Plan Review Details - Permit 05120268
Plan Review Stops For Permit 05120268
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-11 Cont ID  
Sent By mjacobs Date 2006-01-11 Time 16:21 Rev Time 1.00
Received By mjacobs Date 2006-01-11 Time 15:37 Sent To PC
Notes
2006-01-11 00:00:00BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-25 Cont ID  
Sent By dpalmer Date 2006-01-25 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2006-01-25 Time 13:36 Sent To PC
Notes
2006-01-25 00:00:00REDLINED NO OVER HEAD LINES INCLUDING
 LV.
 680.8

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By dpalmer Date 2005-12-28 Time 07:32 Rev Time 0.00
Received By dpalmer Date 2005-12-28 Time 07:24 Sent To P
Notes
2005-12-28 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 DETAIL ON PLANS WITH THE 8 1/2X 11
 SUBMITTED BY EASTERN EELCTRIC WHICH
 MENTIONS NEW PANEL ETC.
 PLEASE SEE DETAIL DOES NOT INCLUDE THE
 SAME INFORMATION.?
  
 2)NOTE: PLEASE SEE THE PLANS REFERENCE
 THE 2005 NEC?, PLEASE KNOW, THE STATE
 HAS NOT YET ADOPTED THE 2005 CODE.
 (PROBABLY NOT UNTIL OCT 2006 AT THE
 EARLIEST).
  
 3)NOTE: PLEASE SEE SURVEY SHOWS POOL
 WITHIN 5' OF REAR PROPERTY LINE, PLEASE
 VERIFY ANY OVER HEAD POWER LINES. ALL
 MUST MEET MIN CLEARENCES AS SET FORTH IN
 680.8 PLEASE SEE THIS IS 0-750VETC AND
 ABOVE. THIS CAN BE REDLINED, HOWEVER NOW
 WOULD BE THE TIME TO VERIFYSINCE PLANS
 ARE COMING BACK FOR CORRECTIONS BEFORE
 HAVING TO MOVE A POOL AT A LATER DATE,
 AS THE UTILITY COMPANIES WILL NOT BE
 MOVING.
 CONTRACTOR RESPONSIBLE TO MOVE POOL IF
 CLOSER THAN MIN.
  
 4)NOTE: PLEASE INCLUDE MIN LOAD
 CALCULATIONS FOR ADDED LOADS.
 PLEASE INCLUDE CONTINUOUS LOADS AT 125%.
 215.3,230.42, 220 ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-12-29 Cont ID  
Sent By mperson Date 2005-12-29 Time 15:50 Rev Time 0.00
Received By mperson Date 2005-12-29 Time 15:50 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:39 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:39 Sent To E
Notes
2006-01-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 10:54 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 10:54 Sent To E
Notes
2005-12-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-11 Time   Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 15:08 Sent To  
Notes
2005-12-10 00:00:00TO 'Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-29 Cont ID  
Sent By mperson Date 2005-12-29 Time 15:51 Rev Time 1.25
Received By mperson Date 2005-12-29 Time 15:51 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 17:12 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 17:12 Sent To I
Notes
***NONE***