Plan Review Details - Permit 05120772
Plan Review Stops For Permit 05120772
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By lursu Date 2006-07-17 Time 16:22 Rev Time 0.00
Received By lursu Date 2006-07-17 Time 16:22 Sent To  
Notes
2006-07-17 00:00:00REQUEST FROM THE APPLICANT TO REMOVE 311
 CLEMATIS AS AN ADDRESS INITIALLY SET UP
 FOR THE SECOND LEVEL AND HAVE ONLY 309
 TO REMAIN ;SITE PLANS NECESSARY .311 IS
 NOT IN OUR SYSTEM AS A EXTENSION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-11-21 Cont ID  
Sent By shill Date 2006-11-21 Time 11:21 Rev Time 0.00
Received By shill Date 2006-11-21 Time 11:21 Sent To Z
Notes
2006-11-21 11:22:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)THE ENGINEER'S TITLE BLOCK IS TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002 (NAME OF THE
 PERSON SEALING THE DOCUMENT IS TO BE ON EACH SHEET).
  
 2.)TWO SETS OF SIGNED, SEALED, DATED ORIGINALS
 REQUIRED (ONLY ONE SEALED SET SUBMITTED).
  
 3.)THE PLANS APPEAR CODE COMPLIANT, BUT THEY DO NOT
 MATCH THE ARCHITECTURAL SHEETS.PLEASE REVISE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-11-06 Cont ID  
Sent By shill Date 2006-11-06 Time 08:49 Rev Time 0.00
Received By shill Date 2006-11-06 Time 08:49 Sent To  
Notes
2006-11-06 08:50:10RESTAMP, STRUCTURAL 8 1/2 X 11

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-03 Cont ID  
Sent By shill Date 2006-08-03 Time 16:25 Rev Time 0.00
Received By shill Date 2006-08-03 Time 16:25 Sent To  
Notes
2006-08-03 00:00:00STRUCTURAL DETAILS 7/2/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-10 Cont ID  
Sent By shill Date 2006-07-10 Time 08:26 Rev Time 0.00
Received By shill Date 2006-07-10 Time 08:26 Sent To  
Notes
2006-07-10 00:00:00***PROVISO***PROVIDE DESIGN PRESSURES,
 SEP PERMIT DOORS & SHUTTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-06 Cont ID  
Sent By shill Date 2006-07-06 Time 13:24 Rev Time 0.00
Received By shill Date 2006-07-06 Time 12:20 Sent To  
Notes
2006-07-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED
  
 2-5.)ADDRESSED.
  
 6.)THIRD REQUEST FOR PRODUCT APPROVALS
 FOR THE FRENCH DOORS.PRODUCT APPROVALS
 WERE SUBMITTED FOR THE IMPACT
 PROTECTION.CODE COMPLIANCE CANNOT BE
 DETERMINED AS ITEM #10 HAS NOT BEEN
 PROPERLY ADDRESSED.
  
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
  
 7-9.)
  
 10.)PROVIDE WIND DESIGN INFORMATION
 FBC1603.1.4.PROVIDE DESIGN PRESSURES
 FOR THE NEW DOORS.THIRD REQUEST.
  
 STATING THAT THE DOORS WILL WITHSTAND
 155 AND 175 MPH IS NOT PROVIDING DESIGN
 PRESSURES (ENGINEER), OR PROVIDING ALL
 INFORMATION REQUIRED BY FBC1603.1.4.
 THE ARCHITECT PROVIDED A COMPUTERIZED
 SHEET (WRONG CODE, FBC2001 RATHER THAN
 FBC2004) WITH SOME OF THE INFORMATION,
 BUT IT CONFLICTS WITH THE ENGINEER'S
 INCOMPLETE WIND INFORMATION, AND THE
 ARCHITECT'S COMPUTERIZED WIND CALCS ARE
 NOT SIGNED AND SEALED.
  
 THIS INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE.
  
 11.)THERE IS A HALF PARTITION WALL
 STILL SHOWN BETWEEN COLUMNS F1 AND G1.
 THIS SHOULD BE A TENANT PARTITION WALL,
 FIRE RATED.WHY IS A HALF HIGH WALL
 SHOWN?A-1.1.
  
 12-13.)ADDRESSED.
  
