2005-11-15 00:00:00 | DENIED |
| |
| 1) THE FLORIDA PRODUCT APPROVAL COVER |
| SHEET FOR THE FIRESTONE MODIFIED ROOFING |
| WAS NOT SUBMITTED. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 2) THE SBS SYSTEM THAT IS SPECIFIED IN |
| THE FIRESTONE NOA HAS A MAXIMUM DESIGN |
| PRESSURE OF -45 PSF WITH NO INCREASE |
| ALLOWED FOR ENHANCED FASTENING PER |
| LIMITATION #9. THIS DOES NOT MEET THE |
| REQUIRED UPLIFT PRESSURES AT THE ROOF |
| CORNERS OR EDGES (ZONES 2 & 3) FOR |
| EXPOSURE B AND 140 MPH WIND SPEED. |
| |
| 3) THE MAXIMUM DESIGN PRESSURE SPECIFIED |
| IN THE MULE-HIDE PRODUCT APPROVAL OF -45 |
| PSF WITH LIMITATION #9 DOES NOT MEET THE |
| REQUIRED UPLIFT PRESSURE. |
| |
| 4) THE FLORIDA PRODUCT APPROVAL FOR THE |
| MULE-HIDE PRODUCT HAS A STATUS OF |
| VALIDATED AND HAS NOT YET BEEN APPROVED |
| BY THE STATE. |
| |
| 5) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |