Plan Review Details - Permit 05121022
Plan Review Stops For Permit 05121022
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-08 Cont ID  
Sent By shill Date 2006-05-08 Time 19:33 Rev Time 0.00
Received By shill Date 2006-05-08 Time 19:10 Sent To  
Notes
2006-05-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)THE SCOPE OF WORK IS NOT CLEAR.
 THE APPLICATION STATES "EXPANSION",
 WHICH IMPLIES AN ADDITION, BUT A
 FOUNDATION PLAN IS NOT SHOWN.NO SITE
 PLAN WAS PROVIDED.THE PLANS STATE BOTH
 "EXIST CART BARN" AND "NEW LAUNDRY".
  
 SECOND REVIEW - SCOPE OF WORK WAS
 CLARIFIED, BUT CHANGES TO THE PLAN HAVE
 TRIGGERED NEW COMMENTS.
  
 2.)ONLY A PARTIAL FLOOR PLAN WAS
 PROVIDED.WHAT IS IN THE REST OF THE
 BUILDING?DECLARE OCCUPANCY FOR THIS
 AREA AND ADJACENT AREA, ADDRESSING ANY
 FIRE RATING REQUIREMENTS, IF ANY.SHOW
 NEARBY STRUCTURES.
  
 SECOND REVIEW - BUSINESS OCCUPANCY WAS
 DECLARED.READ FBC 311.THIS IS NOT
 BUSINESS OCCUPANCY, READ FBC304.1. THE
 CART STORAGE AREA IS S1.THE LAUNDRY IS
 EITHER MIXED USE F1 306.2 OR INCIDENTAL
 USE FBC 302.1.1.READ CHAPTER 3 AND
 DECLARE CORRECT OCCUPANCY. IF THIS IS
 MIXED USE, SHOW REQUIRED FIRE SEPARATION
 OF 2 HOURS.
  
 DECLARE CONSTRUCTION TYPE FBC6.TYPE
 III WAS DECLARED, A OR B?
  
 3.)THE SINGLE DOORAPPEARS TO LEAD
 OUTSIDE; IS THIS CORRECT?WHY DOES THE
 WALL THAT IT IS PERPENDICULAR TO EXTEND
 FURTHER, IMPLYING ADDITIONAL AREA?ALSO
 THIS DOOR IS FIRE RATED, IMPLYING A
 SEPARATION, AND THE DOUBLE DOOR DOES NOT
 SHOW A FIRE RATING.IF THIS DOOR LEADS
 TO INTERIOR SPACE, EVEN IF IT IS A WORK
 SPACE, THE DOOR MUST MEET MANEUVERING
 CLEARANCE FBC11-4.13.6.
  
 SECOND REVIEW - THE DOOR HAS BEEN
 RELOCATED BUT NOW BLOCKS OVER HALF THE
 REQUIRED WIDTH OF THE PASSAGEWAY,
 FBC1008.1.8.8.
  
 4.)ADDRESSED, NOT AN ADDITION.
  
 5.)IF THIS IS AN ADDITION, SHOW A WALL
 DETAIL CONTINUOUS FROM THE FOUNDATION
 THROUGH THE ROOF, ALL WIND DESIGN
 CRITERIA, FBC16.
  
 SECOND REVIEW - ALTHOUGH THIS IS NOT AN
 ADDITION, THERE IS STILL AN EXTERIOR
 ALTERATION (DOORS).PROVIDE WIND DESIGN
 CRITERIA FBC1603.1.4.
  
 6.) ADDRESSED.A LOCAL PRODUCT APPROVAL
 WILL BE ISSUED USING THE NOA.
  
 7.)ADDRESSED.
  
 NEW COMMENTS:
  
 8.)PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By shill Date 2006-03-13 Time 11:17 Rev Time 0.00
Received By shill Date 2006-03-13 Time 11:17 Sent To  
Notes
2006-03-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE SCOPE OF WORK IS NOT CLEAR.
 THE APPLICATION STATES "EXPANSION",
 WHICH IMPLIES AN ADDITION, BUT A
 FOUNDATION PLAN IS NOT SHOWN.NO SITE
 PLAN WAS PROVIDED.THE PLANS STATE BOTH
 "EXIST CART BARN" AND "NEW LAUNDRY".
  
 2.)ONLY A PARTIAL FLOOR PLAN WAS
 PROVIDED.WHAT IS IN THE REST OF THE
 BUILDING?DECLARE OCCUPANCY FOR THIS
 AREA AND ADJACENT AREA, ADDRESSING ANY
 FIRE RATING REQUIREMENTS, IF ANY.SHOW
 NEARBY STRUCTURES.
  
