Plan Review Stops For Permit 05100904 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-03-30 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-03-30 |
Time |
10:10 |
Rev Time |
1.75 |
Received By |
alange |
Date |
2006-03-30 |
Time |
09:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-02-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-03-24 |
Time |
14:47 |
Rev Time |
2.50 |
Received By |
alange |
Date |
2006-02-24 |
Time |
13:35 |
Sent To |
|
|
Notes |
2006-02-24 00:00:00 | DENIED | | 1. 713.13(2) F.S.THE NOTICE OF | | COMMENCEMENT MUST BE RE-RECORDED BECAUSE | | THE DESCRIBED IMPROVEMENT OR | | CONSTRUCTION DID NOT COMMENCE WITHIN 90 | | DAYS OF RECORDING. | | | | 2.SUBMIT TWO ORIGONAL SIGNED AND | | SEALED SURVEYS. | | | | 3.ALL PLANS SUBMITTED AFTER OCTOBER 1, | | 2005 SHALL BE DESIGNED TO THE 2004 FBC. | | BUILDING CODE USED IS THE 2004 | | RESIDENTIAL CODE AND THE 2004 FBC, CODE | | REFERENCES SHOULD REFLECT THOSE CODES. | | | | 4.SUBMIT ENERGY CALCS TO THE 2004 FBC. | | | | | | 7.SUBMIT GUARD RAIL DETAILS PER | | R-312.1 NO DETAILS SUBMITTED, ONLY CODE | | SECTIONS. | | | | 8.SELECT THE ASSEMBLY USED FOR THE | | BITUMEN ROOF AND INCLUDE ONLY THE PAGES | | REQUIRED FOR THAT ASSEMBLY. | | | | NEW COMMENT: | | THOSE PRODUCT APPROVALS WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL.WPB | | AMMENDMENT TO FBC 106.3.3 | | | | ANY QUESTIONS CALL ME. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-12-23 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-12-23 |
Time |
09:54 |
Rev Time |
4.00 |
Received By |
alange |
Date |
2005-12-23 |
Time |
09:38 |
Sent To |
|
|
Notes |
2005-12-23 00:00:00 | DENIED | | 1. 713.13(2) F.S.THE NOTICE OF | | COMMENCEMENT MUST BE RE-RECORDED BECAUSE | | THE DESCRIBED IMPROVEMENT OR | | CONSTRUCTION DID NOT COMMENCE WITHIN 90 | | DAYS OF RECORDING. | | | | 2.SUBMIT TWO ORIGONAL SIGNED AND | | SEALED SURVEYS. | | | | 3.ALL PLANS SUBMITTED AFTER OCTOBER 1, | | 2005 SHALL BE DESIGNED TO THE 2004 FBC. | | | | 4.SUBMIT ENERGY CALCS TO THE 2004 FBC. | | | | 5.ENERGY CALCS DO NOT MATCH R- VALUES | | ON PLANS. | | | | 6.SUBMIT SPECS FOR HOOD AND GAS BBQ. | | A HOOD IS REQUIRED FOR BUILT IN UNITS. | | | | 7.SUBMIT GUARD RAIL DETAILS PER | | R-312.1 | | | | 8.SUBMIT PRODUCT APPROVAL FOR BITUMEN | | ROOF WITH THE FOLLOWING STATE PRODUCT | | APPROVAL ATTACHED. | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 9.PLEASE CLARIFY... IS THE ULTIMATE | | DOOR TO BE USED IN THE FRONT ENTRY? | | IF IT IS A DIFFERENT DOOR SUBMIT A | | PRODUCT APPROVAL FOR THAT PRODUCT. | | | | ANY QUESTIONS CALL ME. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-15 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-15 |
Time |
16:36 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-01 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-01 |
Time |
09:50 |
Sent To |
PC |
|
Notes |
2007-08-01 11:17:03 | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | 1} PROVIDE A PANEL SCHEDULE FOR ADDED PANEL "C". | | | | 2} PANEL "C" IS NOT ON THE RISER DIAGRAM, PLEASE ADD | | SAME. | | | | 3} THE CONDENSER LABELED AC #3 IS IN BOTH PANEL "A" AND | | "EM", AND THE LOAD IN EACH IS DIFFERENT. PLEASE CORRECT | | TO SHOW ACTUAL CONDITIONS. | | | | 4} LOCATE THE DISCONNECT FOR AC #3, 440.14. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-03-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-03-22 |
