Plan Review Stops For Permit 05120625 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-12-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-12-21 |
Time |
15:37 |
Rev Time |
0.33 |
Received By |
jgomez |
Date |
2005-12-21 |
Time |
15:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-12-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-12-12 |
Time |
18:48 |
Rev Time |
0.33 |
Received By |
jgomez |
Date |
2005-12-12 |
Time |
18:48 |
Sent To |
PC |
|
Notes |
2005-12-12 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- FLAT ROOF SYSTEM SELECTED IS LIMITED | | BY GENERAL LIMITATION #9 WITH THE MAX. | | DESIGN PRESSURES OF 45PSF. LIMITATION #9 | | DOESN'T ALLOW ADDITIONAL NAIL ENHANCING | | TO INCREASE THE UPLIFT RESISTANCE. NEED | | SYSTEM THAT MEETS THE DESIGN PRESSURES | | AS SHOWN ON TABLE 1609.6B OF FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
|