 14.)THIRD REVIEW - THE RAMP IS TO
 COMPLY WITH FBC11-4.8.NO DETAIL OR
 SLOPE WAS PROVIDED.IF HANDRAILS ARE
 REQUIRED, THEY ARE TO COMPLY WITH
 FBC11-4.8.5. PROVIDE SLOPE AND ELEVATION
 CHANGE.THE LEGEND SHOWS THE HEAVY
 SINGLE DASHED LINE AS DELINEATING
 EXISTING AND RENOVATED AREAS.IS THERE
 A WALL BETWEEN THE EXISTING KITCHEN AND
 THE STAGE 108?
  
 THE ELEVATIONS PROVIDED STATE "SLOPE TO
 WALL" OR "SLOPE TO SLAB".THE SLOPES AT
 THE RAMPS ARE NOT CLEAR.THERE ARE NO
 LANDINGS SHOWN, NO DIMENSION FOR THE
 RAMP, ONLY AN ELEVATION CHANGE OF 5.16".
 AS I DO NOT HAVE THE RUN DIMENSION I
 CANNOT DETERMINE THE SLOPE.
  
 15.)ADDRESSED.
  
 16.)HOW IS THE STAGE ACCESSIBLE?IT
 IS NOT CLEAR IF THE DARK LINE IS A WALL
 OR IF IT IS DELINEATING THE LINE BETWEEN
 THE AREA OF WORK AND AREA NOT INCLUDED
 IN THE REMODEL.
  
 VERTICAL ACCESSIBILITY REQUIRED, EITHER
 IN THE FORM OF A PERMANENT RAMP OR A
 LIFT, FBC11-4.1(1), 11-4.1.2(2),
 11-4.1.6(1)(B).
  
 3RD REVIEW - THE ARCHITECT'S LETTER
 STATES THAT THE STAGE DETAILS HAVE BEEN
 REMOVED, BUT THEY ARE STILL ON THE PLAN,
 ALL SHEETS.IT IS UNCLEAR AS TO HOW
 ACCESSIBILITY HAS BEEN ADDRESSED.
  
 17.)SHOW COMPLIANCE WITH FBC11-5.NO
 DETAILS IN REGARDS TO ACCESSIBILITY WERE
 SHOWN.
  
 SEE ITEM 16.THE RAMP PREVIOUSLY SHOWN
 ON THE PLAN IS NO LONGER ON THE PLAN.
 THE RAMP IMPLIES A CHANGE OF ELEVATION.
 OLD SHEETS WERE NOT INCLUDED IN THIS
 RESUB.SHOW ELEVATION CHANGES ON THE
 PLAN, INCLUDING IN THE AREA HATCHED AS
 AN AREA NOT PART OF THE REMODEL.THERE
 STILL MUST BE AN ACCESSIBLE ROUTE FROM
 THE NEW AREA TO THE EXISTING AREA.
  
 18.-19.)ADDRESSED.
  
 20.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE HAS BEEN CHARGED AS
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-18 Cont ID  
Sent By shill Date 2006-04-18 Time 09:46 Rev Time 0.00
Received By shill Date 2006-04-18 Time 09:46 Sent To  
Notes
2006-04-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED
  
 2-5.)ADDRESSED.
  
 6.)WHERE IS THE EXTERIOR WALL AT THE
 ENTRY?IS THIS LOCATION CHANGING?ARE
 THE FRENCH ENTRY DOORS SHOWN NEW OR
 EXISTING?IF THEY ARE NEW, PROVIDE
 PRODUCT APPROVALS.NOTE THAT IMPACT
 PROTECTION IS REQUIRED FBC EB 507.3,
 FBC16091.4.USE OF REMOVABLE SHUTTERS
 FOR COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.
 PLEASE CONTACT ME IF THIS IS YOUR
 INTENT.RESUBMITTING WITH PLANS SHOWING
 USE OF REMOVABLE SHUTTES WITHOUT AN
 APPROVED INSTALLATION PLAN WILL RESULT
 IN A DELAY OF PERMIT ISSUANCE.
  
 NOT ADDRESSED.IT IS NOW DETERMINED
 THAT AN EXTERIOR WALL IS BEING RELOCATED
 AND THAT NEW DOORS ARE BEING INSTALLED.
 NO PRODUCT APPROVALS SUBMITTED.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.AGAIN, FAILURE
 TO PROPERLY ADDRESS THIS COMMENT WILL
 RESULT IN A DELAY OF PERMIT ISSUANCE.
  
