Plan Review Details - Permit 05111101
Plan Review Stops For Permit 05111101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By mjacobs Date 2006-05-15 Time 09:02 Rev Time 0.00
Received By mjacobs Date 2006-05-13 Time 10:49 Sent To  
Notes
2006-05-15 00:00:001) ONCE AGAIN THE CLAIMED VALUATION ON
 THE PERMIT APPLICATION IS TOO LOW. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT COST EXCLUDING LAND VALUE.
 OUR VALUATION REFERENCE IS ICC(BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES PER WPB AMENDMENTS SEC. 108.3
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By mjacobs Date 2006-03-01 Time 18:38 Rev Time 1.00
Received By mjacobs Date 2006-03-01 Time 17:29 Sent To PC
Notes
2006-03-01 00:00:001) 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 13:52 Sent To  
Notes
2006-05-09 00:00:00**** UNSAT 2ND REVIEW **
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE VALUE SHALL BE BASED
 ON ALL LABOUR AND MATERIALS.
 INCLUSIVE OF ANY OWNER SUPLLIED
 EQUIPMENT.
 108.3
 PLEASE SEE A VALUE OF $15,200 IS NOW
 PLACED ON APPLICATION WHICH STILL SEEMS
 LOW FOR GEN/ ATS ETC.
 PLEASE KNOW, A VALUE WILL BE APPLIED BY
 THIS OFFICE PER "MARSHALL'S SWIFT GUIDE"
 IF NEEDED.
  
 2) NOTE: PLEASE SUBMIT ALL SPECS FOR
 GEN., ATS AND FUEL TANK.
 PLEASE SEE ONLY THE SPECS FOR THE GEN
 WHICH DOES NOT CORRELATE WITH THE KW
 RATING OF THE GEN. SHOWN ON PLANS.
 50 OR 60?
 PLEASE ALSO SEE SPECS FOR WHETHER PROOF
 ENCLOSURE WAS SUBMITTED WHICH IS OK.
 215.5
  
 3) NOTE: PLEASE KNOW, THIS PERMIT IS FOR
 THE INSTALLATION OF THE GEN ONLY/SLAB,
 AND A "GEN-ELEC" PERMIT WILL BE
 REQUIRED. THIS PERMIT APPLICATION WILL
 REFERENCE THESE PLANS ONCE ISSUED, AND
 THE PERMIT WILL BE A "TURN AROUND
 PERMIT" ISSUED THE SAME DAY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 11:06 Sent To  
Notes
2005-12-24 00:00:00********** UNSAT ***********
  
  
 1)NOTE: PLEASE SEE VALUATION FOR
 PERMITTING AND COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR AND MATERIALS.
 PLEASE SEE THE VALUE APPLIED FOR ($5200)
 IS WAY TOO LOW.
 FBC ADMIMISTRATIVE SEC 108.3 AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR SAID GENERATOR, ATS,
 AND SUB-BASE FUEL TANK.
 PLEASE BE SURE ALL LISTINGS ARE SHOWN
 AND ALL ARE LISTED BY A NRTL.
  
 3)NOTE: PLEASE PROVIDE A MEANS OF
 DISCONNECT FOR FEEDERS FROM GEN INT
 EXISTING SERVICE.,
 THIS DISCONNECTING MEANS MUST BE RATED
 FOR LOAD SERVED, SERVICE RATED, GROUPED
 WITH EXISTING MAINS ETC.
 PLEASE SEE 225.31- 225.39.
  
 4)NOTE: PLEASE INCLUDE OCP AT GENERATOR
 IN ORDER TO VERIFY CONDUCTORS, LOADS,
 ETC.
 215.5
  
 5)NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCUALTIONS FOR SAID LOADS TO BE
 IMPLIED ON GENERATOR.
 PLEASE SEE 702.5, WHICH PERMIT THE
 CUSTOMER TO SELECT LOADS, HOWEVER ON A
 ATS SYSTEM, GENERATOR MUST STILL BE
 RATED FOR ALL LOADS TO BE SERVED.
 PLEASE BE SURE ANY A/C/ HEAT, MOTOR
 LOADS ARE FIGURED AT 100%.
 ** LOAD SHEDDING IS PERMITTED, HOWEVER
 PLEASE SHOW DETAILS IF THIS IS DONE.
  
