Plan Review Details - Permit 05120232
Plan Review Stops For Permit 05120232
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-07-11 Cont ID  
Sent By mjacobs Date 2008-07-11 Time 10:18 Rev Time 0.00
Received By mjacobs Date 2008-07-11 Time 10:01 Sent To PC
Notes
2008-07-11 10:01:42REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-02-04 Cont ID  
Sent By mjacobs Date 2008-02-04 Time 13:59 Rev Time 0.00
Received By mjacobs Date 2008-02-04 Time 12:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-30 Cont ID  
Sent By mjacobs Date 2007-11-30 Time 07:04 Rev Time 0.00
Received By mjacobs Date 2007-11-30 Time 06:02 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 08:40 Rev Time 1.50
Received By alange Date 2006-07-25 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-06 Cont ID  
Sent By alange Date 2006-06-06 Time 08:16 Rev Time 1.33
Received By alange Date 2006-06-06 Time 08:06 Sent To  
Notes
2006-06-06 00:00:00DENIED
  
  
 5.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUATION IS TOO LOW.
 THE ROOM ADDITION ALONE IS $143,481.00
 PLUS THE ENCLOSED CARPORT AND ANY OTHER
 ADDIONAL ITEMS.
 REVISE THE PERMIT VALUE AND PAY THE
 ADDITIONAL PERMIT FEES.
  
 6."R" VALUES ON ENERGY CALCS DO NOT
 MATCH THOSE ON PLANS.
  
 A.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 B. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
  
  
 NOTE:SINCE MUCH OF THIS WORK HAS BEEN
 COMPLETED WITH OUT INSPECTIONS
 ADDITIONAL ENGINNERING REPORTS MAY BE
 NEEDED AFTER THE PERMIT HAS BEEN ISSUED
 AND YOU ARE READY TO START INSPECTIONS.
 CONTACT KEN CONRAD CHIEF BUILDING
 INSPECTOR ONCE A PERMIT HAS BEEN ISSUED
 TO ARRANGE AN INSPECTION OF THE SITE TO
 DETERMINE WHAT ADDITIONAL ENGINEERING
 REPORTS THAT MAY BE NEEDED.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-14 Cont ID  
Sent By alange Date 2006-02-14 Time 15:56 Rev Time 2.25
Received By alange Date 2006-02-14 Time 15:08 Sent To  
Notes
2006-02-14 00:00:00DENIED
  
 1.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 2.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304, AND 305 OF THIS CODE.
 2004 EXISTING BUILDING CODE 301.5.
  
 3.PICTURES SHOW A LARGE SLIDING GLASS
 DOOR, YET PLANS SPEC OUT A SMALLER
 FRENCH DOOR.PLEASE CLARIFY.
  
 4.SHOW SQUARE FOOTAGE ON PLANS OF
 EXISTING AREAS AND NEW ROOM ADDITION AND
 GARAGE AREAS.
  
 5.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUATION IS TOO LOW.
 THE ROOM ADDITION ALONE IS $143,481.00
 PLUS THE ENCLOSED CARPORT AND ANY OTHER
 ADDIONAL ITEMS.
 REVISE THE PERMIT VALUE AND PAY THE
 ADDITIONAL PERMIT FEES.
  
 6.SUBMIT TWO COPIES OF ENERGY CALCS.
 TO THE 2004 FBC.
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 NOTE:SINCE MUCH OF THIS WORK HAS BEEN
 COMPLETED WITH OUT INSPECTIONS
 ADDITIONAL ENGINNERING REPORTS MAY BE
 NEEDED AFTER THE PERMIT HAS BEEN ISSUED
 AND YOU ARE READY TO START INSPECTIONS.
 CONTACT KEN CONRAD CHIEF BUILDING
 INSPECTOR ONCE A PERMIT HAS BEEN ISSUE
 TO ARRANGE AN INSPECTION OF THE SITE TO
 DETERMINE WHAT ADDITIONAL ENGINEERING
 REPORTS THAT MAY BE NEEDED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-02-04 Cont ID  
Sent By dpalmer Date 2008-02-04 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2008-02-04 Time 10:54 Sent To M
Notes
2008-02-04 10:54:54ELEC ON ARCH SHEETS NOW UPDATED.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-11-01 Cont ID  
Sent By mjacobs Date 2007-11-30 Time 07:04 Rev Time 0.00
Received By dpalmer Date 2007-11-01 Time 08:30 Sent To M
Notes
2007-11-01 08:52:17 
 ** DENIED REVISION**
  
