Plan Review Details - Permit 05111183
Plan Review Stops For Permit 05111183
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-08-04 Cont ID  
Sent By jgomez Date 2006-08-04 Time 10:18 Rev Time 0.33
Received By jgomez Date 2006-08-04 Time 10:18 Sent To  
Notes
2006-08-04 00:00:00ROOF FRAMING PLAN, DRAWING A-5.0.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-06-29 Cont ID  
Sent By jgomez Date 2006-06-29 Time 13:53 Rev Time 0.50
Received By jgomez Date 2006-06-29 Time 13:37 Sent To  
Notes
2006-06-29 00:00:00BUILDING REVISION CHECKLIST:
 1- NEED TO SIGN AND SEAL BOTH DRAWINGS
 AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTES. ONLY ONE WAS SIGNED AND
 SEALED.
  
 2- THIS IS A REVISION, NOT SUBMITTAL
 OWES $60.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-05-24 Cont ID  
Sent By jgomez Date 2006-05-24 Time 10:34 Rev Time 0.75
Received By jgomez Date 2006-05-23 Time 17:35 Sent To  
Notes
2006-05-24 00:00:00BUILDING REVISION CHECKLIST:
 1- ITEM 3(B) OF PROVISO DATED 4-18-06
 REQUIRED ARCHITECT TO REVISE CONNECTOR
 HTS 20 FOR GIRDER TRUSS THAT RUNS FROM
 BREAKFAST AREA TO POWDER ROOM (SEE
 COMMENTS ON SHEET A-5.0). HTS 20 IS A
 WOOD TO WOOD CONNECTOR. NEED TO SPECIFY
 A WOOD TO MASONRY CONNECTOR. SEE SIMPSON
 CATALOGUE FOR PROPER MASONRY CONNECTORS
 AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-19 Cont ID  
Sent By jgomez Date 2006-04-18 Time 18:58 Rev Time 3.00
Received By jgomez Date 2006-04-18 Time 17:16 Sent To  
Notes
2006-04-19 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT
 AS REQUESTED BY CONTRACTOR.
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL UNDER A SEPARATE PERMIT FOR
 6' X 8' OVERHEAD GARAGE DOOR THAT MEETS
 THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT. SEE PLANS.
 3- SHEET A-5.0: A) REVISE DETAILS 4
 AND 5. SEE CATALOGUE TO MATCH PROPER
 CONNECTOR SIZE AND NUMBER OF NAILS.
 B) REVISE CONNECTORS SPECIFIED FOR BOTH
 ENDS OF GIRDER TRUSS THAT RUNS FROM
 BREAKFAST AREA TO POWDER ROOM. SPECIFY
 CONNECTORS THAT MEET THE CALCULATED
 UPLIFT LOADS AND MAKE SURE CONNECTORS
 ARE WOOD TO MASONRY INSTALLATION. HTS 20
 IS NOT A WOOD TO MASONRY CONNECTOR.
 4- SHEET D-1: A) REVISE WOOD FRAMING
 DETAIL TO MATCH, ROOF FRAMING PLAN AND
 DETAIL 4, 5 AND 7.
 B) DETAILS 4 AND 7: SPECIFY HOW MUCH
 EMBEDMENT IS REQ'D FOR 3/4" ANCHOR BOLTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-14 Cont ID  
Sent By jgomez Date 2006-03-14 Time 17:12 Rev Time 3.00
Received By jgomez Date 2006-03-14 Time 17:12 Sent To  
Notes
2006-03-14 00:00:00BUILDING REVIEW CHECKLIST:
 1- ARCHITECT WAS ASKED TO REVIEW AND
 APPROVE (TYPICALLLY THIS IS DONE BY
 USING THE REVIEWED AND APPROVED STAMP),
 NOT SIGN AND SEAL THE PRODUCT APPROVALS.
 SEC. 106.3.3 CITY AMENDMENTS TO FBC
 2004. RE-SUBMIT CLEAN COPIES OF ALL THE
 PRODUCT APPROVALS WITHOUT THE
 ARCHITECT'S SEAL. INSTEAD ARCHITECT TO
 USE THE STANDARD REVIEW STAMP.
 ARCHITECT IS NOT ALLOWED TO SIGN AND
 SEAL THE PRODUCT APPROVALS, SINCE HE'S
 NOT THE DESIGNER.
  
