Plan Review Details - Permit 05120170
Plan Review Stops For Permit 05120170
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-19 Cont ID  
Sent By alange Date 2006-10-19 Time 08:23 Rev Time 0.00
Received By alange Date 2006-10-19 Time 08:22 Sent To P
Notes
2006-10-19 08:24:55PROVISO:SEPERATE PERMIT REQUIRED FOR FLAT ROOF.
 BEDROOM WINDOWS SHALL MEET EMERGENCY ESCAPE OPENING
 SIZESR-310.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-07 Cont ID  
Sent By alange Date 2006-09-07 Time 14:09 Rev Time 0.75
Received By alange Date 2006-09-07 Time 14:09 Sent To  
Notes
2006-09-07 00:00:00DENIED
  
 NEW COMMENTS:
  
 1.SUBMIT TWO COPIES OF STATE PRODUCT
 APPROVALS. ONLY ONE HAS BEEN SUBMITTED.
  
 2.SELECT THE ROOF ASSEMBLY USED ON THE
 TAMKO PRODUCT APPROVAL.
  
 3.FRONT BUILDING, SINGLE HUNG 24 DOES
 NOT MEET EMERGENCY ESCAPE AND RESCUE
 OPENING REQUIREMENTS.FBC R-310
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-21 Cont ID  
Sent By alange Date 2006-07-21 Time 10:24 Rev Time 0.75
Received By alange Date 2006-07-21 Time 10:24 Sent To E
Notes
2006-07-21 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 COMMENTS FROM LAST REVIEW:
 C. PLANS SHALL BE SIGNED AND DATED BY
 THE DESIGNEER OF RECORD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-13 Cont ID  
Sent By alange Date 2006-04-13 Time 11:37 Rev Time 1.25
Received By alange Date 2006-04-13 Time 11:28 Sent To  
Notes
2006-04-13 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.SEPERATE FENCING PERMIT REQUIRED.
  
 3. SUBMIT A FLOOR PLAN INCLUDING
 LOCATIONS OF NEW WINDOWS AND DOORS
 INCLUDING SIZES AND TYPES.
 CLEARLY SHOW EXISTING AREA AND AREA OF
 NEW WORK.
  
 5.ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL TO BE
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 NEW COMMENTS;
 A. PRODUCT APPROVALS REQUIRED FOR IMPACT
 PROTECTION.
 B.TWO COMPLETE SETS OF PRODUCT
 APPROVALS REQUIRED.
 C. PLANS SHALL BE SIGNED AND DATED BY
 THE DESIGNEER OF RECORD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By alange Date 2006-02-15 Time 10:56 Rev Time 1.50
Received By alange Date 2006-02-15 Time 10:49 Sent To  
Notes
2006-02-15 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.SEPERATE FENCING PERMIT REQUIRED.
  
 3. SUBMIT A FLOOR PLAN INCLUDING
 LOCATIONS OF NEW WINDOWS AND DOORS
 INCLUDING SIZES AND TYPES.
 SHOW ALSO THE LOCATIONS FO THE BEDROOMS.
  
 4.SHOW ON PLANS EXISTING BATHROOM AND
 KITHEN AND INCLUDE NEW WORK.
  
 5.ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL TO BE
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-01-22 Cont ID  
Sent By btrobaug Date 2007-01-22 Time 11:25 Rev Time 0.33
Received By btrobaug Date 2007-01-22 Time 11:25 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2006-08-24 Cont ID  
Sent By btrobaug Date 2006-08-24 Time 07:06 Rev Time 0.50
Received By btrobaug Date 2006-08-24 Time 06:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-07-21 Cont ID  
Sent By jleahy Date 2006-07-21 Time 14:56 Rev Time 0.30
Received By jleahy Date 2006-07-21 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2006-07-21 Cont ID  
Sent By jleahy Date 2006-07-21 Time 14:57 Rev Time 0.00
Received By jleahy Date 2006-06-27 Time 15:02 Sent To  
Notes
2006-06-27 00:00:00PLANS ROUTED TO ZONING AS IT DOES NOT
 APPEAR THESE ARE THREE LEGAL UNITS.
 "GREEN CARDS" SHOW RES AND APT ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-12 Cont ID  
Sent By btrobaug Date 2006-04-12 Time 06:51 Rev Time 0.50
Received By btrobaug Date 2006-04-12 Time 06:36 Sent To M
Notes
2006-04-12 00:00:00 
 THE NOTE ON THE ELECTRICAL SHEET
 INDICATES "EXISTING CONDITION". IF THERE
 IS ELECTRICAL WORK TO BE DONE UNDER THIS
 APPLICATION, INDICATE SAME ON PLANS. SEE
 NFPA-70 (NEC) 2002, NFPA-72, EXISTING
 BUILDING CODE 2004, AND FBC 2004.
  