  
 1) NOTE: PLEASE CLARIFY WHERE REVISION #8 IS LOCATED AS
 LISTED ON REVISION TITLE BLOCK.
 FBC 106.1.2 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 2) NOTE: PLEASE SEE RECEPTACLE ALONG KITCHEN WALL
 WITHIN 6FT OF DOOR IS STILL MISSING PER 210.52.
 REDLINED ON PREVIOUS PLANS.
  
 3) NOTE: PLEASE SEE KITCHEN WALL RECEPTACLES STILL
 SHOWN ON LIVING ROOM CIRCUIT WHICH IS NOT PERMITTED PER
 210.52B1.
  
 4) NOTE: PLEASE SEE BATHS 1 AND 2 ARE BOTH SHOWN
 CIRCUITED TOGETHER WHICH IS NOT PERMITTED PER 210.11C3.
 MAY ONLY CIRCUIT THE RECEPTACLES TOGETHER OR IF
 LIGHTING ETC IS ON WITH THE RECEPTACLE THEN NO OTHER
 AREAS OR ELECTRICAL IS PERMITTED TO BE FED. MAY NOT
 CIRCUIT AS SHOWN.
  
 5) NOTE: PLEASE SEE SHEET A-2 AS THIS SHOWS PANEL AS
 150AMPS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-05-02 Cont ID  
Sent By dpalmer Date 2007-05-02 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2007-05-02 Time 12:18 Sent To PC
Notes
2007-05-02 15:40:58REDLINED MISSING RECEPT PER 210.52, REDLINED KITCHEN
 RECEPT SHOWN ON LIV RM CIRCUIT WHICH IS NOT PERMITTED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-05 Cont ID  
Sent By dpalmer Date 2007-04-05 Time 13:26 Rev Time 0.00
Received By dpalmer Date 2007-04-05 Time 11:22 Sent To PC
Notes
2007-04-05 13:26:59** UNSAT **
  
  
 1) NOTE: PLEASE SEE RISER DIAGRAM AND PLANS DO NOT
 MATCH. PLEASE SEE THAT THE PANEL *B* STILL DOES NOT
 INCLUDE ANY BREAKER OR OCP FEEDING PANEL *A*..
 215.5, 240.4, 310.16
  
 2) NOTE: PLEASE SEE THAT NEW SMOKE ALARM CIRCUIT
 REQUIRES ARC FAULT PROTECTION PER 210.12.
 PLEASE SEE THAT ALL CIRCUITS IN SLEEPING ROOMS FOR LTS,
 SA?S , RECEPTS AND FANS ARE AFCI.
  
 3) NOTE: PLEASE SEE MISSING DISCONNECTS FOR AHU?S #1
 AND #2.
 440.11
  
 3) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL BOTH SEEM
 TO SHOWN TO THE SAME DEVICE/YOKE. PLEASE SEE 210.4 AS
 IF THIS IS INDEED AS SHOWN THEN THIS WOULD REQUIRE THE
 BOTH OF THESE ON A 2-POLE BREAKER.
  
 4) NOTE: PLEASE SEE JACUZZI TUB, PLEASE VERIFY THE
 BREAKER AND CONDUCTOR SIZE. THE SIZE OF THE CONDUCTORS
 WAS CHANGED TO #12 AWG, YET THE BREAKER WAS LEFT AT
 15AMPS?
 PLEASE VERIFY THIS AS IT IS NOT A CODE VIOLATION ONLY A
 COMMENT.
  