 7-8.) ADDRESSED.
  
 9.)IF THE BUILDING IS REQUIRED TO BE
 SPRINKLED BY CODE, SUPPLY FIRE SPRINKLER
 PLANS.
  
 NOT ADDRESSED.HAVING A SUBCONTRACTOR
 SUBMIT SHOPS AT A FUTURE DATE IS NOT
 SHOWING CODE COMPLIANCE ON THIS PLAN.
 PROVIDE A FIRE SPRINKLER PLAN AS
 REQUIRED BY FBC*106.3.5.1.1(5) AND
 FLORIDA STATUTE.
  
 10.)DECLARE GOVERNING CODE.IF
 EXTERIOR ALTERATIONS ARE INCLUDED IN
 THIS PROJECT, PROVIDE WIND DESIGN
 INFORMATION FBC1603.1.4.
  
 THE ARCHITECT REFERS TO THE STRUCTURALS,
 THE ENGINEER HAS STATED THAT NO EXTERIOR
 WORK IS TO BE DONE.YOU ARE RELOCATING
 AN EXTERIOR WALL AND INSTALLING EXTERIOR
 DOORS.THIS IS EXTERIOR WORK.PROVIDE
 INFORMATION REQUESTED, INCLUDING DESIGN
 PRESSURES FOR THE NEW DOORS.
  
 11-13.)ADDRESSED.
  
 14.)THE RAMP IS TO COMPLY WITH
 FBC11-4.8.NO DETAIL OR SLOPE WAS
 PROVIDED.IF HANDRAILS ARE REQUIRED,
 THEY ARE TO COMPLY WITH FBC11-4.8.5.
 PROVIDE SLOPE AND ELEVATION CHANGE.THE
 RAMP APPEARS TO LEAD TO THE REAR AREA,
 WHICH WOULD IMPLY THAT THE HEAVY DASHED
 LINE IS NOT A WALL.PLEASE PROVIDE A
 LEGEND FOR CLARIFICATION.
  
 YOU HAVE CHANGED THE LINE FROM A DASHED
 TO A SOLID, AND A LETTER STATING THAT
 HIS DELINEATES THE WORK AREA.PROVIDE A
 LEGEND ON THE PLAN AS REQUESTED AS A
 RESPONSE LETTER IS TO ASSIST IN PLAN
 REVIEW, NOT TO SHOW CODE COMPLIANCE, AND
 THE LETTER IS NOT A PART OF THE PLAN.
  
 PROVIDE ELEVATIONS AS REQUESTED.THE
 ARCHITECT HAS RESPONDED THAT HANDRAILS
 ARE NOT NECESSARY.ACCESSIBILITY
 REQUIRED TO ALL AREAS.PROVIDE THE
 INFORMATION REQUESTED.THE PLANS ARE TO
 SHOW CODE COMPLIANCE.
  
 15.)ADDRESSED.
  
 16.)HOW IS THE STAGE ACCESSIBLE?IT
 IS NOT CLEAR IF THE DARK LINE IS A WALL
 OR IF IT IS DELINEATING THE LINE BETWEEN
 THE AREA OF WORK AND AREA NOT INCLUDED
 IN THE REMODEL.
  
 VERTICAL ACCESSIBILITY REQUIRED, EITHER
 IN THE FORM OF A PERMANENT RAMP OR A
 LIFT, FBC11-4.1(1), 11-4.1.2(2),
 11-4.1.6(1)(B).
  
 17.)SHOW COMPLIANCE WITH FBC11-5.NO
 DETAILS IN REGARDS TO ACCESSIBILITY WERE
 SHOWN.
  
 SEE ITEM 16.THE RAMP PREVIOUSLY SHOWN
 ON THE PLAN IS NO LONGER ON THE PLAN.
 THE RAMP IMPLIES A CHANGE OF ELEVATION.
 OLD SHEETS WERE NOT INCLUDED IN THIS
 RESUB.SHOW ELEVATION CHANGES ON THE
 PLAN, INCLUDING IN THE AREA HATCHED AS
 AN AREA NOT PART OF THE REMODEL.THERE
 STILL MUST BE AN ACCESSIBLE ROUTE FROM
 THE NEW AREA TO THE EXISTING AREA.
  
