Plan Review Details - Permit 05111003
Plan Review Stops For Permit 05111003
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 15:17 Rev Time 0.77
Received By jwitmer Date 2005-12-01 Time 15:16 Sent To  
Notes
2005-12-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05111003
 ADD: 701 NORTHPOINTE PARKWAY
 CONT: PASS INTERNATIONAL
 TEL: (954)421-9000
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 803.5 INTERIOR FINISH REQUIREMENTS
 BASED ON GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL
 HAVE A FLAME SPREAD INDEX NOT GREATER
 THAN THAT SPECIFIED IN TABLE 803.5 FOR
 THE GROUP AND LOCATION DESIGNATED.
 INTERIOR WALL AND CEILING FINISH
 MATERIALS, OTHER THAN TEXTILES, TESTED
 IN ACCORDANCE WITH NFPA 286 AND MEETING
 THE ACCEPTANCE
  
 3) MISSING REQUIREMENTS FOUND UNDER THE
 2004 CODE:
 3A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 3B)THE USE AND OCCUPANCY, IN
 ACCORDANCE WITH THE PROVISIONS OF
 CHAPTER 3 .
 3C)THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6 .
 3D) THE DESIGN OCCUPANT LOAD.
 3E)IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 3F) ANY SPECIAL STIPULATIONS AND
 CONDITIONS OF THE BUILDING PERMIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-01 Cont ID  
Sent By jleahy Date 2005-12-01 Time 14:29 Rev Time 0.45
Received By jleahy Date 2005-12-01 Time 14:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 15:08 Sent To  
Notes
2005-11-29 00:00:00TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-12-09 Cont ID  
Sent By tgordon Date 2005-12-09 Time 10:23 Rev Time 0.20
Received By tgordon Date 2005-12-09 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-07 Cont ID  
Sent By jleech Date 2005-12-07 Time 08:35 Rev Time 0.25
Received By jleech Date 2005-12-07 Time 08:35 Sent To  
Notes
***NONE***