPARATION | | OF 2 HOURS. | | | | DECLARE CONSTRUCTION TYPE FBC6.TYPE | | III WAS DECLARED, A OR B? | | | | 3.)THE SINGLE DOORAPPEARS TO LEAD | | OUTSIDE; IS THIS CORRECT?WHY DOES THE | | WALL THAT IT IS PERPENDICULAR TO EXTEND | | FURTHER, IMPLYING ADDITIONAL AREA?ALSO | | THIS DOOR IS FIRE RATED, IMPLYING A | | SEPARATION, AND THE DOUBLE DOOR DOES NOT | | SHOW A FIRE RATING.IF THIS DOOR LEADS | | TO INTERIOR SPACE, EVEN IF IT IS A WORK | | SPACE, THE DOOR MUST MEET MANEUVERING | | CLEARANCE FBC11-4.13.6. | | | | SECOND REVIEW - THE DOOR HAS BEEN | | RELOCATED BUT NOW BLOCKS OVER HALF THE | | REQUIRED WIDTH OF THE PASSAGEWAY, | | FBC1008.1.8.8. | | | | 4.)ADDRESSED, NOT AN ADDITION. | | | | 5.)IF THIS IS AN ADDITION, SHOW A WALL | | DETAIL CONTINUOUS FROM THE FOUNDATION | | THROUGH THE ROOF, ALL WIND DESIGN | | CRITERIA, FBC16. | | | | SECOND REVIEW - ALTHOUGH THIS IS NOT AN | | ADDITION, THERE IS STILL AN EXTERIOR | | ALTERATION (DOORS).PROVIDE WIND DESIGN | | CRITERIA FBC1603.1.4. | | | | 6.) ADDRESSED.A LOCAL PRODUCT APPROVAL | | WILL BE ISSUED USING THE NOA. | | | | 7.)ADDRESSED. | | | | NEW COMMENTS: | | | | 8.)PRODUCT APPROVALS TO BE REVIEWED BY | | DESIGNER OF RECORD, FBC*106.3.3. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-03-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-03-13 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-03-13 |
Time |
11:17 |
Sent To |
|
|
Notes |
2006-03-13 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)THE SCOPE OF WORK IS NOT CLEAR. | | THE APPLICATION STATES "EXPANSION", | | WHICH IMPLIES AN ADDITION, BUT A | | FOUNDATION PLAN IS NOT SHOWN.NO SITE | | PLAN WAS PROVIDED.THE PLANS STATE BOTH | | "EXIST CART BARN" AND "NEW LAUNDRY". | | | | 2.)ONLY A PARTIAL FLOOR PLAN WAS | | PROVIDED.WHAT IS IN THE REST OF THE | | BUILDING?DECLARE OCCUPANCY FOR THIS | | AREA AND ADJACENT AREA, ADDRESSING ANY | | FIRE RATING REQUIREMENTS, IF ANY.SHOW | | NEARBY STRUCTURES. | | | | 3.)THE SINGLE DOORAPPEARS TO LEAD | | OUTSIDE; IS THIS CORRECT?WHY DOES THE | | WALL THAT IT IS PERPENDICULAR TO EXTEND | | FURTHER, IMPLYING ADDITIONAL AREA?ALSO | | THIS DOOR IS FIRE RATED, IMPLYING A | | SEPARATION, AND THE DOUBLE DOOR DOES NOT | | SHOW A FIRE RATING.IF THIS DOOR LEADS | | TO INTERIOR SPACE, EVEN IF IT IS A WORK | | SPACE, THE DOOR MUST MEET MANEUVERING | | CLEARANCE FBC11-4.13.6. | | | | 4.)IF THIS IS AN ADDITION, PROVIDE A | | SITE PLAN.IMPACT FEES REQUIRED, | | 233-5025. | | | | 5.)IF THIS IS AN ADDITION, SHOW A WALL | | DETAIL CONTINUOUS FROM THE FOUNDATION | | THROUGH THE ROOF, ALL WIND DESIGN | | CRITERIA, FBC16. | | | | 6.)FLORIDA STATE OR LOCAL PRODUCT | | APPROVAL REQUIRED IN ADDITION TO THE | | NOAS PROVIDED, FAC9B72. | | WWW.FLORIDABUILDING.ORG | | | | 7.)NOT ENOUGH INFORMATION TO | | DETERMINE CODE COMPLIANCE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-05-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-05-09 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-05-08 |
Time |
22:47 |
Sent To |
|
|
Notes |
