Plan Review Details - Permit 05100347
Plan Review Stops For Permit 05100347
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-16 Cont ID  
Sent By rmcdouga Date 2005-11-16 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2005-11-16 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By rmcdouga Date 2005-10-11 Time 12:10 Rev Time 0.00
Received By rmcdouga Date 2005-10-11 Time 12:10 Sent To  
Notes
2005-10-11 00:00:00DENIED
  
 1) THE EVALUATION REPORT FOR FL#884 IS
 AN SBCCI/ICC REPORT. SUBMIT THE
 CORRESPONDING REPORT THAT IS LISTED ON
 THE STATE PRODUCT APPROVAL WEBSITE WITH
 THE CORRESPONDING COVER PAGE.
  
 2) THE FL COVER SHEET SUBMITTED FOR THE
 RUBEROID MODIFIED BITUMEN NOA IS NOT THE
 CORRECT ONE FOR NOA # 03-0501.02. THE
 FL# LISTED ON THE WEBSITE FOR THIS NOA
 IS FL617-R1 UNDER THE 2004 PRODUCT
 APPROVALS.
  
 3) CIRCLE THE APPROVED ASSEMBLY THAT
 WILL BE INSTALLED. THEY ARE LISTED IN
 THE NOA STARTING ON PAGE 9.
 NON-INSULATED WOOD DECKS START ON PAGE
 26.
  
 4)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 17:58 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 17:58 Sent To B
Notes
2005-11-15 00:00:00TO "RMCDOUGAL" DESK/RESUB