Plan Review Details - Permit 05110837
Plan Review Stops For Permit 05110837
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-01-13 Cont ID  
Sent By mperson Date 2006-01-13 Time 13:35 Rev Time 0.33
Received By mperson Date 2006-01-13 Time 13:35 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-05 Cont ID  
Sent By mperson Date 2006-01-05 Time 15:48 Rev Time 1.25
Received By mperson Date 2006-01-05 Time 15:48 Sent To  
Notes
2006-01-05 00:00:00DENIED
  
 REFERENCE: FBC-2004 FUEL GAS
  
 ON AN 0.5 PSI OR LESS INLET PRESSURE
 NATURAL GAS SYSTEM, ALL SYSTEM PIPES
 SHALL HAVE THE SAME INLET PRESSURE OF
 0.5 PSI OR LESS AND PRESSURE DROP OF
 0.5 IN OF WC PER TABLES
 404.4(2) SCH. 40 METALLIC PIPE
 402.4(14) CSST
 402.4(20) PE
 NOTE:PER FLORIDA PUBLIC UTILITIES THE
 MAXIMUM DELIVERY PRESSURE AFTER THE
 METER IS 11 INCH WATER COL.
 DENIED
  
 REFERENCE: FBC-2004 FUEL GAS
  
 ON AN 0.5 PSI OR LESS INLET PRESSURE
 NATURAL GAS SYSTEM, ALL SYSTEM PIPES
 SHALL HAVE THE SAME INLET PRESSURE OF
 0.5 PSI OR LESS AND PRESSURE DROP OF 0.5
 IN OF WC PER TABLES
 402.4(2) SCH. 40 METALLIC PIPE
 402.4(14) CSST
 402.4(20) PE
 NOTE: PER FLORIDA PUBLIC UTILITIES THE
 MAXIMUM DELIVERY PRESSURE AFTER THE
 METER IS 11 INCH WATER COL.
  
 ANY QUESTIONS REGUARDING THESE
 REQUIREMENTS MAY BE REFERRED TO:
  
 PLAN REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 OR
 CHEIF PLUMBING INSPECTOR
 PAUL SCHMITZ (561)805-6692
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-05 Cont ID  
Sent By mperson Date 2006-01-05 Time 17:02 Rev Time 0.00
Received By mperson Date 2005-11-28 Time 16:19 Sent To  
Notes
2005-11-28 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved