Plan Review Details - Permit 05100519
Plan Review Stops For Permit 05100519
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-16 Cont ID  
Sent By shill Date 2006-03-16 Time 09:25 Rev Time 0.00
Received By shill Date 2006-03-16 Time 09:25 Sent To  
Notes
2006-03-16 00:00:00REVISED A1, P1

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-01 Cont ID  
Sent By shill Date 2006-02-01 Time 10:33 Rev Time 0.50
Received By shill Date 2006-02-01 Time 10:33 Sent To  
Notes
2006-02-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)FBC11-4.21.2, SHOW SHOWER SIZE.
  
 2.)FBC11-4.21.4, TO AVOID CONFUSION IN
 THE FIELD, INDICATE THAT BLOCKING WILL
 BE REQUIRED FOR THE SHOWER WALLS FOR
 FUTURE GRAB BARS.
  
 3.)FBC11-4.16.4, GRAB BARS TO COMPLY
 WITH FBC FIGURE 11-29.THE WALL IS OVER
 18" AWAY FROM CENTERLINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-28 Cont ID  
Sent By shill Date 2005-11-28 Time 09:27 Rev Time 0.50
Received By shill Date 2005-11-28 Time 09:12 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-05 Cont ID  
Sent By shill Date 2005-11-05 Time 18:12 Rev Time 2.00
Received By shill Date 2005-11-05 Time 13:53 Sent To PC
Notes
2005-11-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE PLANS INDICATE THAT THEY WERE
 DESIGNED UNDER THE 2001 FLORIDA BUILDING
 CODE.EFFECTIVE OCTOBER 1, 2005,
 GOVERNING CODE IS FBC2004.
  
 3.)TO DETERMINE CODE COMPLIANCE,
 INDICATE LEVEL OF ALTERATION, FBC
 EXISTING BUILDING CODE, CHAPTER 3.
  
 4.)PROVIDE A BACKING DETAIL FOR THE
 ADAPTABLE BATHROOMS.SEE FBC717.5
 REGARDING COMBUSTIBLES IN CONCEALED
 SPACES.
  
 5.)SHOW FIREBLOCKING, 2-A2,
 FBC717.2.3.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-20 Cont ID  
Sent By dpalmer Date 2005-10-20 Time 16:24 Rev Time 0.33
Received By dpalmer Date 2005-10-20 Time 16:24 Sent To  
Notes
2005-10-20 00:00:00REDLINED PLANS..
  
  
 ALL EM/EXT LTS TO BE WIRED TO THE LOCAL
 LIGHTING BRANCH CIRCUIT IN AREA.
 700.12E
  
  
 PERMIT APPLICATION TO INDICATE THE SUITE
 #.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-01-24 Cont ID  
Sent By nmccray Date 2006-01-24 Time 10:18 Rev Time 0.00
Received By nmccray Date 2006-01-24 Time 10:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-28 Cont ID  
Sent By nmccray Date 2005-11-28 Time 14:33 Rev Time 0.00
Received By nmccray Date 2005-11-28 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-19 Cont ID  
Sent By nmccray Date 2005-10-19 Time 11:10 Rev Time 0.00
Received By nmccray Date 2005-10-19 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 10:55 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 10:55 Sent To  
Notes
2006-03-13 00:00:00TO "COMMM" BD#21
2006-02-16 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 14:35 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 14:35 Sent To B
Notes
2005-11-23 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-05 Cont ID  
Sent By shill Date 2005-11-05 Time 18:12 Rev Time 0.00
Received By shill Date 2005-10-14 Time 18:23 Sent To  
Notes
2005-10-14 00:00:00TO "COMM" BD#7

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-18 Cont ID  
Sent By hmoser Date 2005-10-18 Time 10:08 Rev Time 0.00
Received By hmoser Date 2005-10-18 Time 10:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-09 Cont ID  
Sent By jleech Date 2006-03-09 Time 13:00 Rev Time 0.00
Received By jleech Date 2006-03-09 Time 13:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By jleech Date 2006-01-20 Time 13:52 Rev Time 0.50
Received By jleech Date 2006-01-20 Time 13:52 Sent To  
Notes
2006-01-20 00:00:00DENIED;
 W/CTHE 18" MEASUREMENT SHOULD BE OFF
 THE SHOWER WALL. A GRAB BAR COULD NOT BE
 INSTALLED ON LAV SIDE OF W/C (NO WALL).
 THIS BATHROOM IS REQUIRED TO BE
 ADAPTABLE IF REQUIRED BY CODE PLEASE
 REVISE.
 PLEASE SHOW SIZE OF SHOWER. MUST BE MIN.
 36 X 36.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-10-15 Cont ID  
Sent By jleech Date 2005-10-15 Time 06:42 Rev Time 0.50
Received By jleech Date 2005-10-15 Time 06:42 Sent To  
Notes
***NONE***