Time |
16:48 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2006-03-22 |
Time |
16:15 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-02-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-02-21 |
Time |
08:44 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2006-02-21 |
Time |
07:05 |
Sent To |
M |
|
Notes |
2006-02-21 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT THE MANUFACTURERS | | SPECIFICATIONS FOR THE GEN SET AND ALL | | RELATED EQUIPMENT. NOTE THE TRANSFER | | SWITCH MUST BE SERVICE RATED PER 225.36. | | ALL ARTICLE 225 APPLIES TO THE | | GENERATOR, AS WELL AS 445, 700 & 702. | | THIS COMMENT WAS MEDE ON THE PREVIOUS | | REVIEW. | | | | 2} THE CALCULATION FOR THE "EM" PANEL IS | | NOT PER ANY RECOGNIZED FORMULAS IN THE | | NEC. THERE IS NO CALC FOR 1WATT PER | | SQUARE FOOT. IT WAS INDICATING THAT HEAT | | WOULD NOT BE USED WITH EMERGENCY POWER. | | INDICATE HOW THE A/C WOULD BE EXCLUDED | | (LOCKED OUT) WHEN THE GENERATOR POWERS | | UP. IT WOULD APPEAR THAT WITH AN | | AUTOMATIC TRANSFER SWITCH OPERATION ALL | | BRANCH CIRCUITS IN THE "EM" PANEL WOULD | | BE ENERGIZED. SUGGEST REMOVING ALL LOADS | | FROM THAT PANEL NOT INTENDED TO BE | | ENERGIZED BY THE GEN SET. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-11-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-11-10 |
Time |
06:46 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2005-11-09 |
Time |
17:52 |
Sent To |
M |
|
Notes |
2005-11-09 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT THE MANUFACTURERS | | SPECIFICATIONS FOR THE GEN SET AND ALL | | RELATED EQUIPMENT. NOTE THE TRANSFER | | SWITCH MUST BE SERVICE RATED PER 225.36. | | ALL ARTICLE 225 APPLIES TO THE | | GENERATOR, AS WELL AS 445, 700 & 702. | | | | 2} THE FEEDER FROM THE GENERATOR MUST BE | | 115% OF THE NAMEPLATE PER 445.13. | | | | 3} THE GROUNDING ELECTRODE SYSTEM MUST | | BE ATTACHED AT THE METER OR THE FIRST | | MEANS OF DISCONNECT, IT MUST BE REMOVED | | FROM THE ATS. THE ATS SHOULD BE BONDED | | WITH THE EQUIPMENT GROUNDING CONDUCTOR, | | UNLESS THE GENERATOR IS A SEPERATLY | | DERIVED SYSTEM. | | | | 4} PLEASE PROVIDE A LOAD SUMMARY FOR THE | | EMERGENCY LOAD. | | | | 5} THE DINING ROOM RECEPTACLES MUST | | COMPLY WITH 210.52(B)(1 & 2), NO OTHER | | OUTLETS, SEE GALLERY AND FOYER. | | | | 6}THE GFI'S IN THE MASTER BATH ARE SHOWN | | ON INCORRECT CIRCUITS. ONE IS SHOWN ON | | "C 17" (NO SUCH PANEL ON THE PLAN), THE | | OTHER ON "EM 7". PLEASE SEE 210.11(C(3). | | | | 7} PLEASE SEE THE CIRCUIT FOR THE FAMILY | | ROOMEXTENDS TO A RECEPTACLE IN THE | | BREAKFAST ROOM. 210.52(B). | | | | 8} PLEASE SEE BATH GFI IN THE CABANA IS | | INDICATED ON THE POOL PUMP CIRCUIT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
N |
Date |
2006-03-30 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-03-30 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-03-30 |
Time |
10:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2006-02-22 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-02-22 |
Time |
08:05 |
Rev Time |
1.00 |
Received By |
jleech |
Date |
2006-02-22 |
Time |
08:05 |
Sent To |
B |
|
Notes |