 NEW COMMENTS:
  
 18.)TWO COPIES OF ALL DOCUMENTS
 REQUIRED.ONLY ONE SET OF ENGINEERING
 WAS SUBMITTED.
  
 19.)WAS A SOILS INVESTIGATION REPORT
 DONE TO DETERMINE SOIL BEARING CAPACITY?
 IF IT WAS, PROVIDE TWO SIGNED, SEALED
 ORIGINALS.IF NOT, THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT A SOILS
 INVESTIGATION REPORT WILL BE REQUIRED
 BEFORE FIRST INSPECTION.
  
 20.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF THE
 COMMENTS ARE NOT PROPERLY ADDRESSED IN
 THE THIRD REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-01 Cont ID  
Sent By shill Date 2006-02-01 Time 10:55 Rev Time 1.50
Received By shill Date 2006-01-27 Time 08:23 Sent To  
Notes
2006-02-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED
  
 2.)SOME OF THE SHEETS ON A THIRD SET
 OF ENGINEERING ARE NOT SEALED.ONLY TWO
 SETS ARE REQUIRED FOR PERMITTING; EITHER
 HAVE THE UNSEALED SHEETS SEALED OR
 RETAIN THEM AND SUBMIT TWO SETS.
  
 3.)THE SITE PLAN HAS TWO SEPARATE
 PARCELS HIGHLIGHTED, BOTH 313 AND 309
 CLEMATIS AND PART OF301 CLEMATIS,
 ENDING IN PARCEL ID NUMBERS 0170, 0180,
 AND 0190 RESPECTIVELY.THE APPLICATION
 IS FOR 309 CLEMATIS.CLARIFY.THE
 IMPROVEMENT CANNOT CROSS OVER PROPERTY
 LINES.
  
 4.)THE EXISTING FLOOR PLAN PREPARED BY
 THE ENGINEER SHOWS ONE TENANT SPACE.
 THE ARCHITECT?S PLAN HAS A DASHED LINE
 WHICH APPARENTLY SHOWS SCOPE OF WORK.
 IS THIS CORRECT?OR IS THIS A WALL WITH
 A TENANT SEPARATION?USUALLY THE DASHED
 LINE AS SHOWN DEPICTS A 1 HOUR
 SEPARATION.NO WALL LEGEND WAS
 PROVIDED.
  
 5.)AREA 100, OUTDOOR PATIO, IS TO
 MATCH THE ELEVATION OF THE EXISTING
 SIDEWALK.WHAT IS THE ELEVATION
 DIFFERENCE BETWEEN THE NEW OUTDOOR PATIO
 AND THE FINISHED FLOOR OF THE INTERIOR
 (ACCESSIBLE ENTRANCE/EXIT)?SEE FBC11.
  
 6.)WHERE IS THE EXISTING EXTERIOR WALL
 AT THE ENTRY?IS THIS LOCATION
 CHANGING?ARE THE FRENCH ENTRY DOORS
 SHOWN NEW OR EXISTING?IF THEY ARE NEW,
 PROVIDE PRODUCT APPROVALS.NOTE THAT
 IMPACT PROTECTION IS REQUIRED FBC EB
 507.3, FBC1609.1.4.USE OF REMOVABLE
 SHUTTERS FOR COMMERCIAL BUILDINGS MUST
 BE APPROVED BY THE BUILDING OFFICIAL.
 PLEASE CONTACT ME IF THIS IS YOUR
 INTENT.RESUBMITTING WITH PLANS SHOWING
 USE OF REMOVABLE SHUTTERS WITHOUT AN
 APPROVED INSTALLATION PLAN WILL RESULT
 IN A DELAY OF PERMIT ISSUANCE.
  
 7.)NO DETAIL WAS PROVIDED FOR THE
 WALLS/COLUMNS ON EITHER SIDE OF THE
 ENTRY DOORS.IS THIS NEW OR EXISTING?
  
 8.)DECLARE THE TOTAL SQUARE FOOT AREA
 FOR THE SPACE, OCCUPANCY CLASSIFICATION
 FBC 3, OCCUPANT LOAD FBC1004, BUILDING
 TYPE, SPRINKLED OR UNSPRINKLED.
  
