Plan Review Details - Permit 05100903
Plan Review Stops For Permit 05100903
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-02-01 Cont ID  
Sent By shill Date 2007-02-01 Time 17:04 Rev Time 0.00
Received By shill Date 2007-02-01 Time 17:04 Sent To  
Notes
2007-02-01 17:04:54GARAGE DOOR PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-17 Cont ID  
Sent By alange Date 2006-08-17 Time 09:19 Rev Time 0.00
Received By alange Date 2006-08-17 Time 09:19 Sent To  
Notes
2006-08-17 00:00:00WINDOWS ADDED, REVISED S PAGES

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-01 Cont ID  
Sent By alange Date 2006-08-01 Time 15:45 Rev Time 0.75
Received By alange Date 2006-08-01 Time 15:45 Sent To  
Notes
2006-08-01 00:00:00DENIED
  
 1.ALL OF THE PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 PRODUCT APPROVAL INFORMATION ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.REVISE PERMIT VALUATION TO INCLUDE
 ALL NEW WINDOWS AND DOORS ADDED.
  
 3.SHOW SIZE OF BEDROOMM WINDOWS SO
 THAT EMERGENCY ESCAPE RESCUE OPENING
 SIZES CAN BE CHECKED.R-310
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-10 Cont ID  
Sent By alange Date 2006-07-10 Time 08:06 Rev Time 0.75
Received By alange Date 2006-07-10 Time 08:06 Sent To  
Notes
2006-07-10 00:00:00TRUSS DRAWINGS REVIEWED AND APPROVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-28 Cont ID  
Sent By alange Date 2006-02-28 Time 13:16 Rev Time 1.75
Received By alange Date 2006-02-28 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By alange Date 2005-12-15 Time 07:15 Rev Time 2.25
Received By alange Date 2005-12-15 Time 07:15 Sent To  
Notes
2005-12-15 00:00:00DENIED
  
 1.SUBMIT TWO ORIGONAL SIGN AND SEALED
 SURVEYS.FS 472.025
  
 2.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-04 Cont ID  
Sent By btrobaug Date 2006-10-04 Time 17:55 Rev Time 0.50
Received By btrobaug Date 2006-10-03 Time 07:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-22 Time 07:38 Rev Time 1.33
Received By btrobaug Date 2006-03-22 Time 06:20 Sent To PC
Notes
2006-03-22 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PREVIOUS COMMENT:
  
 1} "IF THE SUBPANEL SHOWN ON THE RISER
 IS FOR A SEPARATE STRUCTURE INDICATE
 COMPLIANCE WITH 250.32 AND 225.32."
 CLEARLY THERE IS A GUEST COTTAGE ON THE
 PROPERTY. THIS BUILDING MUST HAVE A
 DISCONNECTING MEANS AND A GROUNDING
 SYSTEM INSTALLED PER THE ABOVE NOTED
 ARTICLES. PLEASE INDICATE SAME ON THE
 PLAN. SHOW THE LOCATIION OF ALL SERVICE
 EQUIPMENT , INCLUDING THE PANELS AND
 SUBPANELS, ON THE PLAN. DESIGNATE THEM
 FOR CLARITY.
  
 2} THE GROUNDING ELECTRODE SYSTEM MUST
 ALSO BE BONDED TO BUILDING STEEL SINCE
 IT IS AVAILABLE ON THE PREMISES PER
 250.52(A)(3). PLEASE INDICATE COMPLIANCE
 ON THE RISER.
  
  
 REGARDING THE ARCHITECT OF RECORD. THE
 TITLE BLOCK MUST COMPLY WITH
 61G1-16.004, FAC. A COPY OF THE
 CERTIFICATION IS NOTED, BUT THE FAC
 STTES THAT THE AA NUMBER MUST APPEAR IN
 THE TITLE BLOCK.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-22 Cont ID  
Sent By btrobaug Date 2006-02-22 Time 13:20 Rev Time 0.50
Received By btrobaug Date 2006-02-22 Time 12:29 Sent To M
Notes
2006-02-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE THE AIC RATING OF THE SERVICE
 EQUIPMENT PER 110.9.
  
 2} PLEASE INDICATE THE OCP AND CONDUCTOR
 SIZES ON THE PANEL SCHEDULES SO THAT
 BRANCH CIRCUIT COMPLIANCE MAY BE
 REVIEWED.
  
 3} IF THE SUBPANEL SHOWN ON THE RISER IS
 FOR A SEPARATE STRUCTURE INDICATE
 COMPLIANCE WITH 250.32 AND 225.32.
  
 4} A RECEPTACLE IS REQUIRED IN THE
 FAMILY ROOM PER 210.52(A)(2). SEE
 REVIEWED PLAN FOR LOCATION.
  
 5} THERE ARE TWO PANEL #1'S ON THE
 RISER.
  
 REGARDING THE ARCHITECT OF RECORD. THE
 TITLE BLOCK MUST COMPLY WITH
 61G1-16.004, FAC. WHAT IS "DESIGN
 METHODS" ?
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By btrobaug Date 2005-12-06 Time 14:41 Rev Time 0.50
Received By btrobaug Date 2005-12-06 Time 07:43 Sent To M
Notes
2005-12-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250.66, 1/0 MINIMUM FOR
 400MCM.
  
 2} A RECEPTACLE PER 210.52(E) IS
 REQUIRED IN THE FRONT AND REAR OUTSIDE,
 AND PER 210.63 FOR THE CONDENSERS, BUT
 ONE IN THE REAR (WITHIN 25'),WILL
 SUFFICE.
  