2006-02-22 00:00:00 | DENIED; | | 1.GAS RISER DIAGRAM DOES NOT SHOW POOL | | HEATER OR GENERATOR. | | 2.NO SPECIFICATIONS WERE FOUND FOR | | INSTANT HOT. I COULD NOT FIND TOTLE | | BTU'S FOR STOVE AND DRIER FROM SPEC. | | SHEETS. | | 3.BTU'S ON RISER DIAGRAM DO NOT MATCH | | BTU'S ON SPEC. SHEETS. (MARKED IN RED ON | | ONE SET OF PLANS) | | 4.PIPE SIZES ARE NOT CORRECT, SEE | | FBC-2004 FUEL GAS TABLE 402.4(2). | | 5.OTHER PIPING MATERIAL WILL BE USED BY | | THE GAS CONTRACTOR @ PE FOR UNDER | | GROUND, CSST IN ATTIC. EACH PIPING | | MATERIAL HAS IT'S OWN TABLE. | | IF YOU DELETE THE GAS RISER FROM YOUR | | PLAN THE GAS CONTRACTOR HIRED COULD | | PROVIDE THE REQUIRED DRAWINGS WITH THE | | GAS PERMIT APPLICATION AT A LATER TIME. | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2005-11-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-11-19 |
Time |
14:39 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2005-11-19 |
Time |
14:39 |
Sent To |
B |
|
Notes |
2005-11-19 00:00:00 | GAS PLAN DENIED. | | 1.GAS PIPE SIZING IS NOT CORRECT | | FBC-2004 FUEL GAS TABLE 402.4(2) | | 2.GALV PIPE UNDER GROUND MUST BE FACTORY | | RAPPED AND CAN NOT HAVE ANY EXPOSED | | AREAS. SEC. 404.8. | | 3.PROVIDE MANUFATURE'S CUT SHEETS | | SHOWING BTU'S FOR EACH APPLIANCE. | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-14 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-14 |
Time |
16:19 |
Sent To |
M |
|
Notes |
2007-08-14 16:25:25 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-14 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-14 |
Time |
16:15 |
Sent To |
|
|
Notes |
2007-08-14 16:15:59 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-02 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-02 |
Time |
10:34 |
Sent To |
M |
|
Notes |
2007-08-02 10:35:14 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-26 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-26 |
Time |
09:43 |
Sent To |
E |
|
Notes |
2007-07-26 09:43:29 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-11 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-11 |
Time |
15:18 |
Sent To |
M |
|
Notes |
2007-07-11 15:19:17 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-02-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-01 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-01 |
Time |
11:39 |
Sent To |
B |
|
Notes |
2007-02-01 11:40:12 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-03-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-03-17 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-03-17 |
Time |
14:35 |
Sent To |
E |
|
Notes |
2006-03-17 00:00:00 | TO "BTROBAUG" DESK/RESUB--APPL. STATES | | GAS CONTRACTOR TO REAPPLY LATER. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-02-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-19 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-19 |
Time |
10:47 |
Sent To |
E |
|
Notes |
2006-02-19 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-13 |
Time |
18:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-13 |
Time |
18:02 |
Sent To |
Z |
|
Notes |
2006-02-13 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-11-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-11-09 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-09 |
Time |
10:34 |
Sent To |
E |
|
Notes |