 9.)IF THE BUILDING IS REQUIRED TO BE
 SPRINKLED BY CODE, SUPPLY FIRE SPRINKLER
 PLANS.
  
 10.)DECLARE GOVERNING CODE.IF
 EXTERIOR ALTERATIONS ARE INCLUDED IN
 THIS PROJECT, PROVIDE WIND DESIGN
 INFORMATION FBC1603.1.4.
  
 11.)WHY IS THERE A DIFFERENT WALL TYPE
 DEPICTED BETWEEN COLUMN LINES D AND F,
 WEST SIDE?IS THIS A WALL OR OPEN?
  
 12.)SHOW ALL REQUIRED FIRE
 SEPARATIONS, VERTICAL AND HORIZONTAL,
 AND NOTE HOW THIS RENOVATION WILL AFFECT
 THE FIRE SEPARATIONS.SCOPE OF WORK IS
 NOT CLEAR FROM THE PLAN.
  
 13.)WHAT IS THE PURPOSE OF THE NEW
 COLUMNS AND BEAMS?SPECIFY DESIGN
 LOADS.DECLARE OCCUPANCY OF THE SECOND
 FLOOR, WHICH THIS BEAM IS NOW APPARENTLY
 SUPPORTING.
  
 14.)THE RAMP IS TO COMPLY WITH
 FBC11-4.8.NO DETAIL OR SLOPE WAS
 PROVIDED.IF HANDRAILS ARE REQUIRED,
 THEY ARE TO COMPLY WITH FBC11-4.8.5.
 PROVIDE SLOPE AND ELEVATION CHANGE.THE
 RAMP APPEARS TO LEAD TO THE REAR AREA,
 WHICH WOULD IMPLY THAT THE HEAVY DASHED
 LINE IS NOT A WALL.PLEASE PROVIDE A
 LEGEND FOR CLARIFICATION.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE STAGE CONSTRUCTION.
  
 16.)HOW IS THE STAGE ACCESSIBLE?IT
 IS NOT CLEAR IF THE DARK LINE IS A WALL
 OR IF IT IS DELINEATING THE LINE BETWEEN
 THE AREA OF WORK AND AREA NOT INCLUDED
 IN THE REMODEL.
  
 17.)SHOW COMPLIANCE WITH FBC11-5.NO
 DETAILS IN REGARDS TO ACCESSIBILITY WERE
 SHOWN.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 10:36 Sent To  
Notes
2006-06-29 00:00:00REDLINED 600.5
  
 TO BE FIELD VERIFIED, COULD NOT LOCATE
 ON PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 14:32 Sent To  
Notes
2006-04-03 00:00:00REDLINED 600.5
  
 TO BE FIELD VERIFIED, COULD NOT LOCATE
 ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 19:44 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 19:22 Sent To  
Notes
2006-01-20 00:00:00****UNSAT ****
  
  
 1)NOTE: PLEASE INDICATE THE NEW
 CIRCUTING ON PLANS AND CORRELATE WITH A
 PANEL SCHEDULE TO BE SUBMITTED.
 PLEASE SEE NEW BAR ARE ETC.
 215.5, 408.4
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM AND EXT LTS. THESE SAHLL BE
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FEEDING LOCAL LIGHTING.
  
 2)NOTE: PLEASE INDICATE A NEW OR
 EXISTING SIGN CIRCUIT AS REQUIRED PER
 600.5
  
 3)NOTE: PLEASE INDICATE THE SWITCHING
 FOR LIGHTING, FANS ETC ON PLANS.
  
 4)NOTE: PLANS SHOULD REFLECT THE CURRENT
 CODES IN EFFECT AS FOLLOWS.
 NFPA-101 2003, NFPA-72 2002, NFPA-70
 2002.
  