 3} THE FANS IN THE LIVING ROOM MUST HAVE
 A LIGHT KIT OR A RECEPTACLE SWITCHED.
 210.70(A)(1).
  
 4} THE TITLE BLOCK MUST CONTAIN THE
 CORPORATE NUMBER OF THE FIRM PER
 61G1-16.003 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-02-28 Cont ID  
Sent By jleech Date 2006-02-28 Time 07:27 Rev Time 0.00
Received By jleech Date 2006-02-28 Time 07:27 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-12-10 Cont ID  
Sent By pschmitz Date 2005-12-10 Time 13:30 Rev Time 0.00
Received By pschmitz Date 2005-12-10 Time 13:30 Sent To P
Notes
2005-12-10 00:00:00PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
 DENIED
 1. SHT P-1 GAS RISER
 SHOW LOCATION OF GAS WATER HEATER.
 2.KITCHEN STOVE,PROVIDE MANFACTURE
 INFORMATION FOR RESIDENTAL USE.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. TYPE OF GAS, (LP OR NATURAL)
 5. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-09-21 Cont ID  
Sent By adarroug Date 2006-09-21 Time 08:20 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 08:20 Sent To E
Notes
2006-09-21 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-09-21 Cont ID  
Sent By adarroug Date 2006-09-21 Time 08:17 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 08:17 Sent To M
Notes
2006-09-21 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 14:59 Sent To B
Notes
2006-08-12 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 11:41 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 11:40 Sent To B
Notes
2006-07-31 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 11:55 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 11:55 Sent To B
Notes
2006-07-06 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 14:30 Sent To E
Notes
2006-03-17 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 11:18 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 11:18 Sent To E
Notes
2006-02-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 18:07 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 18:07 Sent To Z
Notes
2006-02-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 11:03 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 11:02 Sent To E
Notes
2005-12-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 11:17 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 11:17 Sent To B
Notes
2005-11-10 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-15 Cont ID  
Sent By alange Date 2005-12-15 Time 07:20 Rev Time 0.00
Received By alange Date 2005-10-19 Time 09:38 Sent To  
Notes
2005-10-19 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-28 Cont ID  
Sent By tgordon Date 2006-09-28 Time 15:39 Rev Time 0.45
Received By tgordon Date 2006-09-28 Time 15:39 Sent To  
Notes
2006-09-28 00:00:00*** PROVISO ***
 1) DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R 309.1.1 .
 2) PROVIDE COMBUSTION AIR FOR GAS WATER
 HEATER, PER 2004 FBC/R M1701.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-22 Cont ID  
Sent By tgordon Date 2006-02-22 Time 15:43 Rev Time 0.45
Received By tgordon Date 2006-02-22 Time 15:43 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By tgordon Date 2005-12-07 Time 09:39 Rev Time 0.30
Received By tgordon Date 2005-12-07 Time 09:39 Sent To P
Notes
2005-12-07 00:00:00*** DENIED ***
 1) NEED ENERGY CALCULATIONS ON THE
 ENTIRE HOUSE NOT JUST THE ADDITION ONLY.
 2) PLEASE CHECK THE SIZE OF THE RETURN
 AIR GRILL ON THE FIRST FLOOR, TWO 18X12
 GRILLS APPEAR TO BE A 148 SQUARE INCHES
 TO SMALL.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-28 Cont ID  
Sent By jleech Date 2006-02-28 Time 07:26 Rev Time 0.00
Received By jleech Date 2006-02-28 Time 07:26 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-10 Cont ID  
Sent By pschmitz Date 2005-12-10 Time 13:51 Rev Time 0.00
Received By pschmitz Date 2005-12-10 Time 13:51 Sent To B
Notes
2005-12-10 00:00:00PAUL SCHMITZ
 FBC 2001 PLUMBING CODEPLAN REVIEW
 DENIED
 1.TAB 403.1 MINIMUM PLUMBING FIXTURES.
 ONE AUTOMATIC CLOTHES WASHER CONNECTONN
 REQUIRED.
 2.SHT E-1 SERVICE CALCULATION, SHOWS AN
 ELECTRRIC WATER. PLEASE CLARIFY IF THERE
 ARE TWO WATER HEATERS, ONE ELECTRIC &
 ONE GAS WATER HEATER, AND THEY LOCATION
 OF EACH ONE
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-02-21 Cont ID  
Sent By mmclean Date 2006-02-21 Time 10:18 Rev Time 0.00
Received By mmclean Date 2006-02-21 Time 10:18 Sent To I
Notes
2006-02-21 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS/GATE WITH EASMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-11-01 Cont ID  
Sent By mmclean Date 2005-11-01 Time 14:05 Rev Time 0.00
Received By mmclean Date 2005-11-01 Time 14:05 Sent To I
Notes
2005-11-01 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF COMPLETE
 SITEPLANS, SHOWING THE ADDRESS OF THE
 PROPERTY
 2. MUST PROVIDE THE SETBACKS OF THE
 EXISTING AND NEW STRUCTURE (SIDE/FRONT
 REAR SETBACK)
 3. MUST PROVIDE THE DISTANCE OF THE
 PROPOSED ADDITION FROM THE EXISTING ONE
 STORY GUEST HOUSE.
  
 ****************************************
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 CMU RETAINING WALL WITH EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720