Plan Review Details - Permit 05120012
Plan Review Stops For Permit 05120012
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-10-25 Cont ID  
Sent By alange Date 2006-10-25 Time 14:09 Rev Time 0.00
Received By alange Date 2006-10-25 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-10-06 Cont ID  
Sent By alange Date 2006-10-06 Time 09:24 Rev Time 1.00
Received By alange Date 2006-10-06 Time 09:24 Sent To  
Notes
2006-10-06 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
 IF EACH PRODUCT APPROVAL IS NOT
 INDIVIDUALLY APPROVED. LIST PRODUCTS
 WITH NOA ON A PAGE AND SIGN AND DATE
 THAT PAGE.
  
 8.PERSON RESPONSIBLE FOR THE DESIGN
 SHALL SIGN AND DATE ALL PAGES.FBC
 106.1.3 WEST PALM BEACH AMMENDMENTS.
  
 NEW:
 PGT SH-700 MISSING STATE PRODUCT
 APPROVAL.SUBMIT TWO COPIES.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-07 Cont ID  
Sent By alange Date 2006-09-07 Time 10:56 Rev Time 1.25
Received By alange Date 2006-09-07 Time 10:49 Sent To  
Notes
2006-09-07 00:00:00DENIED
  
 NEW REVIEW COMMENTS BASED ON NEW PLANS
 SUBMITTED:
  
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PLUMBING PAGES MISSING FROM NEW SET
 OF PLANS.
  
 3.PERMIT VALUE SHOULD REFLECT ALL
 METERIALS AND LABOR FOR PROJECT.
 ADJUST PERMITTED VALUE PRIOR TO
 RESUBMITTING PLANS.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 4.SUBMIT PRODUCT APPROVALS FOR
 EXTERIOR INSWING DOOR.
  
 5.SUBMIT PRODUCT APPROVALS AND SHUTTER
 SCHEDULE FOR IMPACT PROTECTION.
  
 6.WIND DESIGN LOADS SHALL BE DESIGNED
 TO ASCE 7-02 AND SECTION 1609 OF THE
 2004 FBC.
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.PERSON RESPONSIBLE FOR THE DESIGN
 SHALL SIGN AND DATE ALL PAGES.FBC
 106.1.3 WEST PALM BEACH AMMENDMENTS.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-19 Cont ID  
Sent By alange Date 2006-06-19 Time 08:26 Rev Time 2.50
Received By alange Date 2006-06-19 Time 08:26 Sent To  
Notes
2006-06-19 00:00:00DENIED
  
 1.CHECKED DEMO INFORMATION FILE WITH
 TOM MOORE.BUILDINGS NEED STRUCTURAL
 WORK.SUBMIT A COMPLETE SET OF PLANS
 SHOWING ALL WORK TO BE COMPLETED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-08 Cont ID  
Sent By alange Date 2006-05-08 Time 13:26 Rev Time 1.00
Received By alange Date 2006-05-08 Time 13:19 Sent To  
Notes
2006-05-08 00:00:00DENIED
  
 1. PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS AND STRAPS AND TIEDOWNS.
  
 2. ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4. W P B ADMINISTRATIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5.SHOW DETAILS FOR WALL FRAMING AND
 ROOF REPAIRS.
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303 , 304 AND 305 OF THIS CODE.
 2004 FLORIDA EXISTING BUILDING CODE.
  
 8. WPB AMMENDMENTS TO THE 2004 FBC
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL
 INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN;FLOOR/ROOF
 FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS.
 INSUFFICIENT INFORMATION PROVIDED FOR A
 COMPLETE PLAN REVIEW.ADDITIONAL
 COMMENTS MAY ARISE AFTER REVIEWING
 UPDATED PLANS.SCOPE OF WORK ON
 APPLICATION DOES NOT REFLECT WORK SHOWN
 ON PLANS.PLANS ALSO DO NOT SHOW
 COMPLETE SCOPE OF WORK TO BE COMPLETED.
  
 9. SELECT THE ROOF ASSEMBLY USED ON THE
 MIAMI-DADE PRODUCT APPROVAL SUBMITTED.
 WPB AMMENDMENTS TO THE 2004 FBC
 106.1.1.2 FOR ROOF ASSEMBLIES REQUIRED
 BY THE CODE, THE CONSTRUCTION DOCUMENTS
 SHALL ILLUSTRATE, DESCRIBE, AND
 DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS,
 FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO
 BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND WPB AMENDMENTS TO FBC 2004
 EDITION 1.10 CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN
 ARCHITECT OR ENGINEER FOR THE SPECIFIC
 SITE MUST BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS.
  
 A.INCLUDE A DOOR AND WINDOW SCHEDULE.
  
 B.PERMIT VALUATION IS TOO LOW AND DOES
 NOT REFLECT ALL WORK SHOWN.ADDITIONAL
 PERMIT FEES WILL BE DUE.
  
 C.PLANS ARE VAGUE AND DO NOT SHOW
 COMPLETE SCOPE OF WORK TO BE COMPLETED.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-24 Cont ID  
Sent By jleech Date 2006-05-04 Time 08:47 Rev Time 1.00
Received By alange Date 2006-01-24 Time 13:53 Sent To  
Notes
2006-01-24 00:00:00DENIED
  
 1. PRODUCT APPROVALS REQUIRED FOR
 ROOFING AND STRAPS AND TIEDOWNS.
  
 2. ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.TRACO WINDOWS MISSING PAGES FROM THE
 MIAMI-DADE NOA.
  