 2- PROVIDE PRODUCT APPROVAL FOR 6'X8'
 GARAGE DOOR THAT MEETS THE DESIGN
 PRESSSURES CALCULATED BY THE ARCHITECT.
  
 3- PROVIDE COMPLETE SPECS FOR ONE HOUR
 FIRE RATED DOOR AT ATRIUM AS SPECIFIED
 ON ARCHITECT'S PLANS.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ALL STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AS REQUIRED BY RULE
 9B-72 DEPARTMENT OF COMMUNITY AFFAIRS.
 SEE PLANS AND DETAILS TO FIND ALL
 CONNECTORS SPECIFIED ON PLANS.
  
 6- PROVIDE TWO COPIES OF THE SAME DADE
 COUNTY NOA SUBMITTED FOR 2" WINDOW
 MULLION FOR FLORIDA PRODUCT APPROVAL.
 SEE WEBSITE WWW.FLORIDABUILDING.ORG TO
 DOWNLOAD SPECIFIC NOA SUBMITTED.
  
 7- DRAWING A-2.0: A) UPDATE NOTE #11.
 SEE 2004 RESIDENTIAL CODE.
 B) SPECIFY SIZE FOR ATTIC ACCESS BY
 MASTER BEDROOM CLOSET. SEC. R807 2004
 RESIDENTIAL CODE.
 C) UPDATE CEILING NOTES. SEE R703.6
 2004 RESIDENTIAL CODE.
  
 8- DRAWING A-5.0: A) CONNECTOR D
 SPECIFIED ON ROOF FRAMING PLAN IS A WOOD
 TO WOOD CONNECTOR. NEED WOOD TO MASONRY
 CONNECTOR. SEE PLANS AND REVISE AS REQ'D
 B) DETAIL 2: REVISE NUMBER OF MICROLAM
 BEAMS. SEE ROOF FRAMING PLAN.
 C) DETAIL 4 AND 5: SEE CATALOGUE FOR
 CORRECT SIZE OF CONNECTOR AND SPECIFIC
 SIZE AND TYPE OF ANCHOR TO BE USED.
 REVISE AS REQUIRED.
 D) SPECIFY CALCULATED UPLIFT LOADS FOR
 REAR PORCH BEAM ENDS USING CONNECTORS ON
 DETAIL 4 AND 5. SEE PLANS.
 E) SPECIFY CALCULATED UPLIFT LOADS FOR
 GIRDER TRUSS THAT IS SUPPORTING GIRDER
 TRUSSES AT ENTRY AREA. SEE PLANS.
 F) SPECIFY CALCULATED UPLIFT LOADS FOR
 GIRDER TRUSS BY KITCHEN DESK. SEE PLANS.
 G) SPECIFY CALCULATED UPLIFT LOADS FOR
 GIRDER TRUSS ABOVE BREAKFAST AREA AND
 NEXT TO GIRDER TRUSS NAMED ON ITEM E)
 ABOVE. SEE PLANS FOR COMMENTS.
 H) ROOF FRAMING PLAN AT ENTRY AREA HAS
 TWO DIFFERENT DETAILS 4/D1 AND 7/A-5.
 PROVIDE ONLY THE DETAIL THAT APPLIES FOR
 THE ACTUAL CONSTRUCTION. AND MAKE SURE
 CORRECT TRUSS CONNECTOR IS SPECIFIED.
 I) DETAIL 9/A-5 SHOWN ON ROOF FRAMING
 PLAN BY THE ENTRY AREA DOESN'T APPLY TO
 THIS JOB. REVISE AS REQUIRED.
  
