Plan Review Details - Permit 05111120
Plan Review Stops For Permit 05111120
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-16 Cont ID  
Sent By mjacobs Date 2006-03-16 Time 16:26 Rev Time 0.00
Received By mjacobs Date 2006-03-16 Time 06:59 Sent To  
Notes
2006-03-16 00:00:001) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.TWO COPIES OF
 EACH PRODUCT APPROVAL SHALL BE SUBMITTED
 FOR REVIEW.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3)THE TWO WINDOWS ON THE 2ND FL. NEXT TO
 THE FOYER AND THE TWO WINDOWS BELOW
 SHALL BE FIRE-RATED WINDOWS. SUBMIT THE
 PRODUCT APPROVALS FOR THE FIRE-RATED
 WINDOWS
 SEE FBC.1022.
 1022.6 EXTERIOR RAMPS AND STAIRWAY
 PROTECTION.
 EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL
 BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING AS REQUIRED IN SECTION 1019.1 .
 OPENINGS SHALL BE LIMITED TO THOSE
 NECESSARY FOR EGRESS FROM NORMALLY
 OCCUPIED SPACES.
 EXCEPTIONS:
 (1)SEPARATION FROM THE INTERIOR OF THE
 BUILDING IS NOT REQUIRED FOR
 OCCUPANCIES, OTHER THAN THOSE IN GROUP
 R-1 OR R-2, IN BUILDINGS THAT ARE NO
 MORE THAN TWO STORIES ABOVE GRADE WHERE
 THE LEVEL OF EXIT DISCHARGE IS THE FIRST
 STORY ABOVE GRADE.
  
 3) WPB ADMIN. 106.1.
 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART I, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO
 SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. IF THE DESIGN
 PROFESSIONAL IS A LANDSCAPE ARCHITECT
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF LANDSCAPE
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART II, THEN HE
 OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 DEFINED IN SECTION
 481.303(6)(A)(B)(C)(D), FS.
  
 NOTE:WPB ADMIN105.9*
 FL.S 469. THIS AGENCY IS THE LOCAL
 ASBESTOS AUTHORITY, AND SHOULD RECEIVE
 ALL NOTIFICATIONS FOR BUILDING
 DEMOLITION OR RENOVATION PROJECTS.
 CONTACT THEM FOR GENERAL INFORMATION ON
 ASBESTOS ISSUES INCLUDING REGULATIONS,
 CONTRACTORS OR CONSULTANTS.FL SS 469.003
 PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENVIROMENTAL SCIENCE &
 ENGINEERING AIR POLLUTION CONTROL
 SECTION)
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561)366-3070
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By mjacobs Date 2005-12-21 Time 11:45 Rev Time 2.50
Received By mjacobs Date 2005-12-21 Time 07:14 Sent To E
Notes
2005-12-21 00:00:001) ACCORDING TO THE DESCRIPTION OF WORK,
 PLANS ARE REQUIRED TO SHOW THE AREA AND
 DETAILS OF WORK.
  
 2) 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.ALSO A DIAGRAM SHOWING THE
 LAYOUT AND SIZE OF EACH WINDOW IS
 REQUIRED.
  
 3) SHOW IN DETAILS THE WALLS WHICH WILL
 BE REMODLED. THE TYPE OF STUDS WOOD OR
 METAL, THE STUD SPACING ETC.
  
 4) A DETAIL DRAWING FOR THE FLOOR JOIST
 REPAIR IS REQUIRED. SHOW THE SPACING OF
 THE JOISTS/THE CONNECTION/THE TYPE OF
 WOOD/THE SIZE OF JOISTS AND THE
 SHEATHING THICKNESS FOR THE FLOOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 13:58 Sent To  
Notes
2006-03-17 00:00:00************ UNSAT 2ND REVIEW *********
  
 1)NOTE: PLEASE KNOW, THERE ARE MANY
 ELECTRICAL COMMENTS BASED ON SERVICES AS
 SHOWN, HOWEVER MANY OF THOSE DO NOT
 APPLY AS THE SERVICES AS SHOWN ARE NOT
 PERMITTED. PLEASE SEE 230.2, ONLY ONE
 ELECTRICAL SERIVCE WILL BE PERMITTED.
 ALL MAINS ARE TO BE GROUPED PER 230.72.
 PLEASE SEE PTHER COMMENTS AS THEY WILL
 HAVE AN AFFECT ONE RISER AND NEW
 SERVICE.
  
