Plan Review Details - Permit 05110817
Plan Review Stops For Permit 05110817
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-20 Cont ID  
Sent By jwitmer Date 2005-12-20 Time 07:46 Rev Time 0.55
Received By jwitmer Date 2005-12-20 Time 07:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 09:32 Rev Time 0.77
Received By jwitmer Date 2005-12-01 Time 09:30 Sent To PC
Notes
2005-12-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110817
 ADD: 1675 PALM BEACH LAKES # 111
 CONT: MJS CONSTRUCTION
 TEL: (561)615-9348
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS NEED TO BE UPDATED TO THE 2004
 FL BLDG CODE. THE FOLLOWING ITEMS NEED
 TO REFLECT THE REQUIREMENTS OF 110.2.*
 1A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 1B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3 .
 1C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6 .
 1D)THE DESIGN OCCUPANT LOAD.
 1E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 1F) ANY SPECIAL STIPULATIONS AND
 CONDITIONS OF THE BUILDING PERMIT.
  
 2) SEE TABLE 601 FOR NEW BLDG
 CLASSIFICATION, FIRE REISITANT
 REQUIREMENTS PLEASE CORRECT.
  
 3) UPDATE PLANS TO THE 2004 CODE FOR
 T803.3 SEE TABLE 803.5.
 803.5 INTERIOR FINISH REQUIREMENTS BASED
 ON GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL
 HAVE A FLAME SPREAD INDEX NOT GREATER
 THAN THAT SPECIFIED IN TABLE 803.5 FOR
 THE GROUP AND LOCATION DESIGNATED.
 INTERIOR WALL AND CEILING FINISH
 MATERIALS, OTHER THAN TEXTILES, TESTED
 IN ACCORDANCE WITH NFPA 286 AND MEETING
 THE ACCEPTANCE CRITERIA OF SECTION
 803.2.1 , SHALL BE PERMITTED TO BE USED
 WHERE A CLASS A CLASSIFICATION IN
 ACCORDANCE WITH ASTM E 84 IS REQUIRED.
 TABLE 803.5
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-30 Cont ID  
Sent By jleahy Date 2005-11-30 Time 15:51 Rev Time 0.45
Received By jleahy Date 2005-11-30 Time 15:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-30 Cont ID  
Sent By nmccray Date 2005-11-30 Time 11:49 Rev Time 0.00
Received By nmccray Date 2005-11-30 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 10:00 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 10:00 Sent To B
Notes
2005-12-15 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2005-12-20 Time 07:42 Sent To  
Notes
2005-11-28 00:00:00TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-30 Cont ID  
Sent By hmoser Date 2005-11-30 Time 14:36 Rev Time 0.00
Received By hmoser Date 2005-11-30 Time 13:28 Sent To  
Notes
***NONE***