Plan Review Details - Permit 05120625
Plan Review Stops For Permit 05120625
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By jgomez Date 2005-12-21 Time 15:37 Rev Time 0.33
Received By jgomez Date 2005-12-21 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-12 Cont ID  
Sent By jgomez Date 2005-12-12 Time 18:48 Rev Time 0.33
Received By jgomez Date 2005-12-12 Time 18:48 Sent To PC
Notes
2005-12-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF SYSTEM SELECTED IS LIMITED
 BY GENERAL LIMITATION #9 WITH THE MAX.
 DESIGN PRESSURES OF 45PSF. LIMITATION #9
 DOESN'T ALLOW ADDITIONAL NAIL ENHANCING
 TO INCREASE THE UPLIFT RESISTANCE. NEED
 SYSTEM THAT MEETS THE DESIGN PRESSURES
 AS SHOWN ON TABLE 1609.6B OF FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712