 3.)THE SINGLE DOORAPPEARS TO LEAD
 OUTSIDE; IS THIS CORRECT?WHY DOES THE
 WALL THAT IT IS PERPENDICULAR TO EXTEND
 FURTHER, IMPLYING ADDITIONAL AREA?ALSO
 THIS DOOR IS FIRE RATED, IMPLYING A
 SEPARATION, AND THE DOUBLE DOOR DOES NOT
 SHOW A FIRE RATING.IF THIS DOOR LEADS
 TO INTERIOR SPACE, EVEN IF IT IS A WORK
 SPACE, THE DOOR MUST MEET MANEUVERING
 CLEARANCE FBC11-4.13.6.
  
 4.)IF THIS IS AN ADDITION, PROVIDE A
 SITE PLAN.IMPACT FEES REQUIRED,
 233-5025.
  
 5.)IF THIS IS AN ADDITION, SHOW A WALL
 DETAIL CONTINUOUS FROM THE FOUNDATION
 THROUGH THE ROOF, ALL WIND DESIGN
 CRITERIA, FBC16.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 7.)NOT ENOUGH INFORMATION TO
 DETERMINE CODE COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 07:53 Rev Time 0.00
Received By dpalmer Date 2006-05-08 Time 22:47 Sent To  
Notes
2006-05-09 00:00:00***** UNSAT *********
  
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS
 REVIEW. PLEASE INDICATE THE FEEDERS TO
 THIS EXISTING PANEL.
 INDICATE THE MEANS OF DISCONNECT
 REQUIRED PER 225.31-225.39
 PLEASE SEE 250.32.
 240.4,310.16, ETC.
  
 2) NOTE: PLEASE SEE CIRCUITING FOR NEW
 EM LT IS NOW SHOWN CIRCUITED TO THE
 COUNTER SPACE RECEPT?
 PLEASE SEE 700.12E. ALL EM/EXT LTS SHALL
 BE CIRCUITED TO THE LOCAL LIGHTING
 BRACNCH CIRCUIT.
  
 3) NOTE: PLEASE SEE SEE ORIG NOTE
 MENTIONED THE MIN OCP FOR THE WATRE
 HEATER HAD TO BE 125%. PLEASE SEE NOW,
 THE KW RATING IS SHOWN AT 4KW AND THE
 OCP IS SHOWN TOO HIGH.
 PLEASE SEE 422.11(E)3) MAX OCP SHOULD BE
 150%. PLEASE KNOW, THIS WOULD BE 25A'S.
  
 4) NOTE: PLEASE SEE WATER HEATER IS NOW
 BEINGSHOWN IN A CLOSED IN AREA AND
 DOES NOT INDICATE WHERE THE ACCESS IS?
 422.17,110.26 ETC.
  
 5) NOTE: PLEASE SEE THAT HAND DRAWN
 CHNAGES ARE NOT PERMITTED ON PLANS WHICH
 ARE SIGNED, DATED AND SEALED BY AN
 ARCHITECT OR ENGINEER.
 FS 471/481
 PLEASE SEE HAND WRITTEN CHANGE OVER WHAT
 WAS SHOWN AS 100A PANEL, NOW DRAWN AS
 200A'S.?
  
 6) NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT CODE
 COMPLIANT COMMENTS.
  
 PLEASE CORRELATE ALL OF THE ABOVE.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE SURE TO SEE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-05-08 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-24 Cont ID  
Sent By dpalmer Date 2006-01-24 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2006-01-24 Time 18:29 Sent To  
Notes
2006-01-24 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN
 AS EXISTING, HOWEVER PLEASE INDICATE IF
 THE EXISTING FEEDERS. THIS CAN BE NOTED.
 PLEASE ALSO INDICATE OF PANEL CONTAINS A
 MEANS OF DISCONNECT, MCB ?SINCE THIS
 SEEMS TO BE SHOWN AS A DETACHED BLDG.
 PLEASE ALSO INDICATE GROUNDING ELECTRODE
 , NEW OR EXISTING FOR THIS PANEL AT
 DETACHED BLDG.
 ALL PER 240.4,310.16,225.31,250.32 ETC.
  
 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE PANEL SCHEDULE
 SUBMITTED.
 215.5
 PLEASE BE SURE TO INDICATE THE EM LT
 CIRCUITED TO THE SAME CIRCUIT FEEDING
 THE LOCAL LIGHTING BRANCH CIRCUIT.
 700.12E.
  
