Plan Review Details - Permit 05121006
Plan Review Stops For Permit 05121006
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-03 Cont ID  
Sent By dpalmer Date 2006-01-03 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2006-01-03 Time 07:20 Sent To  
Notes
2006-01-03 00:00:00ELEC ONLY.
 FA DEVICES FOR FIRE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-03 Cont ID  
Sent By mwennerg Date 2006-01-03 Time 10:29 Rev Time 0.00
Received By mwennerg Date 2006-01-03 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 10:43 Sent To M
Notes
2006-02-16 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-16 Cont ID  
Sent By tgordon Date 2006-02-16 Time 15:19 Rev Time 0.00
Received By tgordon Date 2005-12-23 Time 10:09 Sent To  
Notes
2005-12-23 00:00:00TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-16 Cont ID  
Sent By tgordon Date 2006-02-16 Time 14:31 Rev Time 0.25
Received By tgordon Date 2006-02-16 Time 14:31 Sent To  
Notes
2006-02-16 00:00:00*** PROVISO ***
 1) ENGINEER STAMPED DRAWINGS (2 COPYS)
 FOR CONDENSER STAND TO BE ON JOB SITE
 FOR INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By tgordon Date 2005-12-28 Time 14:03 Rev Time 0.25
Received By tgordon Date 2005-12-28 Time 14:03 Sent To  
Notes
2005-12-28 00:00:00*** DENIED ***
 1) ENGINEER NEEDS TO SHOW HOW THE
 CONDENSER STAND IS TO BE MOUNTED TO THE
 CONCRETE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.