 6)NOTE: PLEASE KNOW, THE CGC APPLIED TO
 PERMIT IS ONLY PERMITTED TO PLACE SLAB
 AND GEN AND IS NOT PERMITTED TO DO ANY
 OTHER ELECTRICAL WORK.
 PLEASE SEE THAT AN ELECTRICAL CONTRACTOR
 WAS NOT SIGNED ON PERMIT APPLICATION.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-25 Cont ID  
Sent By nmccray Date 2006-05-25 Time 14:31 Rev Time 0.00
Received By nmccray Date 2006-05-24 Time 14:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By mcarsill Date 2005-12-23 Time 10:35 Rev Time 0.00
Received By mcarsill Date 2005-12-23 Time 10:35 Sent To  
Notes
2005-12-23 00:00:001. PLEASE PROVIDE PRODUCT INFORMATION
 FOR PROPOSED EMERGENCY GENERATOR.
  
 2. PLEASE ILLUSTRATE ANY INGRESS/EGRESS
 DOORS FOR THE EXISTING SHELTER. ALSO ARE
 ANY WINDOWS PRESENT.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By nmccray Date 2006-05-24 Time 15:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-02-28 Cont ID  
Sent By kstevens Date 2006-02-28 Time 10:33 Rev Time 0.00
Received By kstevens Date 2006-02-28 Time 10:33 Sent To  
Notes
2006-02-28 00:00:00GENERATOR IS A DIESAL GENERATOR - NO
 NATURAL OR L/P GAS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 09:57 Sent To  
Notes
2006-05-08 00:00:00TO "COMM" BD#3
2006-04-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 10:35 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 10:35 Sent To  
Notes
2005-12-22 00:00:00TO "COMM" BD#34
2005-12-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-01 Time   Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 18:49 Sent To  
Notes
2005-11-30 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-22 Cont ID  
Sent By tgordon Date 2006-05-22 Time 14:22 Rev Time 0.30
Received By tgordon Date 2006-05-22 Time 14:22 Sent To  
Notes
2006-05-22 00:00:00REQUESTED INFORMATION HAS BEEN PROVIDED
 AND PLACEMENT REQUIREMENTS HAVE BEEN
 MET.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By pkrauss Date 2006-01-25 Time 08:15 Rev Time 0.00
Received By pkrauss Date 2006-01-25 Time 08:15 Sent To  
Notes
2006-01-25 00:00:00DENIED:
 1.PLEASE PROVIDE MANUFACTURERS
 SUBMTITTAL DATA FOR THE GENERATOR.
  
 2.PER NFPA 37 SECTION 4.1.4, ENGINES
 LOCATED OUTDOORS SHALL BE LOCATED AT
 LEAST 5 FT FROM OPENINGS IN WALLS AND 5
 FT FROM STRUCTURES HAVEING COMBUSTIBLE
 WALLS.AS MINIMUM SEPARATION IS NOT
 REQUIRED IF THE FOLLOWING CONDITIONS ARE
 MET: 1) THE ADJACENT WALL OF THE
 STRUCTURE HAS A FIRE RESISTANCE RATING
 OF AT LEAST 1 HOUR.2)THE WEATHERPROOF
 ENCLOSURE WILL NOT IIGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
  
 3.PLEASE INDICATE DISTANCE OF THE
 GENERATOR EXHAUST TO ANY OPENINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-24 Cont ID  
Sent By mmclean Date 2006-05-24 Time 11:59 Rev Time 0.00
Received By mmclean Date 2006-05-24 Time 11:59 Sent To  
Notes
2006-05-24 00:00:00DENIED,
 1. THE BOUNDARY SURVEY & A-1 SHEET DOES
 NOT MATCH (SEE A-1 THAT SHOWS MOVE
 DETAIL INFORMATION ON EQUIPMENT SHELTER)
 2. PLEASE PLACE THE PROPOSED GENERATOR
 ON THE BOUNDARY SURVEY WITH SETBACKS (AS
 SHOWN ON A-1
 3. PLEASE IDENTIFY IF THERE WILL BE ANY
 PARKING USED FOR THE PLACEMENT OF THE
 PROPOSED GENERATOR (BOUNDARY SURVEY
 SHOWS ASPHALT)
 4. NEED TO PROVIDE THE EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM BEACH FOR THE
 FENCE/GATE ON A-1

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-13 Cont ID  
Sent By mmclean Date 2005-12-13 Time 14:37 Rev Time 0.00
Received By mmclean Date 2005-12-13 Time 14:37 Sent To I
Notes
2005-12-13 00:00:00DENIED,
 1. MUST PROVIDE AN UPDATED SURVEY OR
 SITEPLAN SHOWING THE LOCATION OF THE
 GENERATOR WITH SETBACKS.
 2. MUST PROVIDE THE DIMENSION OF THE
 GENERATOR.
 3. INFORMATION PROVIDED DOES NOT GIVE A
 CLEAR VIEW OF THE PROPERTY AND SETBACK
 OF THE GENERATOR
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720