 3)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATER SHALL BE SIZED A MIN OF 125%.
 422.13
  
 4)NOTE: PLEASE SEE WALL A/C UNIT ON
 PANEL SCHEDULE WHICH INDICATES A 5KW
 UNIT ON A 1-POLE 20A BRKR? PLEASE
 CORRELATE WITH LOAD CALCUALTIONS, AS
 LOAD CALCS INDICATE THE LOAD AS 1.5KW?
 215.5
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By mwennerg Date 2006-05-23 Time 13:53 Rev Time 0.00
Received By mwennerg Date 2006-05-23 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-26 Cont ID  
Sent By mwennerg Date 2006-01-26 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2006-01-26 Time 15:05 Sent To  
Notes
2006-01-26 00:00:00******PROVISO******
  
 1) FLOOR PLAN INDICATES THAT EXISTING
 FIRE SPRINKLER SYSTEM TO REMAIN, HOWEVER
 DRAWINGS SHOW NEW PIPING AND (2) HEADS.
 PLEASE EXPLAIN.
  
 2) PLEASE PROVIDE FIRE RESISTANCE OR
 RETARDANT INFORMATION FOR NEW AWNING.
  
 3) PLEASE SHOW FIRE EXTINGUISHER
 LOCATION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-20 Cont ID  
Sent By adarroug Date 2006-04-20 Time 12:40 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 12:40 Sent To  
Notes
2006-05-25 00:00:005/25/06-OFF "COMM" BD TO "P"
2006-05-05 00:00:00TO "COMM" BD#34
2006-04-20 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-13 Cont ID  
Sent By shill Date 2006-03-13 Time 11:17 Rev Time 0.00
Received By shill Date 2005-12-27 Time 11:52 Sent To  
Notes
2006-01-24 00:00:00TO "COMM" BD#55
2005-12-27 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By tgordon Date 2006-05-23 Time 09:28 Rev Time 0.25
Received By tgordon Date 2006-05-23 Time 09:28 Sent To  
Notes
2006-05-23 00:00:00RECIVED SUBMITTAL FOR CLOTHES DRYER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-06 Cont ID  
Sent By hmoser Date 2006-02-06 Time 07:27 Rev Time 0.00
Received By hmoser Date 2006-02-06 Time 07:27 Sent To  
Notes
2006-02-06 00:00:00PLAN DENIED
 PLEASE PROVIDE DETAILS ON MECHANICAL
 PLANS FOR DRYER EXHAUST.
 PLEASE SUBMITE A COPY OF THE
 MANUFACTURERS INSTRUCTIONS FOR THE
 DRYERS WITH THE PLANS.
 PLAN REVIEW BY HAROLD MOSER.561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 13:28 Rev Time 0.00
Received By jleech Date 2006-06-02 Time 13:28 Sent To  
Notes
2006-06-02 00:00:00DENIED;
 1.WASHING MACHINE WASTE CONNECTION TO BE
 3"FBC-2004 SEC. 406.3. A SANIARY CROSS
 CAN NOT BE USED. 3"X2" Y FITTING MUST BE
 USED SEC. 706.3 (EXCEPTION) CLEANOUT AT
 48"AFF IS ALSO REQUIRED.
 2.SHOW LOCATION OF VENT FOR FLOOR DRAIN
 AND TRAP PRIMER AND TYPE OF PRIMMER TO
 BE USED.
 3.WATER HEATER DETAIL, SHOW MEANS OF
 CONTROLING THERMAL EXPANTION. SEC.
 607.3.
 4.WATER HAMMER ARRESTORS REQUIRED ON
 WATER PIPES AT WASHER HOOK UP. SEC 604.9
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-03-04 Cont ID  
Sent By pschmitz Date 2006-03-04 Time 08:03 Rev Time 0.00
Received By pschmitz Date 2006-03-04 Time 08:03 Sent To  
Notes
2006-03-04 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW.
 SEE PROVISO
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-18 Cont ID  
Sent By lfranco Date 2006-05-18 Time 19:44 Rev Time 0.00
Received By lfranco Date 2006-05-18 Time 19:43 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-17 Cont ID  
Sent By lfranco Date 2006-02-17 Time 12:48 Rev Time 0.00
Received By lfranco Date 2006-02-17 Time 10:58 Sent To  
Notes
2006-02-17 00:00:00FAILED:
 PLANNING AND ZONING:
  
 1.PROVIDE RESPONSES IN WRITING.
  
 2.PLEASE BE ADVISED THAT A REQUEST FOR A
 NEW AWNING AND ADDITIONAL SQUARE FOOTAGE
 TO A BUILDING IN THE PLANNED DEVELOPMENT
 WILL NEED A MINOR AMENDMENT APPLICATION
 SUBMITTAL AND APPROVAL, PRIOR TO
 SIGN-OFF FROM PLANNING AND ZONING.
  
 3. PROVIDE SITE PLAN SHOWING LOCATION OF
 THE PROPOSED LAUNDRY FACILITY BUILDING
 WITHIN THE IBIS PLANNED DEVELOPMENT.
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT:
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 (561) 822-1435