 9- DRAWING D-1: A) REVISE SECTION
 SPECIFIED ON TYPICAL WALL SECTION FOR
 TERMITE PROTECTION. SEE 2004 FLORIDA
 RESIDENTIAL CODE FOR CORRECT SECTION.
 B) DETAIL 5: HETA 20 CONNECTOR IS
 SHOWN AS ATTACHED TO BEAM. SEE CATALOGUE
 FOR PROPER HETA INSTALLATION AND REVISE
 AS REQUIRED.
 C) SPECIFY SPACING REQUIRED FOR HETA
 20 SPECIFIED ON DETAIL 5.
 D) WOOD ARCH FRAMING DETAILS DON'T
 MATCH DETAILS SHOWN FOR ENTRY. SEE ROOF
 FRAMING PLAN. REVISE AS REQUIRED.
 E) GLASS BLOCK DETAIL NOTE SAYS "GLASS
 BLOCK SHALL CONFORM TO SBC 2704.10".
 UPDATE NOTE AS REQUIRED. SEE 2004
 RESIDENTIAL CODE.
 F) ONE AND TWO FAMILY DWELLINGS DON'T
 REQUIRE HANDICAPPED TOILET FIXTURES.
 REVISE/CLARIFY NOTE AS REQUIRED.
  
 10- DRAWINGS D-2 AND D-3 HAVE THE TITLE
 BLOCK OF MCCARTHY AND ASSOCIATES INC.
 CONSULTING ENGINEER'S. ENGINEER
 RESPONSIBLE FOR THESE DRAWINGS TO
 PROVIDE ALL HIS INFORMATION AND TO SIGN
 AND SEAL DRAWINGS AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
  
 11- DRAWINGS D-1 AND D-3 HAVE DIFFERENT
 DETAILS FOR GARAGE DOOR STRUTURAL BUCK
 ANDDOORS AND WINDOWS STRUCTURAL BUCKS.
 PROVIDE ONLY THE ACTUAL DETAILS THAT
 APPLY TO THIS PROJECT.
  
 12- ENERGY CALCULATIONS NEED TO BE DONE
 FOR WORST CASE SCENARIO OR BE SPECIFIC
 TO THE ACTUAL ORIENTATION OF THE HOUSE.
 INFORMATION SUBMITTED IS NOT FOR WORST
 CASE SCENARIO AND IT DOESN'T MATCH
 ACTUAL ORIENTATION OF HOUSE. SEE SURVEY
 AND REVISE AS REQUIRED.
 PROVIDE CORRECT CALCULATIONS.
  
 13- ARCHITECT TO SPECIFY ROOF TILE
 FASTENING AS REQUIRED BY SEC. 106.1.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 14- PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By jgomez Date 2005-12-29 Time 18:02 Rev Time 2.50
Received By jgomez Date 2005-12-29 Time 18:02 Sent To PC
Notes
2005-12-29 00:00:00BUILDING REVIEW CHECKLIST:
 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST
 2005 ARE REQUIRED TO COMPLY WITH FBC
 2004. REVISE ALL PLANS, GENERAL NOTES,
 DESIGN PARAMETERS, CONSTRUCTION TYPE AND
 ALL PERTINENT ITEMS SHOWN ON PLANS AS
 REQUIRED TO COMPLY WITH FBC 2004.
  
 2- TRUSS DESIGN DRAWINGS NEED TO BE
 PROVIDED TO THE BUILDING OFFICIAL FOR
 APPROVAL PRIOR TO INSTALLATION. SEC.
 R802.10.1 RESIDENTIAL FBC 2004.
 (REMAINDER: DESIGNER OF RECORD TO REVIEW
 ALL TRUSSES PRIOR TO SUBMITTAL TO THIS
 OFFICE).
  
 3- DESIGNER OF RECORD TO REVIEW ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 4- PROVIDE ALL INFORMATION ON PLANS
 REGARDING THE SEPARATION AND OPENING
 PROTECTION AS REQUIRED BY SEC. R309 OF
 RESIDENTIAL FBC 2004.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) TRUSS CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE COVER PAGE AND
 PAGES SHOWING THE SPECIFIC CONNECTOR
 SPECIFIED ON PLANS. PLEASE DON'T SUBMIT
 COMPLETE REPORT TO EXPEDITE REVIEW
 PROCESS AND SAVE PAPER.
  
 B) GARAGE DOORS: FLORIDA NUMBER
 SUBMITTED IS NOT LONGER LISTED.
  
 C) 2" WINDOW MULLION: NEED CURRENT
 DADE COUNTY NOA THAT MATCHES ONE
 SUBMITTED FOR FLORIDA APPROVAL.
  
 D) FIXED WINDOWS: MISSING FLORIDA
 PRODUCT APPROVAL.
  