 5)NOTE: PLEASE INDICATE ANY NEW OR
 EXISTING LOADS BEING ADDED. PLEASE SE
 THE NUMBER OF RECEPTS BEING ADDED IS
 GREATER THAN THE EXISTING. PLEASE
 INCLUDE THE ADDED LOADS TO SERVICE AND
 VERIFY LOAD ON EXISTING SERVICE.
 220,215.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 14:36 Sent To  
Notes
2006-07-03 00:00:00RESUBMITTED PLANS INDICATE AN OCCUPANT
 LOAD OF LESS THAN 300.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-19 Cont ID  
Sent By mwennerg Date 2006-04-19 Time 10:43 Rev Time 0.00
Received By mwennerg Date 2006-04-19 Time 10:43 Sent To  
Notes
2006-04-19 00:00:00******APPROVED******
  
 1) EXISTING DOORS ARE TO BE REINSTALLED.
 PANIC HARDWARE IS REQUIRED IF SERVING AN
 AREA WITH OCCUPANT LOAD GREATER THAN
 100.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By mwennerg Date 2006-01-20 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2006-01-20 Time 14:15 Sent To  
Notes
2006-01-20 00:00:00******DENIED******
  
 1) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF THE RAMP.
  
 2) IT APPEARS THAT THE EMERGENCY LIGHT
 LOCATED NEAR THE MANTLE MAY BE
 OBSTRUCTED BY THE WALLS ON EITHER SIDE.
  
 3) PLEASE PROVIDE THE OCCUPANT LOAD. A
 NEW SIGN MAY BE OBTAINED BY THE BUREAU
 OF FIRE PREVENTION PRIOR TO OR AT THE
 TIME OF THE FIRE FINAL INSPECTION.
  
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS OF WALLS AND CEILINGS IN
 TERMS OF CLASS A,B,OR C ETC.
  
 5) SEPARATE SHOP DRAWINGS REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL IF
 APPLICABLE.
  
 6) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 09:58 Sent To B
Notes
2006-11-21 09:58:40TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 18:19 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 18:19 Sent To B
Notes
2006-11-04 18:19:45TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 13:30 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 13:30 Sent To P
Notes
2006-08-16 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 08:29 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 08:29 Sent To B
Notes
2006-08-03 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 09:47 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 09:47 Sent To B
Notes
2006-07-24 00:00:00TO "Z" BOX/SUBMITTAL
2006-07-12 00:00:007/12/06--WHEN APPL. COMES BACK FOR
 RESUB, MATTHEW FLIS TO SEE PLANS FIRST,
 HIS REVIEW MAY BE MINIMAL.ADARROUGH

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 13:16 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 13:16 Sent To  
Notes
2006-06-29 00:00:00TO "COMM" BD#19
2006-06-20 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 12:57 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 12:57 Sent To  
Notes
2006-04-05 00:00:00TO "COMM" BD#24
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-01 Cont ID  
Sent By shill Date 2006-02-01 Time 10:56 Rev Time 0.00
Received By shill Date 2005-12-19 Time 10:14 Sent To  
Notes
2006-01-19 00:00:00TO "COMM" BD#20
2005-12-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-21 Cont ID  
Sent By hmoser Date 2006-12-21 Time 17:18 Rev Time 0.00
Received By hmoser Date 2006-12-21 Time 17:17 Sent To  
Notes
2006-12-21 17:20:56PLAN DENIED
 NO DUCT SIZE,CFM,GRILLSIZE ON PLANS .PLANS AER NOT
 COMPLETE
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-01-26 Cont ID  
Sent By pkrauss Date 2006-01-26 Time 10:58 Rev Time 0.00
Received By pkrauss Date 2006-01-26 Time 10:58 Sent To B
Notes
2006-01-26 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE INDICATE SCOPE OF WORK.ANNOTATE
 IF A MECHANICAL CONTRACTOR WILL BE
 PROVIDING PLANS WITH MECHANICAL PERMIT
 APPLICATION.ADDITIONAL PERMITS
 REQUIRED FOR HOOD, FIRE SUPPRESSION OR
 WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-08-21 Cont ID  
Sent By jleech Date 2006-08-21 Time 08:59 Rev Time 0.00
Received By jleech Date 2006-08-21 Time 08:59 Sent To  
Notes
2006-08-21 00:00:00REVISION;
 CHANGED EQUIPMENT LOCATIONS IN BAR AREA.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-13 Cont ID  
Sent By pschmitz Date 2006-07-12 Time 07:43 Rev Time 0.00
Received By pschmitz Date 2006-07-13 Time 08:56 Sent To  
Notes
2006-07-12 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 1) SEE SHT A-1.2 WATER RISER,DWV.
  
