Plan Review Details - Permit 05100453
Plan Review Stops For Permit 05100453
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By alange Date 2005-12-14 Time 07:54 Rev Time 2.33
Received By alange Date 2005-12-14 Time 07:33 Sent To  
Notes
2005-12-14 00:00:00DENIED
  
 1. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO THE 2004 FBC
  
 4.SUBMIT TWO COPIES OF ROOF PRODUCT
 APPROVALS WITH THE FOLLOWING STATE
 PRODUCT APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
2005-10-12 00:00:00OK PER F MITNER 9-27-05

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By btrobaug Date 2005-11-17 Time 14:26 Rev Time 0.50
Received By btrobaug Date 2005-11-17 Time 13:40 Sent To M
Notes
2005-11-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} THE PLAN INDICATES THE SUB PANEL IS
 FED FROM A SEPERATE BUILDING. THE
 SUBPANEL MUST BE GROUNDED PER 250.32,
 AND HAVE A MAIN BREAKER, OR A SEPERATE
 DISCONNECTING MEANS AT THE BUILDING
 SERVED PER 225.31.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 15:46 Sent To E
Notes
2005-11-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-14 Cont ID  
Sent By alange Date 2005-12-14 Time 07:54 Rev Time 0.00
Received By alange Date 2005-10-13 Time 09:04 Sent To  
Notes
2005-10-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By tgordon Date 2005-11-17 Time 14:51 Rev Time 0.30
Received By tgordon Date 2005-11-17 Time 14:52 Sent To P
Notes
2005-11-17 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS SUBMITTED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By tgordon Date 2005-11-17 Time 14:52 Rev Time 0.33
Received By jleech Date 2005-12-06 Time 14:05 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-31 Cont ID  
Sent By sgraham Date 2005-10-31 Time 15:18 Rev Time 0.00
Received By sgraham Date 2005-10-31 Time 15:18 Sent To  
Notes
***NONE***