Plan Review Details - Permit 05110336
Plan Review Stops For Permit 05110336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-12-15 Cont ID  
Sent By alange Date 2005-12-15 Time 09:30 Rev Time 0.33
Received By alange Date 2005-12-15 Time 09:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-03 Cont ID  
Sent By btrobaug Date 2006-03-03 Time 09:47 Rev Time 0.75
Received By btrobaug Date 2006-03-03 Time 07:50 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-09 Cont ID  
Sent By btrobaug Date 2005-12-09 Time 07:54 Rev Time 0.58
Received By btrobaug Date 2005-12-09 Time 06:49 Sent To M
Notes
2005-12-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE CITY OF WEST PALM BEACH HAS
 ADOPTED A POLICY FOR GENERATORS THAT IS
 ATTACHED. THE LOAD CALCULATION MUST BE
 DERIVED FROM 220.31.
  
 2} PLEASE SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF ALL SERVICE AND GENERATOR
 EQUIPMENT SO THAT COMPLIANCE WITH
 225.31-39 CAN BE DETERMINED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-12-14 Cont ID  
Sent By jleech Date 2005-12-14 Time 12:36 Rev Time 0.25
Received By jleech Date 2005-12-14 Time 12:36 Sent To B
Notes
2005-12-14 00:00:00GAS PERMIT REQUIRED. GAS CONTRACTOR TO
 SUBMIT PLANS WITH PERMIT APPLICATION.
 ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GENERATOR INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 11:54 Sent To E
Notes
2006-02-19 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 09:36 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 09:36 Sent To E
Notes
2005-11-22 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-15 Cont ID  
Sent By alange Date 2005-12-15 Time 09:31 Rev Time 0.00
Received By alange Date 2005-11-15 Time 18:39 Sent To  
Notes
2005-11-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-12-09 Cont ID  
Sent By tgordon Date 2005-12-09 Time 09:36 Rev Time 0.20
Received By tgordon Date 2005-12-09 Time 09:36 Sent To P
Notes
2005-12-09 00:00:00*** PROVISO ***
 1) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS.
 2) DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS MUST BE ON JOB SITE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-12-14 Cont ID  
Sent By jleech Date 2005-12-14 Time 12:36 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By mmclean Date 2005-11-21 Time 15:32 Rev Time 0.00
Received By mmclean Date 2005-11-21 Time 15:32 Sent To I
Notes
2005-11-21 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO SETBACK.