Plan Review Stops For Permit 05111101 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-05-15 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-05-15 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-05-13 |
Time |
10:49 |
Sent To |
|
|
Notes |
2006-05-15 00:00:00 | 1) ONCE AGAIN THE CLAIMED VALUATION ON | | THE PERMIT APPLICATION IS TOO LOW. FOR | | PERMITTING PURPOSES, VALUATION OF | | BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | REPLACEMENT COST EXCLUDING LAND VALUE. | | OUR VALUATION REFERENCE IS ICC(BVD), | | MARSHALL-SWIFT AND MEANS COST ANALYSIS | | SERVICES PER WPB AMENDMENTS SEC. 108.3 | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-03-01 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-03-01 |
Time |
18:38 |
Rev Time |
1.00 |
Received By |
mjacobs |
Date |
2006-03-01 |
Time |
17:29 |
Sent To |
PC |
|
Notes |
2006-03-01 00:00:00 | 1) 104.6.5 BUILDING PERMIT VALUATION. IF | | IN THE OPINION OF THE BUILDING OFFICIAL | | THE CLAIMED VALUATION OF BUILDING, AL- | | TERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS | | TO BE UNDERESTIMATED ON THE APPLICATION, | | THE PERMIT SHALL BE DENIED, UNLESS THE | | APPLICANT CAN SHOW DETAILED ESTIMATES | | AND/OR BONA FIDED SIGNED CONTRACTS (EX- | | CLUDING LAND VALUE) TO MEET THE APPROVAL | | OF THE BUILDING OFFICIAL. FOR PERMITTING | | PURPOSES, VALUATION FOR BUILDINGS AND | | SYSTEMS SHALL BE FOUND IN MARSHALL AND | | SWIFT OR THE SOUTHERN BUILDING CODE | | CONGRESS INTERNATIONAL VALUATION TABLES, | | LATEST EDITION, AND SHALL BE BASED ON | | TOTAL REPLACEMENT VALUE TO INCLUDE | | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- | | ICAL, INTERIOR FINISH, NORMAL SITE WORK | | (EXCAVATION AND BACKFILL FOR BUILDINGS), | | ARCHITECTURAL AND DESIGN FEES, OVERHEAD | | AND PROFIT, EXCLUDING ONLY LAND VALUE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:805-6726 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-05-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-05-09 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-05-09 |
Time |
13:52 |
Sent To |
|
|
Notes |
2006-05-09 00:00:00 | **** UNSAT 2ND REVIEW ** | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | REVIEW STILL NEED TO BE ADDRESSED. | | | | 1) NOTE: PLEASE SEE VALUE SHALL BE BASED | | ON ALL LABOUR AND MATERIALS. | | INCLUSIVE OF ANY OWNER SUPLLIED | | EQUIPMENT. | | 108.3 | | PLEASE SEE A VALUE OF $15,200 IS NOW | | PLACED ON APPLICATION WHICH STILL SEEMS | | LOW FOR GEN/ ATS ETC. | | PLEASE KNOW, A VALUE WILL BE APPLIED BY | | THIS OFFICE PER "MARSHALL'S SWIFT GUIDE" | | IF NEEDED. | | | | 2) NOTE: PLEASE SUBMIT ALL SPECS FOR | | GEN., ATS AND FUEL TANK. | | PLEASE SEE ONLY THE SPECS FOR THE GEN | | WHICH DOES NOT CORRELATE WITH THE KW | | RATING OF THE GEN. SHOWN ON PLANS. | | 50 OR 60? | | PLEASE ALSO SEE SPECS FOR WHETHER PROOF | | ENCLOSURE WAS SUBMITTED WHICH IS OK. | | 215.5 | | | | 3) NOTE: PLEASE KNOW, THIS PERMIT IS FOR | | THE INSTALLATION OF THE GEN ONLY/SLAB, | | AND A "GEN-ELEC" PERMIT WILL BE | | REQUIRED. THIS PERMIT APPLICATION WILL | | REFERENCE THESE PLANS ONCE ISSUED, AND | | THE PERMIT WILL BE A "TURN AROUND | | PERMIT" ISSUED THE SAME DAY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-12-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-12-24 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2005-12-24 |
Time |
11:06 |
Sent To |
|
|
Notes |
2005-12-24 00:00:00 | ********** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE VALUATION FOR | | PERMITTING AND COMPLETE SCOPE OF WORK | | SHALL INCLUDE ALL LABOR AND MATERIALS. | | PLEASE SEE THE VALUE APPLIED FOR ($5200) | | IS WAY TOO LOW. | | FBC ADMIMISTRATIVE SEC 108.3 AS ADOPTED | | BY THE CITY OF WEST PALM BEACH. | | | | 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES | | CUT/SPEC SHEETS FOR SAID GENERATOR, ATS, | | AND SUB-BASE FUEL TANK. | | PLEASE BE SURE ALL LISTINGS ARE SHOWN | | AND ALL ARE LISTED BY A NRTL. | | | | 3)NOTE: PLEASE PROVIDE A MEANS OF | | DISCONNECT FOR FEEDERS FROM GEN INT | | EXISTING SERVICE., | | THIS DISCONNECTING MEANS MUST BE RATED | | FOR LOAD SERVED, SERVICE RATED, GROUPED | | WITH EXISTING MAINS ETC. | | PLEASE SEE 225.31- 225.39. | | | | 4)NOTE: PLEASE INCLUDE OCP AT GENERATOR | | IN ORDER TO VERIFY CONDUCTORS, LOADS, | | ETC. | | 215.5 | | | | 5)NOTE: PLEASE PROVIDE COMPLETE LOAD | | CALCUALTIONS FOR SAID LOADS TO BE | | IMPLIED ON GENERATOR. | | PLEASE SEE 702.5, WHICH PERMIT THE | | CUSTOMER TO SELECT LOADS, HOWEVER ON A | | ATS SYSTEM, GENERATOR MUST STILL BE | | RATED FOR ALL LOADS TO BE SERVED. | | PLEASE BE SURE ANY A/C/ HEAT, MOTOR | | LOADS ARE FIGURED AT 100%. | | ** LOAD SHEDDING IS PERMITTED, HOWEVER | | PLEASE SHOW DETAILS IF THIS IS DONE. | | | | 6)NOTE: PLEASE KNOW, THE CGC APPLIED TO | | PERMIT IS ONLY PERMITTED TO PLACE SLAB | | AND GEN AND IS NOT PERMITTED TO DO ANY | | OTHER ELECTRICAL WORK. | | PLEASE SEE THAT AN ELECTRICAL CONTRACTOR | | WAS NOT SIGNED ON PERMIT APPLICATION. | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY AFFECT | | ELECTRICAL PLANS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-05-25 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2006-05-25 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2006-05-24 |