 2)NOTE: PLEASE SEE RISER AS SHOWN SHOWS
 200A OCP FEEDING 125A PANEL.
 240.4, 215.5 ETC.
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS ON ALL CONDUITS ON
 RISER.
  
 4)NOTE: PLEASE SHOW ALL SERVICE AND
 PANEL LOCATIONS ON PLANS.
 215.5
  
 5)NOTE: PLEASE KNOW, A HOUSE PANEL WILL
 BE REQUIRED FOR ANY COMMON AREA BRANCH
 CIRCUITS. PLEASE KNOW, THE EGRESS
 LIGHTING ON UPPER FOYER AND STAIRS MAY
 NOT BE FED FROM ANY ONE UNIT.
 210.25
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO
 THE EGRESS LIGHTING AND CONTROL.
  
 6)NOTE: PLEASE SEE LS101-7.8,7.9,
 NFPA-70 210.70, EGRESS LIGHTING IS
 REQUIRED AND THE METHOD OF CONTROL CAN
 BE DECIDED BY THE DESIGNER. PLEASE KNOW
 HOWEVER , IS USING SWITCHES, THERE MUST
 ALSO BE 3-WAY SWITCHING AT LOWER LEVEL.
 PLEASE ALSO SEE 7.9.2.2, 7.8.1.3 WHICH
 REQUIRES 10FT CANDLES MIN DURING NORMAL
 OPERATION AND 1 FT CANDLE UNDER
 EMERGENCY. A BATTERY BACK UP LT OF SOME
 SORT(S0 WILL BE REQUIRED TO SUPPLY THE
 MIN OF 1 FT CANDLE UNDER AN EMERGENCY
 CONDITION.
  
 7)NOTE: PLEASE SEE 424.3B FOR MININUM
 OCP FOR ALL AHU'S. PLEASE SEE 2-POLE 20A
 OCP FOR 10KW LOAD?
 PLEASE SEE 50A OCP FOR 10KW ETC, NONE OF
 THESE MEET ABOVE CODE.
  
 8)NOTE: PLEASE SEE THE "WALL UNIT" AS
 SHOWN AND ALSO VERIFY OCP AND UNIT.
  
 9)NOTE: PLEASE PROVIDE ENERGY
 CALCUALTIONS PER 2004 FBCCHAPTER 13.
  
 10)NOTE: PLEAS PROVIDE SPEC FOR WATER
 HEATERS BEING SHOWN OUTSIDE IN OPEN AIR.
 THESE UNIT MUST BERATED FOR WET
 LOCATIONS, OR OUTDOOR WP ENCLOUSURES
 SHALL BE SHOWN AND DETAILED.
 110.3, 215.5
  
 11)NOTE: PLEASE SEE SD'S SHALL BE
 INSTALLED PER NFPA-72 11.8.3.5, NO SD
 CAN BE WITH-IN 20' OF THE COOKING
 APPLIANCE UNLESS MEETING THE EXCEPTIONS
 AS SET-FORTH. PLEASE PROVIDE NOTES FOR
 TYOE OF SD(S) BEING INSTALLED PER
 EXCEPTIONS.
  
 12)NOTE: PLEASE SEE THAT PLANS SHALL
 INDICATE THE CURRENT CODES FOR THIS
 DESIGN. PLEASE KNOW, WE ARE UNDER THE
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC. PLANS TO INDICATE
 THESE AT A MIN.
  
 13)NOTE: PLEASE SEE 2002 NEC 210.12 FOR
 MIN ARC FAULT PROTECTION REQUIRED FOR
 ALL CIRCUITING TO SLEEPING ROOMS.
 RECEPTS, LTS, FANS SD'S ETC.
  
 14)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES.
 215.5
  
 15)NOTE: PLEASE SEE MISSING DEDICATE
 BATH CIRCUITS PER 210.52D, 210.11C3,
 SHALL BE 20A AND #12.
  
 16)NOTE: COULD NOT LOCATE ANY MAIN
 LAUNDRY FACILITIES , PLEASE SEE
 210.11C2,210.52F, 220.16 ETC.
 PLEASE ALSO SEE MIN FACILITIES REQUIRED
 UNDER THE PLUMB AND MECHANICAL CODE.
  