2005-11-09 00:00:00 | TO "SFR" "E" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-12-23 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-12-23 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2005-10-19 |
Time |
09:39 |
Sent To |
|
|
Notes |
2005-10-19 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-15 |
Time |
12:13 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-08-15 |
Time |
12:13 |
Sent To |
|
|
Notes |
2007-08-15 12:14:28 | REVISION TO MECH. PLANS PAGE M-1 AND M-2. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-02 |
Time |
15:23 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-08-02 |
Time |
15:23 |
Sent To |
|
|
Notes |
2007-08-02 15:24:25 | REVISION TO MECHANICAL PLANS PAGE M-1, M-2, AND ENERGY | | CALCULATIONS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-07-13 |
Time |
09:35 |
Rev Time |
0.40 |
Received By |
tgordon |
Date |
2007-07-13 |
Time |
09:35 |
Sent To |
|
|
Notes |
2007-07-13 09:47:27 | MECHANICAL REVISION | | *** DENIED *** | | 1) EDWARD J. KRANZ (ENGINEER) SEALED THE MECHANICAL | | PLANS ON FILE SO HE NEEDS TO SEAL THE REVISION. | | | | 2) ENERGY CALCULATIONS ON FILE ARE TAKING CREDIT FOR A | | HEAT RECOVERY UNIT THE REVISED MECHANICAL PLANS HAVE | | THE HEAT RECOVERY UNIT REMOVED, PLEASE CORRECT. | | | | 3) SHOW HOW THE RETURN AIR IS GETTING BACK TO AHU 1 AND | | 3 , IF LOUVER DOOR PLEASE SHOW ON MECHANICAL PLANS. | | | | 4) THE 8X4 SUPPLY AIR GRILL FOR BATHROOM #3 IS LOCATED | | IN BEDROOM #5 NOT IN THE BATHROOM, PLEASE CORRECT. | | | | 5) PERMIT #07050292 OR 06110063 ARE FOR THE SAME JOB | | ONE WILL NEED TO BE VOIDED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-03-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-03-23 |
Time |
09:23 |
Rev Time |
1.30 |
Received By |
tgordon |
Date |
2006-03-24 |
Time |
14:46 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-02-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-02-21 |
Time |
11:58 |
Rev Time |
1.20 |
Received By |
tgordon |
Date |
2006-02-21 |
Time |
11:58 |
Sent To |
P |
|
Notes |
2006-02-21 00:00:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON | | FORM 600A-04 (2004) PER FBC 13-600.3.A . | | | | 2) AHU #1 RETURN AIR GRILL 30X14 IS TO | | SMALL FOR A 5 TON A/C UNIT. NOTE, | | KITCHEN DOOR WILL BLOCKRETURN AIR | | GRILL IF LEFT OPEN. | | | | 3) CLOTHES DRYER NEEDS TO TERMINATE AT | | LEAST 4 FEET FROM A/C CONDENSER UNIT. | | | | 4) COMBUSTION AIR INLETS TO LAUNDRY ROOM | | CAN NOT HAVE GENERATOR EXHAUST, CLOTHES | | DRYER VENT, A/C CONDENSER FAN WITHIN 10 | | FEET, PER 2004 FBC/M 401.5.1 . | | | | 5) GENERATOR EXHUST MUST BE TEN FEET | | AWAY FROM ANY BUILDING OPENINGS | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | TEN FEET AWAY FROM ADJECENT BUILDING | | OPENS. PER 2004 FBC/M 401.5.1 . | | | | 6) DUCT (FLEX) TO BEDROOM #4 IS NOT | | SIZED. | | | | 7) RETURN AIR GRILL 24X24 IS TO SMALL | | FOR A 4 TON A/C UNIT. | | | | 8) NOTE, RETURN AIR TRANSFER DUCTS. | | BALANCED RETURN AIR. | | THIS MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. | | (B)TRANSFER GRILLES SHALL USE 50 | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | CFM (OF SUPPLY AIR) FOR SIZING | | THROUGH-THE-WALL TRANSFER GRILLES AND | | USING AN UNRESTRICTED 1-INCH | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | RETURN AIR BALANCE | | (C)HABITABLE ROOMS ONLY SHALL BE | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | PROPER BALANCED RETURN AIR EXCLUDING | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | AIR INTO THE MASTER SUITE SHALL BE | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | 8) PLEASE REMOVE ALL OLD PLANS FROM PLAN | | SET. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2005-11-14 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-11-14 |
