Plan Review Details - Permit 05120211
Plan Review Stops For Permit 05120211
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By mjacobs Date 2006-01-03 Time 16:00 Rev Time 1.25
Received By mjacobs Date 2006-01-03 Time 11:31 Sent To PC
Notes
2006-01-03 00:00:001)ALLINFORMATION/DRAWINGS/SPECIFICATIONS
  
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
  
 2) 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
  
 3) WPB AMENDMENTS 106.1.3 BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE. DRAWINGS SUBMITTED ARE NOT DRAWN
 TO SCALE. PLEASE COMPLY..ALSO SEE
 SEC. 106.1.2
  
 4) PLEASE INDICATE ON DRAWINGS WHAT IS
 EXISTING AND WHAT IS NEW. ALSO THE
 DIMENTIONS OF THE RAMP AND PLATFORM
 INCLUDING HEIGHT/LENGTH/SLOPE AND WIDTH
 IS REQUIRED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-03 Time   Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 15:28 Sent To  
Notes
2005-12-10 00:00:00TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***