Plan Review Details - Permit 05110525
Plan Review Stops For Permit 05110525
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-20 Cont ID  
Sent By rmcdouga Date 2005-12-20 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2005-12-20 Time 16:28 Sent To  
Notes
2005-12-20 00:00:00PROVISO
  
 1) THE SELF ADHERED CAP SHEET MUST BE
 APPLIED OVER A MECHANICALLY FASTENED
 BASE SHEET PER RAS 120.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-15 Cont ID  
Sent By rmcdouga Date 2005-11-15 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2005-11-15 Time 16:25 Sent To  
Notes
2005-11-15 00:00:00DENIED
  
 1) SPECIFY THE ATTACHMENT METHOD THAT
 WILL BE USED TO INSTALL THE CLAY ROOF
 TILE. THE REQUIRED UPLIFT MOMENT BASED
 ON THE INFORMATION SUBMITTED IS 26.1
 FT-LBS.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714