 4. W P B ADMINISTRATIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5.SHOW DETAILS FOR WALL FRAMING AND
 ROOF REPAIRS.
  
 6. PERSON RESPONSIBLE FOR THE DESIGN
 SHALL PRINT AND SIGN THEIR NAME ON EACH
 PAGE OF PLANS.
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303 , 304 AND 305 OF THIS CODE.
 2004 FLORIDA EXISTING BUILDING CODE.
  
 8. WPB AMMENDMENTS TO THE 2004 FBC
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL
 INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN;FLOOR/ROOF
 FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS.
 INSUFFICIENT INFORMATION PROVIDED FOR A
 COMPLETE PLAN REVIEW.ADDITIONAL
 COMMENTS MAY ARISE AFTER REVIEWING
 UPDATED PLANS.
  
 9. WPB AMMENDMENTS TO THE 2004 FBC
 106.1.1.2 FOR ROOF ASSEMBLIES REQUIRED
 BY THE CODE, THE CONSTRUCTION DOCUMENTS
 SHALL ILLUSTRATE, DESCRIBE, AND
 DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS,
 FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO
 BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND WPB AMENDMENTS TO FBC 2004
 EDITION 1.10 CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN
 ARCHITECT OR ENGINEER FOR THE SPECIFIC
 SITE MUST BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-21 Cont ID  
Sent By btrobaug Date 2006-04-21 Time 08:13 Rev Time 0.50
Received By btrobaug Date 2006-04-21 Time 07:17 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-16 Cont ID  
Sent By btrobaug Date 2005-12-16 Time 12:44 Rev Time 0.50
Received By btrobaug Date 2005-12-16 Time 11:39 Sent To M
Notes
2005-12-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 PER 104.2.1 FBC.
  
 2} INDICATE THE SERVICE LOCATION ON THE
 PLAN.
  
 3} SHOW THE REQUIRED DISCONNECTING MEANS
 @ THE COTTAGE PER 225.31 AND GROUNDING
 PER 250.32.
  
 4} PROVIDE THE AIC RATING FOR THE NEW
 EQUIPMENT IF THE SERVICE IS BEING
 CHANGED AS THE NOTE IMPLIES.
  
 5} THE LOAD CALCULATION GIVEN IS
 INCORRECT AS IT DOES NOT INCLUDE THE
 APPLIANCES IN THE COTTAGE. PLEASE
 CORRECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2005-12-01 Cont ID  
Sent By ptjomsto Date 2005-12-01 Time 09:34 Rev Time 0.00
Received By ptjomsto Date 2005-12-01 Time 09:34 Sent To  
Notes
2005-12-01 00:00:00HISTORIC STAMPED OFF STATING NO HP
 REVIEW REQUIRED/ALL INTERIOR WORK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 10:05 Sent To B
Notes
2006-10-23 10:05:41TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 14:27 Sent To B
Notes
2006-09-22 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 10:39 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 10:39 Sent To B
Notes
2006-09-05 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 16:20 Sent To M
Notes
2006-06-05 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 14:39 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 14:39 Sent To E
Notes
2006-04-17 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-24 Cont ID  
Sent By alange Date 2006-01-24 Time 14:20 Rev Time 0.00
Received By alange Date 2005-12-02 Time 14:25 Sent To  
Notes
2005-12-02 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-06 Cont ID  
Sent By tgordon Date 2006-06-06 Time 08:07 Rev Time 0.20
Received By tgordon Date 2006-06-06 Time 08:07 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By tgordon Date 2006-04-25 Time 11:20 Rev Time 0.25
Received By tgordon Date 2006-04-25 Time 11:20 Sent To P
Notes
2006-04-25 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) PLEASE HAVE MECHANICAL PLANS SIGNED.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-21 Cont ID  
Sent By tgordon Date 2005-12-21 Time 09:06 Rev Time 0.15
Received By tgordon Date 2005-12-21 Time 09:06 Sent To P
Notes
2005-12-16 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-10 Cont ID  
Sent By jleech Date 2006-06-10 Time 10:33 Rev Time 0.00
Received By jleech Date 2006-06-10 Time 10:33 Sent To B
Notes
2006-06-10 00:00:00PROVISO;
 FIXTURE REPLACEMENT ONLY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-04 Cont ID  
Sent By jleech Date 2006-05-04 Time 08:32 Rev Time 0.00
Received By jleech Date 2006-05-04 Time 08:32 Sent To B
Notes
2006-05-04 00:00:00DENIED;
  
 FUTURE BATH IS NOT SHOWN ON FLOOR PLAN.
 SHOW FUTURE BATHROOM LOCATION ON PLANS.
 ADD NOTE, PLUMBING ROUGH ONLY.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By jleech Date 2005-12-21 Time 15:03 Rev Time 0.00
Received By jleech Date 2005-12-21 Time 15:03 Sent To B
Notes
2005-12-21 00:00:00NEED MORE INFORMATION. PLEASE LIST WORK
 TO BE DONE BY PLUMBER. @ CHANGE OUT ALL
 PLUMBING FIXTURES, @REPAIR OF WATER AND
 SANITARY PIPING AS NEEDED ALL FIXTURES
 TO STAY IN SAME PLACE. ALL PIPING WILL
 BE BROUGHT UP TO FBC-2004 CODES.
 PLEASE PRINT AND SIGN PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695