Plan Review Details - Permit 05120078
Plan Review Stops For Permit 05120078
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-12-02 Cont ID  
Sent By lmiller Date 2005-12-02 Time 08:54 Rev Time 0.00
Received By lmiller Date 2005-12-02 Time 08:54 Sent To  
Notes
2005-12-02 00:00:00DIS. W/ADDRESS APP READS 408 PAPA READS
 406

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-28 Cont ID  
Sent By alange Date 2006-03-28 Time 07:57 Rev Time 0.50
Received By alange Date 2006-03-28 Time 07:56 Sent To M
Notes
2006-03-21 00:00:00NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-06 Cont ID  
Sent By alange Date 2006-03-06 Time 14:35 Rev Time 0.66
Received By alange Date 2006-03-06 Time 14:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By alange Date 2006-01-20 Time 09:57 Rev Time 0.75
Received By alange Date 2006-01-20 Time 09:31 Sent To  
Notes
2006-01-20 00:00:00DENIED
 SECOND REVIEW:
  
 1.SUBMIT TWO COMPLETE SETS OF PLANS
 SHOWING EXISTING WORK AND NEW WORK TO BE
 COMPLETED.
  
 2. VALUATION IS TOO LOW FOR THE
 WORK TO BE COMPLETED.INCREASE PERMIT
 VALUE AND PAY ADDTIONAL PERMIT FEES.
 108.3WPB AMMENDMENTS TO THE 2004 FBC
  
 3. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 4.INSUFFICIENT INFORMATION SUBMITTED
 FOR A COMPLETE REVIEW.ADDITIONAL NEW
 COMMENTS MAY ARISE AFTER SUBMITTING NEW
 PLANS.WPB AMMENDMENTS TO THE FBC
 106.3.5SEE THIS SECTION FOR THE ITEMS
 REQUIRED FOR REVIEW.BE SURE TO SHOW
 BUILDING CNSTRUCTION TYPE.
  
 5.SUBMIT A DOOR SCHEDULE.
  
 6.WHITE OUT NOT PERMITTED ON PLANS.
 FBC 106.1.3
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 16:13 Rev Time 0.75
Received By alange Date 2006-01-06 Time 15:19 Sent To  
Notes
2006-01-06 00:00:00DENIED
  
 1.SUBMIT TWO COMPLETE SETS OF PLANS
 SHOWING EXISTING WORK AND NEW WORK TO BE
 COMPLETED.VALUATION IS TOO LOW FOR THE
 WORK TO BE COMPLETED.INCREASE PERMIT
 VALUE AND PAY ADDTIONAL PERMIT FEES.
 108.3WPB AMMENDMENTS TO THE 2004 FBC
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.INSUFFICIENT INFORMATION SUBMITTED
 FOR A COMPLETE REVIEW.ADDITIONAL NEW
 COMMENTS MAY ARISE AFTER SUBMITTING NEW
 PLANS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 10:07 Sent To  
Notes
2006-03-24 00:00:00VIF THE VA SHOWN FOR SHOW WINDOW LTS.,
 SEEMS HIGH.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 07:49 Sent To  
Notes
2006-03-01 00:00:00*** UNSAT 3RD REVIEW ***
  
 ** PLEASE KNOW, NEW PLANS BY A NEW
 DESIGNER IS NOW BEING SUBMITTED FOR THE
 FIRST TIME.
 PLEASE SEE SOME NOTES BELOW AS SOME ARE
 NOW NEW AND SOME ARE FROM PREVIOUS
 REVIEW.
  
 1)NOTE: PLEASE SEE LOAD CALCUALTIONS NOW
 SHOW TWO SETS OF "SHOW WINDOW" LIGHTING
 AT 6KW? , HOWEVER PLANS AND PANEL
 SCHEDULE CIRCUITING DOES NOT INDICATE
 ANY OF THIS? PLEASE SHOW FIXTURES ETC
 WHICH ARE BEING INSTALLED FOR THIS.
 215.5
  
 2)NOTE: PLEASE SEE OCCUPANCY
 DESIGNATION/USE OF UNIT BLDG ETC IS
 STILL NOT BEING INDICATED ON PLANS AS
 REQUESTED ON THE PREVIOUS REVIEWS.
 ??
  