 17)NOTE: PLEASE SEE FHAR 24 CFR 100.205
 FOR ALL DEVICE HEIGHTS AND DEVICE
 LOCATIONS. THESE ARE TO BE NOTED ON
 PLANS.
  
 18)NOTE: PLEASE SEE 210.52B1 FOR CIRCUIT
 REQUIRED IN DINING AREAS AND THE LIKE,
 THESE SHALL BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS.
  
 19)NOTE: PLEASE SEE 210.8A FOR GFI
 LOCATIONS. (BATHRMS) EXISTING OR NEW).
  
 20)NOTE: PLEASE SEE FBC FOR EXSITING
 BUILDING AND REQUIREMENTS FOR BRINGING
 ALL UP TO CODE WIHT THE SCOPE OF WORK
 BEING PERMFORMED. PLEASE SEE THAT THE
 LEVEL OF ALTERATION SAHLL BE STATED.
  
 21)NOTE: PLEASE SEE LOAD CALCS FOR UNIT
 "B" WHICH SHOWS NO A/C LOAD IN LOAD
 CALCUALTIONS, YET PANEL SCHEDULE SHOWS
 10KW OF LOAD??
 215.5,424.4,240.4,310.16, ETC.
  
 22)NOTE: PLEASE SEE 250.110, 250.122,
 250.24, 250.66 FOR SIZING OF GROUNDING
 ELECTRODE CONDUCTOR AND EQUIPMENT GRNDS.
  
 23)NOTE: PLEASE SEE PLANS CONTAINING
 TITLE BLOCKS AND WORK COVERED IN THE
 REQUIREMENTS OF FS 481.229 ARE REQUIRED
 TO BE SIGNED , DATED AND SEALED BYB THE
 REGISTERED ARCHITECT AS LISTED. PLEASE
 SEE 481.221, FAC 61G1-16.003, .004
  
 24) NOTE: PLEASE SEE AHU, SHOWS TWO
 DISCONECTS FOR ONE UNIT?? PLEASE VERIFY
 AS THIS IS NOT COMMON AND NO CONDUCTOR,
 DISC SIZE INFORMATION WAS SUPPLIED OR
 SHOWN. PLEASE ALSO SEE 240.21 AS THESE
 ARE BEING SHOWN AS "TAPPED" CONDUCTORS??
 PLEASE KNOW, THIS SHOULD INDICATE ONE
 DISCONNECT PER 440.11.
 31.16,240.4 ETC.
  
 25)NOTE: PLEASE SEE NO MECHANICAL PLANS
 WERE SUBMITTED IN ORDER TO VERIFY AND
 CORRELATE THE EQUIPEMNT, CALCULATIONS
 ETC.
 PLEASE SEE FBC 106.3.5.1.1 WHICH
 DICTATES THE MIN PLANS REQUIRED FOR PLAN
 REVIEW OF COMMERCIAL BUILDINGS.
  
 26)NOTE: PLEASE SEE THE NOC SUBMITTED
 HSA SINCE EXPIRED PER FS 713.13(2). IF
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING NOC, THE NOC SHALL BECOME
 VOID.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 17:13 Sent To FIRE
Notes
2005-12-27 00:00:00*********** UNSAT **************
  
 ** PLEASE KNOW, PERMIT APPLICATION
 SHOULD HAVE GONE TO THE COMM BOARD AS
 4OR MORE APT UNITS ARE CONSIDERED
 COMMERCIAL.
  
  
 1)NOTE: PLEASE SUBMIT MIN PLANS FOR
 SCOPE OF WORK BEING PERFORMED. PLEASE
 SEE FS 481.229 WHICH REQUIRES THESE
 PLANS TO BE DONE BY AN ARCHITECT,
 SIGNED, DATED AND SEALED.
 PLEASE SEE FBC ADMINISTRATIVE SECTION
 106.
  
 2)NOTE: PLEASE SEE NFPA-702002,
 NFPA-101 2003 7.8,7.9 , NFPA-72,FOR
 ALL ELECTRICAL ITEMS WHICH ARE BEING
 BROUGHT UP TO CODE COMPLIANCE.
  
