Plan Review Details - Permit 05120152
Plan Review Stops For Permit 05120152
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-06 Cont ID  
Sent By mjacobs Date 2006-02-06 Time 17:13 Rev Time 1.00
Received By mjacobs Date 2006-02-06 Time 16:18 Sent To PC
Notes
2006-02-06 00:00:00BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-06 Cont ID  
Sent By mjacobs Date 2006-01-06 Time 08:23 Rev Time 1.15
Received By mjacobs Date 2006-01-06 Time 07:09 Sent To PC
Notes
2006-01-06 00:00:001) PLEASE SEE COMMENTS FROM
 ZONING/PLUMBING AND ELCETRICAL. THESE
 COMMENTS SHOULD BE ADDRESSED BEFORE I
 CAN FINISH MY REVIEW.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-22 Cont ID  
Sent By btrobaug Date 2006-02-22 Time 15:19 Rev Time 0.33
Received By btrobaug Date 2006-02-22 Time 15:15 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-03 Cont ID  
Sent By btrobaug Date 2006-02-03 Time 17:27 Rev Time 0.33
Received By btrobaug Date 2006-02-03 Time 17:18 Sent To P
Notes
2006-02-03 00:00:00 
 SUBMIT A LOAD CALCULATION FOR THE
 SERVICE INCLUDING THE NEW EQUIPMENT.
 INDICATE THE SIZE OF THE EXISTING
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By btrobaug Date 2005-12-23 Time 15:53 Rev Time 0.33
Received By btrobaug Date 2005-12-23 Time 15:48 Sent To P
Notes
2005-12-23 00:00:00 
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAIN
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-12-29 Cont ID  
Sent By mperson Date 2005-12-29 Time 11:38 Rev Time 0.00
Received By mperson Date 2005-12-29 Time 11:37 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 12:23 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 12:23 Sent To E
Notes
2006-02-19 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 16:41 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 16:41 Sent To E
Notes
2006-02-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 09:38 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 09:38 Sent To Z
Notes
2006-01-26 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 08:59 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 08:59 Sent To E
Notes
2005-12-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-06 Time   Rev Time 0.00
Received By adarroug Date 2005-12-07 Time 11:05 Sent To  
Notes
2005-12-07 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-22 Cont ID  
Sent By mperson Date 2006-02-22 Time 15:59 Rev Time 0.33
Received By mperson Date 2006-02-22 Time 15:58 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-06 Cont ID  
Sent By mperson Date 2006-02-06 Time 10:33 Rev Time 0.33
Received By mperson Date 2006-02-06 Time 10:33 Sent To B
Notes
2006-02-06 00:00:00DENIED 2ND TIME
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) FBC-2004 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (NOTE:STILL NEED
 MANUFACTURE SHEETS WITH THIRD PARTY
 LISTING THE INFORMATION YOU HAVE
 SUBMITTED ARE SPEC SHEETS)
 2) FBC-2004 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF.(NOTE: STILL NEED MANUFACTURE CUT
 SHEET SUBMITTAL IF ONE CANNOT BE FOUND
 AN EXTERNAL HARTFORD LOOP SHALL BE
 PROVIDED AND SHOWN ON PIPING SCHEMATIC.)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By mperson Date 2005-12-29 Time 11:39 Rev Time 1.25
Received By mperson Date 2005-12-29 Time 11:39 Sent To B
Notes
2005-12-29 00:00:00DENIED
  
 REFERENCE: FBC-2004424.2 SWIMMING
 POOLS.
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR POOL PLUMBING PERMIT:
 1) THE PIPING SCHEMATIC SHOWS ONLY ONE
 MAIN DRAIN TO THE POOL WITH A 1" VENT.
 THERE SHOULD ALSO BE A MAIN DRAIN SHOWN
 FOR THE SPA WITH A 1-1/2" VENT.PLEASE
 CORRECT THE PIPING SCHEMATIC DRAWING TO
 SHOW BOTH MAIN DRAINS ON SCHEMATIC.
 2) COMPLY WITH FBC-2004 SEC 424.2
 PRIVATE SWIMMING POOLS.(ADD TO NOTES)
 3) FBC-2004 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 4) FBC-2004 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-31 Cont ID  
Sent By mmclean Date 2006-01-31 Time 17:46 Rev Time 0.00
Received By mmclean Date 2006-01-31 Time 17:46 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By mmclean Date 2005-12-20 Time 16:05 Rev Time 0.00
Received By mmclean Date 2005-12-20 Time 16:05 Sent To I
Notes
2005-12-20 00:00:00DENIED,
 1. SPA MUST BE 5FT ON THE SIDE (FROM
 WATER'S EDGE TO PROPERTY LINE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720