 INDICATE ALL NEW WORK AND EXISTING IF
 BOTH CONDITIONS EXIST.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-12-23 Cont ID  
Sent By btrobaug Date 2005-12-23 Time 14:49 Rev Time 0.33
Received By btrobaug Date 2005-12-23 Time 14:49 Sent To P
Notes
2005-12-23 00:00:00 
 THERE IS NO ELECTRICAL PLAN TO REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 11:00 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 11:00 Sent To B
Notes
2006-10-04 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 09:22 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 09:22 Sent To E
Notes
2006-08-21 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 18:23 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 18:23 Sent To Z
Notes
2006-08-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 09:31 Sent To E
Notes
2006-07-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 15:16 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 15:16 Sent To E
Notes
2006-06-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 09:38 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 09:38 Sent To E
Notes
2006-03-31 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-15 Cont ID  
Sent By alange Date 2006-02-15 Time 10:56 Rev Time 0.00
Received By alange Date 2005-12-10 Time 14:12 Sent To  
Notes
2005-12-10 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-06 Cont ID  
Sent By tgordon Date 2006-09-06 Time 16:36 Rev Time 0.30
Received By tgordon Date 2006-09-06 Time 16:36 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-07-19 Cont ID  
Sent By tgordon Date 2006-07-19 Time 15:44 Rev Time 0.45
Received By tgordon Date 2006-07-19 Time 15:44 Sent To P
Notes
2006-07-19 00:00:00*** DENIED ***
 1) 5" SUPPLY AIR DUCT GOING THROUGH 1
 HOUR FIRE SEPARATION REQUIRES A METAL
 DUCT AND FIRE DAMPER, PER 2004 FBC/M 607
 . PLEASE SUBMIT DETAILED INFOMATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-12 Cont ID  
Sent By tgordon Date 2006-04-12 Time 11:19 Rev Time 0.30
Received By tgordon Date 2006-04-12 Time 11:19 Sent To P
Notes
2006-04-12 00:00:00*** DENIED ***
 1) MECHANICAL PLANS STATE EXISTING
 CONDITIONS, PLEASE SHOW ON MECHANICAL
 PLANS WHAT WORK WILL BE NEW AND WHAT IS
 EXISTING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By tgordon Date 2006-01-23 Time 08:28 Rev Time 0.20
Received By tgordon Date 2006-01-23 Time 08:28 Sent To B
Notes
2006-01-23 00:00:00*** DENIED ***
 1) A/C CONTRACTOR SINGED ON BUT NO MECH.
 PLANS OR MECH. INFOMATION SUPPLIED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status N Date 2006-10-19 Cont ID  
Sent By jleech Date 2006-10-19 Time 15:08 Rev Time 0.00
Received By jleech Date 2006-10-19 Time 15:08 Sent To B
Notes
2006-10-19 15:09:10FIXTURE CHANGE OUT ONLY

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-09-06 Cont ID  
Sent By jleech Date 2006-09-06 Time 09:32 Rev Time 0.00
Received By jleech Date 2006-09-06 Time 09:31 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-20 Cont ID  
Sent By jleech Date 2006-07-20 Time 10:50 Rev Time 0.00
Received By jleech Date 2006-07-20 Time 10:50 Sent To B
Notes
2006-07-20 00:00:00FIXTURE CHANGE OUT ONLY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-13 Cont ID  
Sent By jleech Date 2006-04-13 Time 08:42 Rev Time 0.00
Received By jleech Date 2006-04-13 Time 08:42 Sent To B
Notes
2006-04-13 00:00:00DENIED;
 PLEASE SHOW ON PLANS WHAT PLUMBING WORK
 WILL BE DONE. SUCH AS A NOTE "CHANGE
 BATHROOM FIXTURES ONLY", "CHANGE
 LOCATION OF LAUNDRY ROOM". IF LOCATION
 OF FIXTURES CHANGE A RISER DIAGRAM WILL
 BE REQUIRED.
 THE SECOND FLOOR REAR APARTMENT DOES NOT
 HAVE LAUNDRY FACILITIES. IS THE LAUNDRY
 FACILITIES IN FRONT BUILDING COMMON? IF
 NOT A AUTOMATIC CLOTHES WASHER IS
 REQUIRED PER FBC-2004 PLUMBING TABLE
 403.1(7).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By jleech Date 2006-01-20 Time 14:40 Rev Time 0.33
Received By jleech Date 2006-01-20 Time 14:40 Sent To M
Notes
2006-01-20 00:00:00PROVISO;
 REPLACEMENT OF FIXTURES ONLY.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-18 Cont ID  
Sent By mmclean Date 2006-08-18 Time 13:56 Rev Time 0.00
Received By mmclean Date 2006-08-18 Time 13:56 Sent To I
Notes
2006-08-18 00:00:00OK - APPROVED BY ANGELLA JONES-VANN,
 DEPUTY DIRECTOR PLANNING & ZONING.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By mmclean Date 2006-07-06 Time 11:33 Rev Time 0.00
Received By mmclean Date 2006-07-06 Time 11:33 Sent To  
Notes
2006-07-06 00:00:00DENIED,
 1. NEED TO PROVIDE PROOF OF PERMIT FOR
 THE THIRD KITCHEN TO THE 2 STORY
 APARTMENT.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720