 3)NOTE: PLEASE SEE 700.12E FOR
 CIRCUTIING OF EM/EXT LTS. THESE MUST BE
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FEEDING ANY ONE AREA.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 13
 13-415.1.ABC.1.1 &.2
 PLEASE KNOW,SQ FT OF BLSG IS NOT KNOWN
 AND IS NOT SHOWN ON PLANS.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADE WHICH MAY AFFECT ELECTRICLA
 PLANS. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-23 Cont ID  
Sent By dpalmer Date 2006-01-23 Time 14:36 Rev Time 0.00
Received By dpalmer Date 2006-01-23 Time 14:36 Sent To  
Notes
2006-01-23 00:00:00*********** UNSAT 2ND REVIEW *******
  
  
 PLEASE SEE COMMENTS FROM PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SUBMIT PLANS WITH
 DRAFTMANS QUALITY.
 FBCADMINISTRATIVE CODE 106
  
 2)NOTE: PLEASE SEE VALUATION HAS NOT
 BEEN INCREASED AND VALUE SHALL BE
 ACCESSED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS ADJUSTED.
 PLEASE SEE THE ELECTRICAL WORK ALONE IS
 SUBSTANIAL.
 FBC 108.3
  
 3)NOTE: PLEASE SEE ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR SAID
 PLANS/DESIGN.
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EXT AND EM LTS AS ON
 PREVIOUS REVIEW. THESE SHALL BE
 CIRCUITED TO THE LOCAL LIGHTING BRANCH
 CIRCUIT.
 PLEASE SEE EM LTS ON WITH RECEPTS.
  
 5)NOTE: PLANS SHALL DESIGNATE OCCUPANCY
 FOR USE.
  
 6)NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS
 REVIEW ALSO.
  
 PLEASE SEE OTHER REVIEWERS COMMENTS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 NOTES FOR FIRST REVIEW.
  
 PLEASE SEE VALUATION FOR SCOPE OF WORK
 IS LOW AND MSUT BE INCREASED TO AN
 APPROPRIATE VALUE OR ONE SHALL BE
 ASSESSED PER MARSHALL'S/ SWIFT GUIDE.
 PLEASE KNOW, THE 4X FEE SHALL BE
 ADJUSTED UPON VALUE INCREASE AND FEES
 WILL BE DUE.
 FBC ADMINISTRATIVE SECTION. 108.3
  
 2)NOTE: PLEASE SUBMIT PLANS WITH
 DRAFTMANS QUALITY FOR ALL DETAILS AND
 SCOPE OF WORK TO BE PERFORMED.
 FBC 106
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE SHOW SIZE OF PANEL AND NEW AND
 EXISTING LOADS.
 215.5
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS. (LOCAL LIGHTING BRNACH
 CIRCUIT)
  
 4)NOTE: OK.
  
 5)NOTE: OK, SEE NEW NOTES
  
 6)NOTE: PLEASE SEE PLANS SUBMITTED
 MENTIONS: " ALL IMPROVEMENTS ARE
 EXISTING. ADDITIONAL DRAWINGS WILL BE
 SUBMITTED FOR THE REMAINDER OF PROPOSED
 CONSTRUCTION"??
 PLEASE CLARIFY THIS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 15:26 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 15:26 Sent To  
Notes
2005-12-30 00:00:00************ UNSAT *************
  
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION:
 PLEASE BES URE CONTRACTOR SIGNS PERMIT
 APPLICATION. MUST BE NOTORIZED IF
 QUALIFIER DOES NOT BRING IN.
 PLEASE SEE VALUATION FOR SCOPE OF WORK
 IS LOW AND MSUT BE INCREASED TO AN
 APPROPRIATE VALUE OR ONE SHALL BE
 ASSESSED PER MARSHALL'S/ SWIFT GUIDE.
 PLEASE KNOW, THE 4X FEE SHALL BE
 ADJUSTED UPON VALUE INCREASE AND FEES
 WILL BE DUE.
 FBC ADMINISTRATIVE SECTION. 108.3
  
 2)NOTE: PLEASE SUBMIT PLANS WITH
 DRAFTMANS QUALITY FOR ALL DETAILS AND
 SCOPE OF WORK TO BE PERFORMED.
 FBC 106
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE SHOW SIZE OF PANEL AND NEW AND
 EXISTING LOADS.
 215.5
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS. (LOCAL LIGHTING BRNACH
 CIRCUIT)
  
 4)NOTE: PLEASE SEE NEW A/C BEING SHOWN,
 HOWEVER NO INFORMATION SUBMITTED FOR
 LOADS ETC.
  
 5)NOTE: PLEASE SEE PLANS INDICATE A
 "STORE"??, PLEASE INCLUDE STOREFRONT
 WINDOWS, PER 210.62.
 PLEASE SEE 600.5 FOR MISSING SIGN
 CIRCUIT.
  