 CONTACTED MIKE SCHMIDT PEACOCK & LEWIS
 772-220-9909
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-11 Cont ID  
Sent By pschmitz Date 2006-04-11 Time 14:41 Rev Time 0.00
Received By pschmitz Date 2006-04-11 Time 14:41 Sent To  
Notes
2006-04-11 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 UNSAT
  
 1( SEC106.3.5.1 COMMERCIAL BUILDINGS:
 PLUMBING RISER FOR DRAIN WASTE AND VENT,
 WATER PIPING DIAGRAM, PIPE SIZES, TYPE
 OF MATERIAL.
 FLOOR SINKS FOR ALL INDIRECT WASTE.
 FLOOR DRAINS IN WALK AREA.
 CONTACTED MIKE SCHMIDT PEACOCK & LEWIS
  
 772-220-9909
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-26 Cont ID  
Sent By pschmitz Date 2006-01-26 Time 10:24 Rev Time 0.00
Received By pschmitz Date 2006-01-26 Time 10:24 Sent To  
Notes
2006-01-26 00:00:00PLUMBING PLAN REVIEW, PAUL SCHMITZ
 DENIED
 FBC 2004 SEC.104.2 DRAWINGS AND
 SPECIFICATIONS.
 RELOCATING BAR:
 1)TWO OR MORE COPIES OF SPECIFICATIONS,
 AND DRAWINGS DRAWN TO SCALE WITH
 SUFFICENT CLARITY AND DETAIL TO INDICATE
 THE THE NATURE AND CHARACTER OF THE
 WORK. SHALL ACCOMPANY THE APPLICATION
 FOR PERMIT.
 END OF COMMENTS, QUESTIONS 561-805-6692
2006-01-20 00:00:00NEW BAR AREA. VERIFY SINKS?

Review Stop Z ZONING
Rev No 5 Status N Date 2006-08-02 Cont ID  
Sent By mflis Date 2006-08-02 Time 09:34 Rev Time 0.00
Received By mflis Date 2006-08-02 Time 09:34 Sent To  
Notes
2006-08-02 00:00:00STRUCTURAL DETAILS ONLY; ZONING REVIEW
 NOT APPLICABLE. NO CHANGE IN PLANS.
  
 MJF

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-14 Cont ID  
Sent By mflis Date 2006-07-14 Time 11:53 Rev Time 0.00
Received By mflis Date 2006-07-14 Time 11:53 Sent To  
Notes
2006-07-14 00:00:00RESUB OF ARCHITECTURAL FOR BUILDING
 ELEVATION REVIEW - SINGLE SHEET.
 -MJF

Review Stop Z ZONING
Rev No 3 Status F Date 2006-07-11 Cont ID  
Sent By mflis Date 2006-07-11 Time 11:57 Rev Time 0.00
Received By mflis Date 2006-07-11 Time 11:53 Sent To  
Notes
2006-07-11 00:00:00ACCORDING TO SECT 94-108(E)(5) - "THE
 FACADES ON RETAIL FRONTAGES AT SIDEWALK
 LEVEL SHALL BE DETAILED AND GLAZED AS
 STOREFRONTS. STOREFRONTS SHALL BE
 DIRECTLY ACCESSIBLE FROM SIDEWALKS.
 STOREFRONTS SHALL HAVE CLEAR GLAZED
 AREAS BETWEEN TWO AND EIGHT FEET FROM
 THE GROUND, EQUAL TO A MINIMUM OF 70
 PERCENT OF ITS FACADE LENGTH." PLEASE
 MODIFY ELEVATIONS AT ENTRY TO REFLECT
 THIS CODE REQUIREMENT.
  
 -MJF

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-26 Cont ID  
Sent By mflis Date 2006-05-26 Time 16:00 Rev Time 0.00
Received By mflis Date 2006-05-26 Time 16:00 Sent To  
Notes
2006-05-26 00:00:00PLANS SHALL PROVIDE EXTERIOR ELEVATIONS
 OF FRONT FACADE INDICATE
 DESIGN/MATERIALS OF NEW FACADE. MJF

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-09 Cont ID  
Sent By sgraham Date 2006-02-09 Time 09:21 Rev Time 0.00
Received By sgraham Date 2006-02-09 Time 09:20 Sent To I
Notes
***NONE***