 5) NOTE: PLEASE SEE THAT NO HAND-DRAWN CHANGES ARE TO
 BE MADE TO PLANS. PLEASE SEE SEVERAL AREAS WHICH
 HAND-WRITTEN ITEMS WERE CHANGED.
 PLEASE REVISE THESE WHEN MAKING CORRECTIONS TO OTHER
 COMMENTS.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE PLANS ARE NOW CALLING FOR THE
 CODES TO BE LISTED UNDER THE 2005 NEC WHEN IN FACT THIS
 PROJECT WAS PERMITTED UNDER THE 2002 NEC.
 PLEASE LIST THE FOLLOWING CODES.
 2002 NFPA-70
 2002 NFPA-72
  
 7) NOTE: PLEASE SEE RECEPTACLES IN KITCHEN, DINING,
 BREAKFAST AREAS ARE TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS. PLEASE SEE 210.52B1, 210.11C1,
 220.16.
 PLEASE SEE SOME SHOWN ON THE LIGHTING CIRCUITS, THIS IS
 NOT PERMITTED.
  
 8) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE
 COMPLETE WITH ALL CIRCUITS TO ROOMS AND AREAS IN WHICH
 THEY FEED. THE USE OF *GENERAL LIGHTING * OR GEN
 RECEPTS* IS NOT PERMITTED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE CODE IN 408.4
 *
 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-09 Cont ID  
Sent By dpalmer Date 2007-02-09 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2007-02-09 Time 12:33 Sent To PC
Notes
2007-02-09 12:48:39***** UNSAT *****
  
  
 1) NOTE: PLEASE CORRELATE THE RISER DIAGRAM WITH ALL
 ELECTRICAL SERVICE EQUIPMENT AND PANEL SCHEDULES.
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS FROM METER
 TO PANEL *B* ARE NOT LARGE ENOUGH.
 PLEASE REMOVE ANY EQUIPMENT GROUNDING CONDUCTORS BEFORE
 THE FIRST MEANS OF DISCONNECT. (CONFUSING AS THE RISER
 AND PLANS DO NOT MATCH).
 PLEASE SEE MISSING EQUIPMENT GROUNDING AFTER THE FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250A MAIN ON 125A PANEL.
 PLEASE SEE LOAD ON PANEL EXCEEDS RATING.
 PLEASE SEE PLANS WHICH DO NOT MATCH WITH RISER.
 PLEASE SUBMIT THE PANEL SCHEDULE FOR THE METER/MAIN
 COMBO WHICH IS MENTIONED, IF THERE IS ONE.
 PLEASE COMPLETE AND CORRELATE LOADS ON EACH PANEL AND
 SERVICE.
 ETC.
 PLEASE SEE 310.16, 310.15B6, 240.4, 240.24, 408,
 230.70, 230.79, 230.76 ETC.
  
 *THERE ARE SEVERAL ITEMS WHICH NEED TO BE CORRECTED.
  
 2) NOTE: PLEASE SUBMIT A PANEL SCHEDULE WHICH REFLECTS
 ROOM AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE FOLLOWING TEXT WHICH WILL HELP EXPLAIN.
 THIS REQUIRES THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 3) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
  
 4) NOTE: PLEASE SEE THAT THERE ARE ELECTRICAL
 APPLIANCES AND EQUIPMENT ON PLANS WHICH ARE NOT ON
 PANEL SCHEDULES OR IN LOAD CALCULATIONS.
 240.4,310.16,220,408.4 ETC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-24 Cont ID  
Sent By btrobaug Date 2006-05-24 Time 13:01 Rev Time 0.50
Received By btrobaug Date 2006-05-24 Time 12:06 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 06:20 Sent To  
Notes
2005-12-29 00:00:00************ UNSAT ************
  
 *** PLEASE SEE SOME OF THE SAME NOTES
 ARE FOR THE REVIEWS DONE UNDER OLD
 "REMODEL" PERMIT OF 04120970.
  
 ** PLEASE SEE A 4X FEE WAS ADDED AS PER
 "HOLD" WHICH WAS IN COMPUTER AT TIME OF
 APPLICATION, HOWEVER WAS NOT ASSESSED.
 PLEASE KNOW THIS PROPERTY HAD A
 "STOPWORK" ORDER GIVEN IN 2003 FOR THE
 REAR ADDITION WHICH IS IN FULL EFFECT.
 FEES OWED.
  