2006-05-09 00:00:00 | ***** UNSAT ********* | | | | | | 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS | | REVIEW. PLEASE INDICATE THE FEEDERS TO | | THIS EXISTING PANEL. | | INDICATE THE MEANS OF DISCONNECT | | REQUIRED PER 225.31-225.39 | | PLEASE SEE 250.32. | | 240.4,310.16, ETC. | | | | 2) NOTE: PLEASE SEE CIRCUITING FOR NEW | | EM LT IS NOW SHOWN CIRCUITED TO THE | | COUNTER SPACE RECEPT? | | PLEASE SEE 700.12E. ALL EM/EXT LTS SHALL | | BE CIRCUITED TO THE LOCAL LIGHTING | | BRACNCH CIRCUIT. | | | | 3) NOTE: PLEASE SEE SEE ORIG NOTE | | MENTIONED THE MIN OCP FOR THE WATRE | | HEATER HAD TO BE 125%. PLEASE SEE NOW, | | THE KW RATING IS SHOWN AT 4KW AND THE | | OCP IS SHOWN TOO HIGH. | | PLEASE SEE 422.11(E)3) MAX OCP SHOULD BE | | 150%. PLEASE KNOW, THIS WOULD BE 25A'S. | | | | 4) NOTE: PLEASE SEE WATER HEATER IS NOW | | BEINGSHOWN IN A CLOSED IN AREA AND | | DOES NOT INDICATE WHERE THE ACCESS IS? | | 422.17,110.26 ETC. | | | | 5) NOTE: PLEASE SEE THAT HAND DRAWN | | CHNAGES ARE NOT PERMITTED ON PLANS WHICH | | ARE SIGNED, DATED AND SEALED BY AN | | ARCHITECT OR ENGINEER. | | FS 471/481 | | PLEASE SEE HAND WRITTEN CHANGE OVER WHAT | | WAS SHOWN AS 100A PANEL, NOW DRAWN AS | | 200A'S.? | | | | 6) NOTE: PLEASE SEE ATTACHED COPY OF FS | | 553.80(2)(B) WITH RESPECT TO REPEAT CODE | | COMPLIANT COMMENTS. | | | | PLEASE CORRELATE ALL OF THE ABOVE. | | | | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS | | AND ONLY INSERT NEW REVISED SHEETS INTO | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | PLEASE BE SURE TO SEE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | EELCTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | 2006-05-08 00:00:00 | IN ELEC FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-01-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-01-24 |
Time |
18:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-01-24 |
Time |
18:29 |
Sent To |
|
|
Notes |
2006-01-24 00:00:00 | *** UNSAT *** | | | | 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN | | AS EXISTING, HOWEVER PLEASE INDICATE IF | | THE EXISTING FEEDERS. THIS CAN BE NOTED. | | PLEASE ALSO INDICATE OF PANEL CONTAINS A | | MEANS OF DISCONNECT, MCB ?SINCE THIS | | SEEMS TO BE SHOWN AS A DETACHED BLDG. | | PLEASE ALSO INDICATE GROUNDING ELECTRODE | | , NEW OR EXISTING FOR THIS PANEL AT | | DETACHED BLDG. | | ALL PER 240.4,310.16,225.31,250.32 ETC. | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | AND CORRELATE WITH THE PANEL SCHEDULE | | SUBMITTED. | | 215.5 | | PLEASE BE SURE TO INDICATE THE EM LT | | CIRCUITED TO THE SAME CIRCUIT FEEDING | | THE LOCAL LIGHTING BRANCH CIRCUIT. | | 700.12E. | | | | 3)NOTE: PLEASE SEE MIN OCP FOR WATER | | HEATER SHALL BE SIZED A MIN OF 125%. | | 422.13 | | | | 4)NOTE: PLEASE SEE WALL A/C UNIT ON | | PANEL SCHEDULE WHICH INDICATES A 5KW | | UNIT ON A 1-POLE 20A BRKR? PLEASE | | CORRELATE WITH LOAD CALCUALTIONS, AS | | LOAD CALCS INDICATE THE LOAD AS 1.5KW? | | 215.5 | | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-05-23 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-05-23 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-05-23 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2006-01-26 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-01-26 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-01-26 |
Time |
15:05 |
Sent To |
|
|
Notes |
2006-01-26 00:00:00 | ******PROVISO****** | | | | 1) FLOOR PLAN INDICATES THAT EXISTING | | FIRE SPRINKLER SYSTEM TO REMAIN, HOWEVER | | DRAWINGS SHOW NEW PIPING AND (2) HEADS. | | PLEASE EXPLAIN. | | | | 2) PLEASE PROVIDE FIRE RESISTANCE OR | | RETARDANT INFORMATION FOR NEW AWNING. | | | | 3) PLEASE SHOW FIRE EXTINGUISHER | | LOCATION. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-04-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-20 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-20 |