  
 ** PLEASE SEE ANY FIRE REVIEW COMMENTS
 PERTAING TO FIRE PROTECTION DEVICES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-03-20 Cont ID  
Sent By nmccray Date 2006-03-20 Time 11:15 Rev Time 0.00
Received By nmccray Date 2006-03-20 Time 10:35 Sent To  
Notes
2006-03-20 00:00:00DENIED:
  
 1) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2) PLEASE REFERENCE NFPA 72, 11.8.3.5 ON
 SPECIFIC LOCATION REQUIREMENTS FOR SMOKE
 ALARM NEAR COOKING APPLIANCES, KITCHENS,
 AND BATHROOMS CONTAINING A SHOWER OR
 TUB.
  
 3) PLEASE SHOW FIRE EXTINGUISHERS
 LOCATION ON PLANS.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By mwennerg Date 2005-12-28 Time 14:39 Rev Time 0.00
Received By mwennerg Date 2005-12-28 Time 14:39 Sent To M
Notes
2005-12-28 00:00:00******DENIED******
  
 1) APARTMENT BUILDINGS WITH 3 OR MORE
 UNITS UNDER 1 ROOF REQUIRE HARD WIRED
 SMOKE DETECTORS. PLEASE SHOW ON DRAWINGS
 EVEN IF EXISTING CONDITION.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT DISTANCE NOT
 TO EXCEED 75'.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-13 Cont ID  
Sent By adarroug Date 2006-03-13 Time 14:38 Rev Time 0.00
Received By adarroug Date 2006-03-13 Time 14:38 Sent To  
Notes
2006-03-13 00:00:00TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-20 Cont ID  
Sent By jleech Date 2006-01-20 Time 14:57 Rev Time 0.00
Received By jleech Date 2005-12-01 Time 11:28 Sent To  
Notes
2005-12-01 00:00:00TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-03-14 Cont ID  
Sent By tgordon Date 2006-03-14 Time 10:52 Rev Time 0.20
Received By tgordon Date 2006-03-14 Time 10:52 Sent To  
Notes
2006-03-14 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By tgordon Date 2005-12-28 Time 15:24 Rev Time 0.15
Received By tgordon Date 2005-12-28 Time 15:24 Sent To P
Notes
2005-12-28 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS SUBMITTED TO SHOW
 A/C WORK BEING DONE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-18 Cont ID  
Sent By pschmitz Date 2006-03-18 Time 10:45 Rev Time 0.00
Received By pschmitz Date 2006-03-18 Time 10:44 Sent To FIRE
Notes
2006-03-18 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED 2ND TIME
 1)
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICAL. CONSTRUCTION
 DOUCMENTS SHALL BE OF SUFFICENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT ITWILL CONFORM TOTHE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICAL (
 SEE ALSO SECTION 106.3.5)
  
 2)TAB 403 MINIMUM FACILITIES.
 ONE AUTOMATIC CLOTHES WASHER CONNECTION
 PER DWELING UNIT.
 3) SHOW THE FIXTURE CLEARANCE
 405.3.1 WATER CLOSETS, URINALS,
 LAVATORIES AND BIDETS.
 A WATER CLOSET, URINAL, LAVATORY OR
 BIDET SHALL NOT BE SET CLOSER THAN 15
 INCHES (381 MM) FROM ITS CENTER TO ANY
 SIDE WALL, PARTITION, VANITY OR OTHER
 OBSTRUCTION, OR CLOSER THAN 30 INCHES
 (762 MM) CENTER-TO-CENTER BETWEEN WATER
 CLOSETS, URINALS OR ADJACENT FIXTURES.
 THERE SHALL BE AT LEAST A 21-INCH (533
 MM) CLEARANCE IN FRONT OF THE WATER
 CLOSET, URINAL OR BIDET TO ANY WALL,
 FIXTURE OR DOOR. WATER CLOSET
 COMPARTMENTS SHALL NOT BE LESS THAN 30
 INCHES (762 MM) WIDE OR 60 INCHES (1524
 MM) DEEP. THERE SHALL BE AT LEAST A
 21-INCH (533 MM) CLEARANCE IN FRONT OF A
 LAVATORY TO ANY WALL, FIXTURE OR DOOR
 (SEE FIGURE 405.3.1).
 4)BACK FLOW PREVENTER REQUIRED ON WATER
 SERVICE, LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By jleech Date 2006-01-20 Time 14:55 Rev Time 0.25
Received By jleech Date 2006-01-20 Time 14:55 Sent To  
Notes
2006-01-20 00:00:00DENIED;
 PLANS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695