Plan Review Stops For Permit 05110768 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2006-07-18 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-07-18 |
Time |
09:57 |
Rev Time |
0.50 |
Received By |
amorse |
Date |
2006-07-18 |
Time |
09:57 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-06-08 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-06-08 |
Time |
11:29 |
Rev Time |
0.50 |
Received By |
amorse |
Date |
2006-06-08 |
Time |
11:29 |
Sent To |
|
|
Notes |
2006-06-08 00:00:00 | | | | | DENIED | | | | 1) WINDOW PRODUCT APPROVALS ARE FOR NON- | | IMPACT AND WILL REQUIRE IMPACT | | PROTECTION DEVICES. PLEASE SUBMIT | | PRODUCT APPROVALS FOR STORM SHUTTERS | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-06-08 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-04-05 |
Time |
11:27 |
Rev Time |
0.50 |
Received By |
amorse |
Date |
2006-04-05 |
Time |
11:26 |
Sent To |
|
|
Notes |
2006-06-08 00:00:00 | | | | | | | DENIED | | | | 1) THE PERMIT APPLICATION SHALL INCLUDE | | TWO COPIES OF EACH PRODUCT APPROVAL THAT | | IS RELEVANT PER 9B-72. THESE SHOULD | | INCLUDE THE FLORIDA STATE APPROVAL COVER | | PAGES, AND THE PRODUCT NOA THAT LISTS | | THE SYSTEM COMPONENTS/ FASTENER LIST | | PAGES, THE PAGES WITH THE CHOSEN | | ASSEMBLY/ SYSTEM TO BE USED AND THE | | GENERAL LIMITATIONS PAGE. ALL CAN BE | | FOUND ON WWW.FLORIDABUILDING.ORG | | | | 2) BEFORE A PERMIT TO CONSTRUCT, MAY | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | SETS OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. | | PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION | | | | 3) AWNINGS SHALL BE SUBMITTED UNDER A | | SEPERATE PERMIT APPLICATION | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-12-19 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2005-12-19 |
Time |
14:40 |
Rev Time |
1.00 |
Received By |
amorse |
Date |
2005-12-19 |
Time |
14:40 |
Sent To |
PC |
|
Notes |
2005-12-19 00:00:00 | | | | | DENIED | | | | 1) THE NEW FRONT ENCLOSURE IS AN | | ADDITION AND AS SUCH SHALL COMPLY WITH | | THE PROVSIONS OF THE 2004 FL BLDG CODE | | REMOVE GENERAL NOTE THAT SPEC'S UBC | | | | 2) WINDOWS SHALL BE IMPACT RESISTANT OR | | MUST BE PROTECTED WITH APPROVED IMPACT | | RESISTANT COVERINGS AS PER 1609.1.4 2004 | | FBC | | | | 3) SUBMIT FRAMING DETAILS THAT SHOW | | BACKING FOR STORM PANELS | | | | 4) SUBMIT DOOR AND WINDOW SIZES | | | | 5) SUBMIT DETAILS OF THE ROOF AND WALL | | FRAMING ATTACHMENT TO EXISTING | | | | 6) SUBMIT DETAILS ON ALL FRAMING | | CONNECTORS FOR STRAPPING/ANCHORING | | | | 7) SUBMIT AN ANCHOR SCHEDULE IN LIEU OF | | PRODUCT APPROVALS FOR EACH CONNECTOR | | BEING USED. SHOW THE APPROVED | | MANUFACTURER,TYPE,SIZE,ETC. OF EACH | | CONNECTOR | | | | 8) ROOFS WITH A PITCH FROM 2/12 TO 4/12 | | REQUIRE DOUBLE UNDERLAYMENT PER 905.2.7 | | 2004 FBC RES. | | | | 9) SUBMIT 2 COPIES OF THE PRODUCT | | APPROVALS COMPLETE WITH THE FLORIDA | | STATE APPROVAL COVER SHEETS AND PRODUCT | | NOA'S. ROOFING AND STORM PANELS ALSO | | REQUIRE PRODUCT APPROVAL | | | | 10) SUBMIT FOUNDATION PLAN, SHOW IF THE | | FOUNDATION IS NEW OR EXISTING | | | | 11) FRONT DOOR AWNING SHALL COMPLY WITH | | 3105. 