Plan Review Details - Permit 05120334
Plan Review Stops For Permit 05120334
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-24 Cont ID  
Sent By alange Date 2006-03-24 Time 10:40 Rev Time 0.75
Received By alange Date 2006-03-24 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By alange Date 2006-02-15 Time 09:16 Rev Time 0.75
Received By alange Date 2006-02-15 Time 07:40 Sent To  
Notes
2006-02-15 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIEDOWNS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 5.VALUATION IS TOO LOW SHOULD REFLECT
 ALL MATERIALS AND LABOR FOR THE PROJECT.
 ADJUST VALUE OR WE WILL ADJUST IT
 ACCORDING TO MARSHALL AND SWIFT
 ESTIMATING GUIDE.ADDITIONAL PERMIT
 FEES WILL BE DUE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-28 Cont ID  
Sent By dpalmer Date 2006-03-28 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2006-03-28 Time 08:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 20:14 Sent To B
Notes
2006-03-16 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE NOTE FROM PREVIOUS
 REVIEW WHICH REQUIRED THE MISSING
 LICENSE INFORMATION ON TITLE BLOCK PER
 FAC 61G15-23.002 AND FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By dpalmer Date 2005-12-28 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2005-12-28 Time 14:23 Sent To B
Notes
2005-12-28 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION REQUIRED ON TITLE BLOCK AS
 REQUIRED UNDER FAC 61G15-23.002 AND FS
 471.023.
  
 2)NOTE: PLEASE INCLUDE A MIN OF 2-GRNDS
 RODS AND CWP AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.250.50
 TECHNICAL CODES MAY NOT BE QUOTED IN
 LEIU OF DETAILS ON PLANS.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE COMPLETE FEEDERS TO
 INTERIOR PANEL.
 PLEASE SEE CONDUCTORS ONLY SHOWN AS
 #1'S? HOW MANY #1'S, NEUTRALAND
 MISSING EQUIPMENT GROUNDING CONDUCTOR
 PER 250.110,250.24,250.122
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-03-27 Time 16:47 Rev Time 0.00
Received By adarroug Date 2006-03-27 Time 16:47 Sent To E
Notes
2006-03-27 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 11:14 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 11:14 Sent To E
Notes
2006-03-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 10:48 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 10:48 Sent To E
Notes
2005-12-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-15 Cont ID  
Sent By alange Date 2006-02-15 Time 09:17 Rev Time 0.00
Received By alange Date 2005-12-12 Time 14:56 Sent To  
Notes
2005-12-12 00:00:00TO 'Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 17:36 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 17:36 Sent To I
Notes
2005-12-22 00:00:00NO ZONING REQUIRED, THE PROPOSED WORK IS
 NOT CHANGING THE FOOT PRINT OF
 STRUCTURE.