 ***************************************
 PLEASE SEE NUMEROUS LOCATIONS ON PLANS
 IN WHICH PLANS ARE REFERENCING THE 2001
 FBC, PLEASE KNOW THE FBC IS NOW THE 2004
 EDITION WHICH WENT INTO EFFECT ON OCT.
 1ST, 2005
  
 1)NOTE: PLEASE SEE PLANS STILL DO NOT
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON TAKING RESPONSIBILITY OF
 SAID PLANS /DESIGN.
 PLEASE SEE FBC ADMINISTRATIVE SECTION,
 106.3.4.3
  
 2)NOTE: PLEASE CLARIFY SERVICE ONCE
 AGAIN, PLEASE SEE SERVICE EQUIPMENT OF
 SOME SORT IS BEING SHOWN AS 250A'S? BUT
 IS UNCLEAR IF THIS IS METER/MAIN OR A
 250A MB PANEL WITH SUB BRANCH BRKRS? NO
 SCHEDULE SUBMITTED?
 PLEASE INDICATE THE SIZE OF THE NEW
 METERCAN(ASBUILT).
 215.5
  
 3)NOTE: PLEASE SEE #14 AWG STILL BEING
 SHOWN WITH 20A OCP.
 240.4, 310.16
  
 4)NOTE: PLEASE SEE MISSING SD'S AS
 REQUIRED UNDER 2002 NFPA-72 11.5.1.1
 SD'S INSIDE AND OUTSIDEALL SLEEPING
 RMS. SEE 2ND FLR.
  
 5)NOTE: PLEASE SEE MISSING RECEPT W/IN
 6' OF DOOR WAY. 210.52
  
 6)NOTE: PLEASE SEE PLANS ARE STILL
 SHOWING THE AHU OUTSIDE???
 PLEASE SHOW ALL A/C EQUIPMENT ON PLANS
 ALONG WITH THE REQUIRED DISCONNECTS PER
 440.11
  
 7)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B)ATTACHED. PLEASE SEE IS
 PLANS COME BACK IN WITHOUT COMMENTS
 BEING FULLY ADDRESSED, PLANS SHALL BE
 TURNED INTO THE STATE FOR PEIR REVIEW BY
 THE FLORIDA BOARD OF ENGINEER'S.
  
  
  
 ** PLEASE SEE BLDG NOTES, AS PLANS SHOW
 DOORS AS BEING "FRENCH DOORS", HOWEVER
 SLIDING DOORS ARE INSTALLED.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-27 00:00:00IN ELEC FOR REVIEW, ON HOLD UNTIL4X
 FEE AS SHOWN IN COMPUTER IS CLEARED OR
 FEES ACCESSED.
 SHOULD HAVE BEEN ASSESSED WHEN SUBMITTED
 OR SIGNED OFF BY A BLDG DEPT MANG.

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 15:42 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 15:41 Sent To B
Notes
2008-07-01 15:42:34TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 11:29 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 11:29 Sent To  
Notes
2008-02-01 11:37:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 10:18 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 10:18 Sent To Z
Notes
2007-10-30 10:18:58TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 16:43 Sent To E
Notes
2007-05-01 16:44:09TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 18:14 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 18:14 Sent To M
Notes
2007-04-02 18:15:18MECH REV TO TOM GORDON

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 18:14 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 18:14 Sent To E
Notes
2007-04-02 18:14:44ELEC REV TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 16:50 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 16:50 Sent To M
Notes
2007-02-12 16:50:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 08:59 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 08:55 Sent To E
Notes
2007-02-08 09:00:48TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 15:37 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 15:37 Sent To B
Notes
2006-07-22 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 11:36 Sent To E
Notes
2006-05-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 11:53 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 11:53 Sent To Z
Notes
2006-05-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 08:56 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 08:56 Sent To E
Notes
2005-12-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-14 Cont ID  
Sent By alange Date 2006-02-14 Time 15:59 Rev Time 0.00
Received By alange Date 2005-12-06 Time 13:59 Sent To  
Notes
2005-12-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-02-04 Cont ID  
Sent By tgordon Date 2008-02-04 Time 11:43 Rev Time 0.40
Received By tgordon Date 2008-02-04 Time 11:43 Sent To B
Notes
2008-02-04 11:48:37*** PROVISO ***
 1) BATHROOM EXHAUST FANS SHALL BE INSTALLED WHERE
 REQUIRED BY 2004 FBC/R R303.3 EXCEPTION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-11-01 Cont ID  
Sent By tgordon Date 2007-11-01 Time 16:44 Rev Time 0.25
Received By tgordon Date 2007-11-01 Time 16:44 Sent To P
Notes
2007-11-01 16:45:30REVISION TO MECH. PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-07-26 Cont ID  
Sent By tgordon Date 2007-07-26 Time 13:43 Rev Time 0.25
Received By tgordon Date 2007-07-26 Time 13:43 Sent To  
Notes
2007-07-26 13:43:56REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-03 Cont ID  
Sent By tgordon Date 2007-04-03 Time 09:11 Rev Time 0.30
Received By tgordon Date 2007-04-03 Time 09:11 Sent To  
Notes
2007-04-03 09:12:26REVISION TO MECH. PLANS PAGE M-1 AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-15 Cont ID  
Sent By tgordon Date 2007-02-15 Time 08:52 Rev Time 0.30
Received By tgordon Date 2007-02-15 Time 08:52 Sent To  
Notes
2007-02-15 09:07:09MECHANICAL REVISION
 *** DENIED ***
 1) SEE NOTES: ON PLANS A/C WILL BE ACCORDING TO S.B.C.
 2001, THE BUILDING CODES BEING USED BY THE CITY OF WEST
 PALM BEACH IS THE 2004 F.B.C., PLEASE CORRECT.
  