Time |
14:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2005-12-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2005-12-23 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2005-12-23 |
Time |
10:35 |
Sent To |
|
|
Notes |
2005-12-23 00:00:00 | 1. PLEASE PROVIDE PRODUCT INFORMATION | | FOR PROPOSED EMERGENCY GENERATOR. | | | | 2. PLEASE ILLUSTRATE ANY INGRESS/EGRESS | | DOORS FOR THE EXISTING SHELTER. ALSO ARE | | ANY WINDOWS PRESENT. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2006-05-24 |
Time |
15:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2006-02-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-02-28 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-02-28 |
Time |
10:33 |
Sent To |
|
|
Notes |
2006-02-28 00:00:00 | GENERATOR IS A DIESAL GENERATOR - NO | | NATURAL OR L/P GAS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-04-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-21 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-21 |
Time |
09:57 |
Sent To |
|
|
Notes |
2006-05-08 00:00:00 | TO "COMM" BD#3 | 2006-04-21 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-12-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-14 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-14 |
Time |
10:35 |
Sent To |
|
|
Notes |
2005-12-22 00:00:00 | TO "COMM" BD#34 | 2005-12-14 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-03-01 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-30 |
Time |
18:49 |
Sent To |
|
|
Notes |
2005-11-30 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-05-22 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-05-22 |
Time |
14:22 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-05-22 |
Time |
14:22 |
Sent To |
|
|
Notes |
2006-05-22 00:00:00 | REQUESTED INFORMATION HAS BEEN PROVIDED | | AND PLACEMENT REQUIREMENTS HAVE BEEN | | MET. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-01-25 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-01-25 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-01-25 |
Time |
08:15 |
Sent To |
|
|
Notes |
2006-01-25 00:00:00 | DENIED: | | 1.PLEASE PROVIDE MANUFACTURERS | | SUBMTITTAL DATA FOR THE GENERATOR. | | | | 2.PER NFPA 37 SECTION 4.1.4, ENGINES | | LOCATED OUTDOORS SHALL BE LOCATED AT | | LEAST 5 FT FROM OPENINGS IN WALLS AND 5 | | FT FROM STRUCTURES HAVEING COMBUSTIBLE | | WALLS.AS MINIMUM SEPARATION IS NOT | | REQUIRED IF THE FOLLOWING CONDITIONS ARE | | MET: 1) THE ADJACENT WALL OF THE | | STRUCTURE HAS A FIRE RESISTANCE RATING | | OF AT LEAST 1 HOUR.2)THE WEATHERPROOF | | ENCLOSURE WILL NOT IIGNITE COMBUSTIBLE | | MATERIALS OUTSIDE THE ENCLOSURE. | | | | 3.PLEASE INDICATE DISTANCE OF THE | | GENERATOR EXHAUST TO ANY OPENINGS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-05-24 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-05-24 |
Time |
11:59 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-05-24 |
Time |
11:59 |
Sent To |
|
|
Notes |
2006-05-24 00:00:00 | DENIED, | | 1. THE BOUNDARY SURVEY & A-1 SHEET DOES | | NOT MATCH (SEE A-1 THAT SHOWS MOVE | | DETAIL INFORMATION ON EQUIPMENT SHELTER) | | 2. PLEASE PLACE THE PROPOSED GENERATOR | | ON THE BOUNDARY SURVEY WITH SETBACKS (AS | | SHOWN ON A-1 | | 3. PLEASE IDENTIFY IF THERE WILL BE ANY | | PARKING USED FOR THE PLACEMENT OF THE | | PROPOSED GENERATOR (BOUNDARY SURVEY | | SHOWS ASPHALT) | | 4. NEED TO PROVIDE THE EASEMENT APPROVAL | | FROM THE CITY OF WEST PALM BEACH FOR THE | | FENCE/GATE ON A-1 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-12-13 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-12-13 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-12-13 |
Time |
14:37 |
Sent To |
I |
|
Notes |
2005-12-13 00:00:00 | DENIED, | | 1. MUST PROVIDE AN UPDATED SURVEY OR | | SITEPLAN SHOWING THE LOCATION OF THE | | GENERATOR WITH SETBACKS. | | 2. MUST PROVIDE THE DIMENSION OF THE | | GENERATOR. | | 3. INFORMATION PROVIDED DOES NOT GIVE A | | CLEAR VIEW OF THE PROPERTY AND SETBACK | | OF THE GENERATOR | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|