 E) ATRIUM DOOR: SEE PLANS FOR SIZE AND
 DOOR SWING DIRECTION.
  
 7- SOIL TEST REPORT WAS DONE BASED ON
 FBC 2001. NEED CURRENT SOIL TEST REPORT
 COMPLYING WITH FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 13:00 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 13:00 Sent To PC
Notes
2006-08-17 00:00:00RE-STAMP, REDLINED OCP FOR CU.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-02 Cont ID  
Sent By dpalmer Date 2006-08-02 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2006-08-02 Time 06:57 Sent To B
Notes
2006-08-02 00:00:00REDLINED TO VERIFY THE 9.8KW LOAD STILL
 SHOWN ON CU W/ 40A OCP.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 14:59 Sent To PC
Notes
2006-07-16 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE TITLE BLOCK AND
 PLANS SEEM TO REFLECT WHAT WOULD AMOUNT
 TO A BLDG REVISION AS NO INDICATION OF
 ELECTRICAL REVISION ON PLANS, OR TITLE
 BLOCKS IS NOTED OR INDICATED??
 PLEASE KNOW, THIS OFFICE HAS ON RECORD
 ELECTRICAL REVISION DATED AFTER THE
 REVISION DATE ON THIS TITLE BLOCK.
 PLEASE SUBMIT ANY BLDG REVISIONS
 SEPARATELY.
  
 106.1.2 FBC ADMIN SECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-13 Cont ID  
Sent By btrobaug Date 2006-04-13 Time 13:31 Rev Time 0.50
Received By btrobaug Date 2006-04-13 Time 12:13 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-02 Cont ID  
Sent By btrobaug Date 2006-03-02 Time 08:23 Rev Time 0.75
Received By btrobaug Date 2006-03-02 Time 06:35 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-15 Cont ID  
Sent By btrobaug Date 2005-12-15 Time 06:29 Rev Time 0.50
Received By btrobaug Date 2005-12-14 Time 17:18 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 13:19 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 13:19 Sent To E
Notes
2006-08-14 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 10:32 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 10:32 Sent To E
Notes
2006-07-31 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-07-15 Cont ID  
Sent By adarroug Date 2006-07-15 Time 10:55 Rev Time 0.00
Received By adarroug Date 2006-07-15 Time 10:55 Sent To E
Notes
2006-07-15 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 18:31 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 18:31 Sent To B
Notes
2006-06-08 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 15:57 Sent To B
Notes
2006-05-11 00:00:00TO "JGOMEZ' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 10:50 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 10:50 Sent To E
Notes
2006-04-05 00:00:00TO "BTROBAUG" DESK/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 15:41 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 15:41 Sent To E
Notes
2006-02-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 10:22 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 10:22 Sent To E
Notes
2005-12-14 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-29 Cont ID  
Sent By jgomez Date 2005-12-29 Time 18:28 Rev Time 0.00
Received By jgomez Date 2005-12-02 Time 09:12 Sent To  
Notes
2005-12-02 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 09:36 Rev Time 0.30
Received By tgordon Date 2006-03-02 Time 09:36 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By tgordon Date 2005-12-15 Time 14:47 Rev Time 0.30
Received By tgordon Date 2005-12-15 Time 14:46 Sent To P
Notes
2005-12-15 00:00:00*** DENIED ***
 1) MANUAL J CALCULATIONS ARE INCOMPLETE
 THEY ARE ONLY CALLING FOR 18,505 TOTAL
 BTU'S. .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-14 Cont ID  
Sent By jleech Date 2006-04-14 Time 07:38 Rev Time 0.00
Received By jleech Date 2006-04-14 Time 07:38 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-07 Cont ID  
Sent By jleech Date 2006-03-07 Time 14:05 Rev Time 0.00
Received By jleech Date 2006-03-07 Time 14:05 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-16 Cont ID  
Sent By jleech Date 2005-12-16 Time 07:53 Rev Time 0.33
Received By jleech Date 2005-12-16 Time 07:53 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-29 Cont ID  
Sent By jgomez Date 2005-12-29 Time 18:01 Rev Time 0.00
Received By jgomez Date 2005-12-29 Time 18:01 Sent To  
Notes
2005-12-29 00:00:00APPROVED BY MICHELLE 12-13-05. SEE
 SURVEY.