2004 FBC AND 2 COPIES OF PRODUCT | | APPROVAL SHALL BE SUBMITTED | | | | 12) SUBMIT 2 COPIES OFF ALL REQUIRED | | DRAWINGS SIGNED BY THE PARTY RESPONSIBLE | | FOR THE DRAWINGS THAT INDICATE | | COMPLIANCE WITH THE 2004 FL BLDG CODE | | | | 13) NOTE THAT IF A FLOOR PLAN WITH | | ELECTRICAL IS NOT SUBMITTED AN | | ADDITIONAL PERMIT WILL BE REQUIRED | | | | 14) SUBMIT A RECORDED NOTICE OF | | COMMENCEMENT PRIOR TO A PERMIT BEING | | ISSUED | | | | 15) PALM BEACH COUNTY IMPACT FEES ARE | | REQUIRED, THE 2 SETS OF PLANS SHALL BE | | STAMPED BY THEM AND A COPY OF THE | | RECEIPT SUBMITTED TO WPB CONSTRUCTION | | SERVICES | | | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-06-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-06-08 |
Time |
14:05 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2006-06-08 |
Time |
14:05 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-03-20 |
Time |
14:04 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2006-03-20 |
Time |
14:02 |
Sent To |
|
|
Notes |
2006-06-08 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} 210.52(A) GENERAL PROVISIONS. IN | | EVERY KITCHEN, FAMILY ROOM, DINING ROOM, | | LIVING ROOM, PARLOR, LIBRARY, DEN, | | SUNROOM, BEDROOM, RECREATION ROOM, OR | | SIMILAR ROOM OR AREA OF DWELLING UNITS, | | RECEPTACLE OUTLETS SHALL BE INSTALLED IN | | ACCORDANCE WITH THE GENERAL PROVISIONS | | SPECIFIED IN 210.52(A)(1) THROUGH | | (A)(3). | | (1) SPACING. RECEPTACLES SHALL BE | | INSTALLED SO THAT NO POINT MEASURED | | HORIZONTALLY ALONG THE FLOOR LINE IN ANY | | WALL SPACE IS MORE THAN 1.8 M (6 FT) | | FROM A RECEPTACLE OUTLET. | | | | PLEASE HAVE THE PERSON RESPONSIBLE FOR | | DRAWING THE PLAN PRINT AND SIGN THEIR | | NAME TO SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-06-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-06 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-06 |
Time |
12:05 |
Sent To |
B |
|
Notes |
2006-06-06 00:00:00 | TO "AMORSE" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-05-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-27 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-27 |
Time |
13:06 |
Sent To |
Z |
|
Notes |
2006-05-27 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-12-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-07 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-07 |
Time |
10:03 |
Sent To |
B |
|
Notes |
2005-12-07 00:00:00 | TO "MISC" BOX#2 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-05-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-19 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-28 |
Time |
09:58 |
Sent To |
|
|
Notes |
2005-11-28 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-06-04 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-06-04 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-06-04 |
Time |
10:14 |
Sent To |
I |
|
Notes |
2006-06-04 00:00:00 | THE PROPOSED ENCLOSED PORCH SITS BEYOND | | THE 25FT FRONT SETBACK AND SIDE SETBACK | | IS MORE THAT 5FT. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-12-06 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-12-06 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-12-06 |
Time |
17:39 |
Sent To |
I |
|
Notes |
2005-12-06 00:00:00 | DENIED, | | 1. MUST PROVIDE TWO COPY OF PLANS | | SHOWING THE SURVEY/SITEPLANS/ELEVATION | | PLANS ETC. (BOTHS SETS TO BE STAMPED AND | | A COPY ATTACH WITH APPLICATION FOR FILE | | WITH THE DEPT (CONSTRUCTION SERVICES). | | ONLY 1 SET WAS SUBMITTED. | | | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|