Plan Review Details - Permit 05120425
Plan Review Stops For Permit 05120425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-31 Cont ID  
Sent By mjacobs Date 2006-01-31 Time 14:57 Rev Time 0.50
Received By mjacobs Date 2006-01-31 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-12 Cont ID  
Sent By mjacobs Date 2006-01-12 Time 16:16 Rev Time 2.00
Received By mjacobs Date 2006-01-11 Time 17:10 Sent To PC
Notes
2006-01-11 00:00:001) PLEASE INDICATEWHICH WALL MOUNT
 DETAIL WILL BE USED, ALSO THE END
 CONNECTION DETAIL FOR BOTH ACCORDIAN AND
 ROLL DOWN SHUTTERS. HI-LIGHT OR CIRCLE
 ON EACH PAGE WHICH ITEMS WILL BE USED.
  
 2) FBC. 1008.1.3.6
 THE TEMPORARY INSTALLATION OR CLOSURE OF
 STORM SHUTTERS, PANELS AND OTHER
 APPROVED HURRICANE PROTECTION DEVICES
 SHALL BE PERMITTED ON EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN GROUP R
 OCCUPANCIES DURING THE THREAT OF A
 STORM. SUCH DEVICES SHALL NOT BE
 REQUIRED TO COMPLY WITH THE OPERATIONAL
 CONSTRAINTS OF SECTION 1025.4. WHILE
 SUCH PROTECTION IS PROVIDED, AT LEAST
 ONE MEANS OF ESCAPE FROM THE DWELLING OR
 DWELLING UNIT SHALL BE PROVIDED.THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING OR DWELLING
 UNIT AND SHALL NOT BE LOCATED WITHIN A
 GARAGE.OCCUPANTS IN ANY PART OF THE
 DWELLING OR DWELLING UNIT SHALL BE ABLE
 TO ACCESS THE MEANS OF ESCAPE WITHOUT
 PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL.
  
 3)IF THE MAIN ENTRY DOOR WILL HAVE A
 ROLL DOWN SHUTTER, INDICATE ON THE FLOOR
 PLAN WHICH ONE OF WINDOW OR DOOR MEETS
 THE EGRESS REQUIREMENTS. EXPLAIN THE
 OPENING PROCEDURES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-31 Cont ID  
Sent By dpalmer Date 2006-01-31 Time 07:44 Rev Time 0.00
Received By dpalmer Date 2006-01-31 Time 07:29 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 19:41 Sent To B
Notes
2005-12-27 00:00:00****** UNSAT *****
  
 1)NOTE: PLEASE SUBMIT A WIRING DETAIL
 FOR CONNECTION OF THE ELECTRIC ROLL UP
 SHUTTER.
 PLEASE SHOW THW WIRING, DISCONNECT.
 215.5
  
 2)NOTE: PLEASE HAVE THE PERSON
 RESPONSIBLE FOR WIRING DIAGRAM PRINT
 NAME AND SIGN SAID PLANS PER FBC
 106.3.4.3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 10:02 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 10:02 Sent To E
Notes
2006-01-26 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-12 Time   Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 09:52 Sent To  
Notes
2005-12-13 00:00:00TO "E" BOX