Plan Review Stops For Permit 05110322 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-01-04 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-01-04 |
Time |
15:35 |
Rev Time |
1.00 |
Received By |
alange |
Date |
2006-01-04 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-12-20 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-12-20 |
Time |
16:31 |
Rev Time |
0.75 |
Received By |
alange |
Date |
2005-12-20 |
Time |
16:30 |
Sent To |
|
|
Notes |
2005-12-20 00:00:00 | DENIED | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | SHALL BE RECORDED AT PALM BEACH COUNTY | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | BLANK FORMS ARE AVAILABLE FROM THIS | | OFFICE. | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | 90 DAYS OF RECORDING. | | | | 11-7.2 SALES AND SERVICE COUNTERS, | | TELLER WINDOWS, INFORMATION COUNTERS. | | (1)IN DEPARTMENT STORES AND | | MISCELLANEOUS RETAIL STORES WHERE | | COUNTERS HAVE CASH REGISTERS AND ARE | | PROVIDED FOR SALES OR DISTRIBUTION OF | | GOODS OR SERVICES TO THE PUBLIC, AT | | LEAST ONE OF EACH TYPE SHALL HAVE A | | PORTION OF THE COUNTER WHICH IS AT LEAST | | 36 INCHES (915 MM) IN LENGTH WITH A | | MAXIMUM HEIGHT OF 36 INCHES (915 MM) | | ABOVE THE FINISH FLOOR. IT SHALL BE ON | | AN ACCESSIBLE ROUTE COMPLYING WITH | | SECTION 11-4.3 . THE ACCESSIBLE COUNTERS | | MUST BE DISPERSED THROUGHOUT THE | | BUILDING OR FACILITY. IN ALTERATIONS | | WHERE IT IS TECHNICALLY INFEASIBLE TO | | PROVIDE AN ACCESSIBLE COUNTER, AN | | AUXILIARY COUNTER MEETING THESE | | REQUIREMENTS MAY BE PROVIDED. | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-11-21 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-11-21 |
Time |
15:55 |
Rev Time |
1.50 |
Received By |
alange |
Date |
2005-11-21 |
Time |
14:16 |
Sent To |
|
|
Notes |
2005-11-21 00:00:00 | DENIED | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | SHALL BE RECORDED AT PALM BEACH COUNTY | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | BLANK FORMS ARE AVAILABLE FROM THIS | | OFFICE. | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | 90 DAYS OF RECORDING. | | | | 2.PLANS SUBMITTED AFTER OCTOBER 1, | | 2005 SHALL BE DESIGNED TO THE 2004 FBC. | | | | 3.ARE NEW BATHROOMS BEING INSTALLED? | | WHY IS PAGE A-4 SHOWN? | | | | 4.RECEPTION DESK SHALL BE DESIGNED TO | | FBC 2004 CHAPTER LL.SHOW DETAILS. | | | | 5.ARE NOTES 14 AND 15 REVERSED? | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2006-06-03 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2006-06-03 |
Time |
09:58 |
Rev Time |
0.30 |
Received By |
jleahy |
Date |
2006-06-03 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-01-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-01-03 |
Time |
06:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-01-03 |
Time |
06:05 |
Sent To |
|
|
Notes |
2006-01-03 00:00:00 | REDLINED 600.5, |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-12-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2005-12-16 |
Time |
14:16 |
Rev Time |
1.00 |
Received By |
jleahy |
Date |
2005-12-16 |
Time |
14:18 |
Sent To |
|
|
Notes |
2005-12-16 00:00:00 | DRAWING NEED TO BE SEALED BY AN | | ELECTRICAL ENGINEER SERVICE IS 480/277 | | | | IF SERVICE HAD BEEN SHOWN ON LAST REVIEW | | WE WOULD HAVE AVOIDED THIS REJECTION. | | | | JAKE | | | | 644-7291 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-11-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2005-11-20 |
Time |
16:16 |
Rev Time |
0.30 |
Received By |
jleahy |
Date |
2005-11-20 |
Time |
16:15 |
Sent To |
P |
|
Notes |
2005-11-20 00:00:00 | NEDD RISER DIAGRAM SHOW LOCATION OF | | SERVICEJLEAHY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2006-01-03 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-01-03 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-01-03 |
Time |
11:08 |
Sent To |
|
|
Notes |
2006-01-03 00:00:00 | PLANS APPROVED AND STAMPED ON 12/20/05 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2005-12-20 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2005-12-20 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2005-12-20 |
Time |
11:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2005-11-22 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-11-22 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-11-22 |
Time |
11:21 |
Sent To |
|
|
Notes |
2005-11-22 00:00:00 | ******DENIED****** | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, | | 2003 EDITION. IN ADDITION TO CHAPTER 38, | | CHAPTER 7 SHALL BE REFERENCED, NOT 5. | | | | 2) PLEASE SEE OTHER REVIEW COMMENTS | | REGARDING APPLICABLE CODE REFERENCES AND | | MAKE APPROPRIATE CHANGES. | | | | 3) CONSTRUCTION, ALTERATION AND | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM REMODEL. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2006-08-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-01 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-01 |
Time |
14:59 |
Sent To |
M |
|
Notes |
2006-08-01 00:00:00 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-07-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-07-03 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-07-03 |
Time |
10:27 |
Sent To |
M |
|
Notes |
2006-07-03 00:00:00 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-05-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-27 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-27 |
Time |
14:23 |
Sent To |
E |
|
Notes |
2006-05-27 00:00:00 | TO "JLEAHY" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-12-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-27 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-27 |
Time |
14:02 |
Sent To |
|
|
Notes |
2005-12-27 00:00:00 | TO "BOB"#6 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-12 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-12 |
Time |
11:43 |
Sent To |
|
|
Notes |
2005-12-12 00:00:00 | TO "BOB"#7 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-11-29 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-14 |
Time |
17:45 |
Sent To |
|
|
Notes |
2005-11-14 00:00:00 | TO "BOB"#4 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2006-08-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-08-04 |
Time |
14:02 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2006-08-04 |
Time |
14:02 |
Sent To |
|
|
Notes |
2006-08-04 00:00:00 | REVISION TO MECH. PLAN PAGE M-1. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-07-05 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-07-05 |
Time |
10:37 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2006-07-05 |
Time |
10:37 |
Sent To |
|
|
Notes |
2006-07-05 00:00:00 | REVISION TO MECH. PLANS PAGE M-1. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-12-19 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-12-19 |
Time |
14:21 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2005-12-19 |
Time |
14:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-11-16 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-11-16 |
Time |
07:56 |
Rev Time |
1.00 |
Received By |
prafter |
Date |
2005-11-16 |
Time |
07:56 |
Sent To |
|
|
Notes |
2005-11-16 00:00:00 | MECH. PLAN REVIEW: | | | | 1. RETURN AIR OUT OF OFFICES/CONFRENCES | | AREA REFLECT R/A THROUGH CEALING. RETURN | | AIR TO A.H.U. REFLECT SPACE RETURN. | | PLEASE CORRECT AND RESUBMIT. | | | | FLEX DUCT CONNECTION REFLECTED ON M-1 IS | | NOT CORRECT, INSULATION IS COMPRESSED | | THEAR BY LOOSING R-RATING . | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | PATTY KRAUSS. | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2005-11-29 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-11-29 |
Time |
17:02 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-11-29 |
Time |
17:02 |
Sent To |
|
|
Notes |
|
|