 2) 12'X13" RETURN AIR DUCT FROM THE 2ND. FLOOR TO THE
 1ST. FLOOR IS TO SMALL FOR 1535 CFM'S., PLEASE CORRECT,
 PER 2004 FBC/R M1602.4.
  
 3) 10" RETURN AIR DUCT (FLEX) IN EXISTING FAMILY ROOM
 IS TO SMALL FOR 1125 CFM'S. AND 12'X12' GRILL, PLEASE
 CORRECT, PER 2004 FBC/R M1602.4.
  
 4) YELLOW HIGH LIGHTED RETURN AIR TRANSFER DUCT TO
 EXISTING BEDROOM NEEDS TO BE SIZED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-24 Cont ID  
Sent By tgordon Date 2006-05-24 Time 16:37 Rev Time 0.45
Received By tgordon Date 2006-05-24 Time 16:37 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By tgordon Date 2005-12-29 Time 10:14 Rev Time 0.45
Received By tgordon Date 2005-12-29 Time 10:14 Sent To B
Notes
2005-12-29 00:00:00*** DENIED ***
 1) NEED TO SUBMIT ENERGY CALCULATIONS.
 ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) NEED TO SHOW THE SIZE OF THE SUPPLY
 AND RETURN AIR DUCTS GOING DOWN TO THE
 FIRST FLOOR.
  
 4) SUPPLY AIR DUCT IN MASTER SUITE WIC
 IS NOT SIZED.
  
 5) ALL RETURN AIR DUCTS ARE TO SMALL SEE
 NOTE #6.
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-07 Cont ID  
Sent By jleech Date 2007-11-07 Time 08:56 Rev Time 0.00
Received By jleech Date 2007-11-07 Time 08:56 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 07:53 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 07:53 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By jleech Date 2005-12-29 Time 08:45 Rev Time 0.33
Received By jleech Date 2005-12-29 Time 08:45 Sent To M
Notes
2005-12-29 00:00:00DENIED;
 1.RISER DIAGRAM NOT SHOWN FOR MASTER
 BATHROOM ON 2ND FLOOR. PLEASE SUBMIT SO
 A PLUMBING PLAN REVIEW CAN BE DONE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-31 Cont ID  
Sent By choops Date 2007-10-31 Time 09:51 Rev Time 0.00
Received By choops Date 2007-10-31 Time 09:50 Sent To E
Notes
2007-10-31 10:02:42***APPROVED - REVISION - CHANGE WOOD FRAME WALLS TO
 CONCRETE BLOCK.***
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-18 Cont ID  
Sent By mmclean Date 2006-05-18 Time 15:50 Rev Time 0.00
Received By mmclean Date 2006-05-18 Time 15:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By mmclean Date 2005-12-20 Time 16:54 Rev Time 0.00
Received By mmclean Date 2005-12-20 Time 16:54 Sent To I
Notes
2005-12-20 00:00:00DENIED,
 1. MUST SHOW THE WORK (ADDITION) ON THE
 TWO COPY OF SURVEY WITH SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720