Time |
12:40 |
Sent To |
|
|
Notes |
2006-05-25 00:00:00 | 5/25/06-OFF "COMM" BD TO "P" | 2006-05-05 00:00:00 | TO "COMM" BD#34 | 2006-04-20 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-03-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-03-13 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-12-27 |
Time |
11:52 |
Sent To |
|
|
Notes |
2006-01-24 00:00:00 | TO "COMM" BD#55 | 2005-12-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-05-23 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-05-23 |
Time |
09:28 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2006-05-23 |
Time |
09:28 |
Sent To |
|
|
Notes |
2006-05-23 00:00:00 | RECIVED SUBMITTAL FOR CLOTHES DRYER. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-02-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2006-02-06 |
Time |
07:27 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2006-02-06 |
Time |
07:27 |
Sent To |
|
|
Notes |
2006-02-06 00:00:00 | PLAN DENIED | | PLEASE PROVIDE DETAILS ON MECHANICAL | | PLANS FOR DRYER EXHAUST. | | PLEASE SUBMITE A COPY OF THE | | MANUFACTURERS INSTRUCTIONS FOR THE | | DRYERS WITH THE PLANS. | | PLAN REVIEW BY HAROLD MOSER.561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-06-02 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-06-02 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-06-02 |
Time |
13:28 |
Sent To |
|
|
Notes |
2006-06-02 00:00:00 | DENIED; | | 1.WASHING MACHINE WASTE CONNECTION TO BE | | 3"FBC-2004 SEC. 406.3. A SANIARY CROSS | | CAN NOT BE USED. 3"X2" Y FITTING MUST BE | | USED SEC. 706.3 (EXCEPTION) CLEANOUT AT | | 48"AFF IS ALSO REQUIRED. | | 2.SHOW LOCATION OF VENT FOR FLOOR DRAIN | | AND TRAP PRIMER AND TYPE OF PRIMMER TO | | BE USED. | | 3.WATER HEATER DETAIL, SHOW MEANS OF | | CONTROLING THERMAL EXPANTION. SEC. | | 607.3. | | 4.WATER HAMMER ARRESTORS REQUIRED ON | | WATER PIPES AT WASHER HOOK UP. SEC 604.9 | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2006-03-04 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-04 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-04 |
Time |
08:03 |
Sent To |
|
|
Notes |
2006-03-04 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC2001 FUEL GAS CODEPLAN REVIEW | | FBC 2001 PLUMBING CODEPLAN REVIEW | | FBC 2001 FL ACESSIBILITY CODE PLAN | | REVIEW. | | SEE PROVISO | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-05-18 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-05-18 |
Time |
19:44 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-05-18 |
Time |
19:43 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-02-17 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-02-17 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-02-17 |
Time |
10:58 |
Sent To |
|
|
Notes |
2006-02-17 00:00:00 | FAILED: | | PLANNING AND ZONING: | | | | 1.PROVIDE RESPONSES IN WRITING. | | | | 2.PLEASE BE ADVISED THAT A REQUEST FOR A | | NEW AWNING AND ADDITIONAL SQUARE FOOTAGE | | TO A BUILDING IN THE PLANNED DEVELOPMENT | | WILL NEED A MINOR AMENDMENT APPLICATION | | SUBMITTAL AND APPROVAL, PRIOR TO | | SIGN-OFF FROM PLANNING AND ZONING. | | | | 3. PROVIDE SITE PLAN SHOWING LOCATION OF | | THE PROPOSED LAUNDRY FACILITY BUILDING | | WITHIN THE IBIS PLANNED DEVELOPMENT. | | | | SHOULD YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT: | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | (561) 822-1435 |
|
|