Time |
14:48 |
Rev Time |
0.35 |
Received By |
tgordon |
Date |
2005-11-14 |
Time |
14:48 |
Sent To |
P |
|
Notes |
2005-11-14 00:00:00 | MECHANICAL PERMIT NOT BEING APPLIED FOR | | AT THIS TIME. PLEASE NOTE THE FOLLOWING | | REGUARDING YOUR MECHANICAL PLANS. | | AHU #1 ( 1ST. FLOOR ) | | 1) NEED TO SHOW RETURN AIR DUCT SIZE. | | 2) TRANSFER DUCT IN STUDY MUST BE 1 1/2 | | TIMES LARGER THAN SUPPLY AIR DUCT (8" | | SUPPLY AIR DUCT REQUIRES A 10" RETURN | | AIR TRANSFER DUCT). PER 2004 FBC/R | | M1602.4 . | | 3)RAG IN MASTER VESTIBULE IS TO SMALL, | | TRANSFER GRILLS MUST BE 50 SQ. IN. PER | | 100 CFM'S (300 SQ. IN.). PER FBC/R | | M1602.4 . | | 4) COMBUSTION AIR LOUVERS, PLEASE SEE | | 2004 FBC/R M1701.5 . | | 5) WILL NEED DETAILED MANUFACTURE'S | | SPECIFICATION'S ON GAS FIREPLACE AND | | COMBUSTION AIR CALCULATIONS. | | 6) WILL NEED DETAILED MANUFACTURE'S | | SPECIFICATION'S ON GAS BBQ UNDER COVERED | | LOGGIA, OR AN APPROVED HOOD. | | 7) PLANS CALL FOR 109,400 TOTAL BTU'S | | ENERGY CALCULATIONS CALL FOR 68,000 | | BTU,S THE TO MUST COINCIDE. | | 8) PLEASE ADDRESS GENERATOR EXHUST. | | 9) WILL NEED DETAILED MANUFACTURE'S | | SPECIFICATION'S AND INSTALLATION | | INSTRUCTIONS ON GENERATOR. | | AHU #2 (2ND. FLOOR) | | 10) RAG IN BEDROOM #5 NOT SIZED. | | 11) TRANSFER DUCT IN BEDROOM #3 & 4 NEED | | TO BE 10" . | | 12) TRANSFER DUCT IN BEDROOM # 2 NOT | | SIZED. | | 13) RETURN AIR DUCT FROM 24X24 RAG TO | | AHU #2 NOT SIZED. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2005-11-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-01 |
Time |
11:22 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2005-11-19 |
Time |
14:38 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-04-16 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-04-16 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-04-16 |
Time |
14:59 |
Sent To |
PC |
|
Notes |
2008-04-16 14:59:56 | ***APPROVED - LANDSCAPE PLAN SUBMITTAL, 4/16/08*** |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-02-17 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-02-17 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-02-17 |
Time |
18:36 |
Sent To |
I |
|
Notes |
2006-02-17 00:00:00 | NOTE: THE EQUIPMENT CAN ONLY ENCROACH | | 4FT INTO A SETBACK (A/C ETC). | | | | NOTE: MUST PULL A SEPERATE PERMIT FOR | | POOL/SPA. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-11-07 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-11-07 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-11-07 |
Time |
14:17 |
Sent To |
I |
|
Notes |
2005-11-07 00:00:00 | DENIED, | | 1. TOO MUCH CONCRETE WITHIN THE FIRST | | 25FT FRONT SETBACK OF PROPERTY. | | 2. MUST MAINTAIN 1000SQ FT OR 75% OF | | LANDSCAPE WHICHEVER IS LESS WITHIN THE | | FIRST 25FT FRONT SETBACK. | | | | FRONT PROPERTY IS 1561.5SQ FT AND CAN | | ONLY HAVE 561.5SQ FT OF CONCRETE WITHIN | | THE FIRST 25FT FRONT SETBACK. | | | | | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|