Plan Review Details - Permit 05111014
Plan Review Stops For Permit 05111014
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-07-06 Cont ID  
Sent By mperson Date 2006-07-06 Time 10:36 Rev Time 0.33
Received By mperson Date 2006-07-06 Time 10:36 Sent To PC
Notes
2006-07-06 00:00:00REVISION: REROUTE GAS LINE TO GENERATOR,
 AND ADD FUTURE LINE TO BARBEQUE GRILL.
 REFERENCE GEN/RES #05121074

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-06-21 Cont ID  
Sent By mperson Date 2006-06-21 Time 10:38 Rev Time 0.33
Received By mperson Date 2006-06-21 Time 10:37 Sent To PC
Notes
2006-06-21 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS REVISION:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106
 CONSTRUCTION DOCUMENTS: REVISION
 DRAWINGS IN PENCIL UNACCEPTABLE
 2. PER FBC-2004 CHAPTER 1, SECTION 106.1
 CONSTRUCTION DOCUMENTS: MINIMUM OF 2
 (TWO) DRAWINGS REQUIRED FOR REVISION.
 (NOTE: ONLY ONE REVISION DRAWING
 SUBMITTED IN PENCIL)
 3. PER FBC-2004 CHAPTER 1
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL.(NOTE: WHERE THE 1" PE
 BELOW GRADE IS INDICATED ON THE REVISION
 THE TRANSITION TO ABOVE GROUND GALVAN-
 IZED NEEDS TO BE INDICATED ON REVISION)
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: THERE ARE NO
 CORRESPONDING LENGTHS INDICATED ON THE
 REVISION DRAWING)
 5. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, AND ALL PIPE SIZES.(NOTE: THE
 ONLY MATERIAL INDICATED ON REVISION IS
 THE UNDERGROUND PE, THE ABOVE GROUND
 GALVANIZED MATERIAL NEEDS TO BE
 INDICATED ON REVISION DRAWING)
 6. PER FBC-2004 FUEL GAS, SECTION 409.4.
 A LISTED SHUT OFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR. PLEASE SEE CORRECTED REVISION
 DRAWING FOR REFERENCE FOR RESUBMITTAL.
 7. FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.(NOTE: ON 2LB SYSTEMS SHUT OFF
 VALVE AND REGULATOR SHALL BE INSTALLED
 ON FUTURE APPLIANCES FOR FINAL, PLEASE
 SEE CORRECTED DRAWING FOR REFERENCE FOR
 RESUBMITTAL)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-01-30 Cont ID  
Sent By mperson Date 2006-01-30 Time 10:45 Rev Time 1.25
Received By mperson Date 2006-01-30 Time 10:45 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By mperson Date 2005-12-23 Time 13:37 Rev Time 1.25
Received By mperson Date 2005-12-23 Time 13:37 Sent To  
Notes
2005-12-23 00:00:00DENIED
 REFERENCE:FBC-2004 FUEL GAS
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. LOCATION OF GENERATOR SHALL BE
 APPROVED BY ZONING AND MACHANICAL PRIOR
 TO HAVING A GAS PERMIT ISSUED
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX(561)805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 09:33 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 09:33 Sent To G
Notes
2006-07-03 00:00:00TO "G" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 16:30 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 16:30 Sent To G
Notes
2006-06-12 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-11 Cont ID  
Sent By adarroug Date 2006-01-11 Time 09:17 Rev Time 0.00
Received By adarroug Date 2006-01-11 Time 09:17 Sent To G
Notes
2006-01-11 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-23 Cont ID  
Sent By mperson Date 2005-12-23 Time 14:46 Rev Time 0.00
Received By mperson Date 2005-11-30 Time 09:23 Sent To  
Notes
2005-11-30 00:00:00TO "G" BOX