 6)NOTE: PLEASE SEE PLANS SUBMITTED
 MENTIONS: " ALL IMPROVEMENTS ARE
 EXISTING. ADDITIONAL DRAWINGS WILL BE
 SUBMITTED FOR THE REMAINDER OF PROPOSED
 CONSTRUCTION"??
 PLEASE CLARIFY THIS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-03-24 Cont ID  
Sent By mwennerg Date 2006-03-24 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2006-03-24 Time 10:36 Sent To  
Notes
2006-03-21 00:00:00NEW SHEETS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By nmccray Date 2006-01-23 Time 11:03 Rev Time 0.00
Received By nmccray Date 2006-01-23 Time 11:03 Sent To  
Notes
2006-01-23 00:00:00PROVISO:
  
 INTERIOR FINISH FOR WALLS AND CEILINGS
 SHALL BE CLASS A, OR CLASS B IN EXITS
 AND IN ENCLOSED CORRIDORS FURNISHING
 ACCESS TO EXITS; CLASS A, CLASS B, OR
 CLASS C IN OFFICE AREAS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By mwennerg Date 2006-01-03 Time 10:46 Rev Time 0.00
Received By mwennerg Date 2006-01-03 Time 10:45 Sent To  
Notes
2006-01-03 00:00:00******DENIED******
  
 1) ONE DRAWINGS SHOWS (2) EXIT SIGNS,
 AND ONE SHOWS ONLY (1) SIGN. PLEASE MAKE
 CORRECTION.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS
 REQUIRED.
  
 3) PERMIT APPLICATION INDICATES (2)
 OFFICE SPACES, BUT PLANS SHOW STORAGE.??
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 19:34 Sent To  
Notes
2006-03-21 00:00:00SENT TO BOB # 15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 14:18 Sent To  
Notes
2006-02-25 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 11:08 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 11:08 Sent To  
Notes
2006-01-19 00:00:00TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-06 Time 11:07 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 08:59 Sent To  
Notes
2005-12-06 00:00:00TO "BOB"#15

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-03-30 Cont ID  
Sent By tgordon Date 2006-03-30 Time 11:12 Rev Time 0.30
Received By tgordon Date 2006-03-30 Time 11:12 Sent To  
Notes
2006-03-30 00:00:00REVISED MECH. PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-02-28 Cont ID  
Sent By tgordon Date 2006-02-28 Time 11:05 Rev Time 0.25
Received By tgordon Date 2006-02-28 Time 11:05 Sent To  
Notes
2006-02-28 00:00:00*** DENIED ***
 1) PLEASE SUBMIT NEW A/C PLANS SHOWING
 EXISTING A/C LAY-OUT AND PROPOSED A/C
 LAY-OUT, AS THE SPACE LAY-OUT HAS BEEN
 CHANGED SINCE A/C PERMIT # 05082034.
 PLEASE NOTE; THAT PREMITS HAD BEEN
 CLOSED LAST MONTH. ENCLOSED IS A COPY OF
 THE MECHANICAL PLAN FOR THAT PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-31 Cont ID  
Sent By hmoser Date 2006-01-31 Time 10:57 Rev Time 0.00
Received By hmoser Date 2006-01-31 Time 10:57 Sent To  
Notes
2006-01-31 00:00:00NO MECHANICAL PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6738

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-30 Cont ID  
Sent By pkrauss Date 2005-12-30 Time 15:44 Rev Time 0.00
Received By pkrauss Date 2005-12-30 Time 15:44 Sent To  
Notes
2005-12-30 00:00:00DENIED:
 PLANS INDICATE 10 KW A/C BUT NO PLANS OR
 EQUIPMENT SCHEDULE SUBMITTED.PLEASE
 PROVIDE PLANS AND SCOPE OF WORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status N Date 2006-03-01 Cont ID  
Sent By jleech Date 2006-03-01 Time 14:39 Rev Time 0.00
Received By jleech Date 2006-03-01 Time 14:39 Sent To  
Notes
2006-03-01 00:00:00NOT ENOUGH INFORMATION FOR PLAN REVIEW.
 IF PLUMBING HAS CHANGED, REVISIONS
 SHOULD BE SUBMITED BY THE PLUMBING
 CONTRACTOR UNDER PERMIT #05090940.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-01-24 Cont ID  
Sent By jleech Date 2006-01-24 Time 12:26 Rev Time 0.50
Received By jleech Date 2006-01-24 Time 12:26 Sent To  
Notes
2006-01-24 00:00:00THIS JOB HAS A PLUMBING PERMIT. PLAN
 REVIEW WAS DONE BY PAUL SCHMITZ ON
 10/13/05 PERMIT # 05090940.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 09:24 Rev Time 0.50
Received By jleech Date 2006-01-03 Time 09:24 Sent To  
Notes
2006-01-03 00:00:00DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW. PLEASE SUBMIT DRAWINGS
 SHOWING THE SCOPE OF PLUMBING WORK TO BE
 DONE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy