Plan Review Details - Permit 05100328
Plan Review Stops For Permit 05100328
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-10 Cont ID  
Sent By jwitmer Date 2006-04-10 Time 14:25 Rev Time 3.33
Received By jwitmer Date 2006-04-06 Time 16:34 Sent To  
Notes
2006-04-10 00:00:00BUILDING PROVISO:R317.1 TWO-FAMILY
 DWELLINGS.
 DWELLING UNITS IN TWO-FAMILY DWELLINGS
 SHALL BE SEPARATED FROM EACH OTHER BY
 WALL AND/OR FLOOR ASSEMBLIES HAVING NOT
 LESS THAN 1-HOUR FIRE-RESISTANCE RATING
 WHEN TESTED IN ACCORDANCE WITH ASTM E
 119. FIRE-RESISTANCE-RATED FLOOR-CEILING
 AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL, AND
 WALL ASSEMBLIES SHALL EXTEND TO THE
 UNDERSIDE OF THE ROOF SHEATHING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 13:36 Rev Time 1.10
Received By jwitmer Date 2006-02-07 Time 13:35 Sent To  
Notes
2006-02-07 00:00:00PERMIT: 05100328
 ADD: 1513 FLORIDA AVENUE
 CONT: CAPITAL BUILDERS OF S. FL INC.
 TEL: (561)762-2436
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 3 FROM THE PREVIOUS RVIEW
 DELS WITH THE ENERGY CALCS, NOT SIGNED
 WHO THEY WERE PREPARED BY NOR BY THE
 OWNER OR AGENT.
  
 3) COMMENT # 6 FROM THE PREVIOUS REVIEW
 DEALS WITH IDENTIFY GLAZING IN
 HAZARDOUS AREAS, R 308.4 ? WINDOW AT 2ND
 FLOOR BATHROOM IN FRONT OF TUB, SAFETY
 GLASS REQUIRED.
  
 4) PLANS INDICATE GLAZING REPLACED UNDER
  
 PERMIT# 05081102. THIS MISC PERMIT WAS
 DENIED WITH A PRE-INSPECT SUBMIT:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) GLAZED DOORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) COMMENT # 8 FROM THE PREVIOUS REVIEW
 R311.2.2 UNDER STAIR PROTECTION.
 ENCLOSED ACCESSIBLE SPACE UNDER STAIRS
 SHALL HAVE WALLS, UNDER STAIR SURFACE &
 ANY SOFFITS PROTECTED ON THE ENCLOSED
 WITH 1/2" GYPSUM BOARD.
  
 6) COMMENT# 12 FROM THE PREVIOUS REVIEW
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By jwitmer Date 2005-12-15 Time 07:24 Rev Time 2.22
Received By jwitmer Date 2005-12-15 Time 07:13 Sent To  
Notes
2005-12-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100328
 ADD: 1513 FLORIDA AVENUE
 CONT: CAPITAL BUILDERS OF S. FL INC.
 TEL: (561)762-2436
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIREDON PLANS FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 USED THE WRONG FORM, FORM IS FOR THE
 2001 CODE.
  
 4)PLANS ARE TO BE DESIGNED UNDER:
 2004 FL RESIDENTIAL CODE
 2004 EXISTING BUILING CODE
 2004 FL BUILDING CODE
 5) EXISTING BUILDING301.1 THE WORK
 PREFORMED ON AN EXISTING BUILDING SHALL
 BE UNDER THIS CHAPTERPROVIDE TO WHAT
 LEVEL, 1,2 OR 3 THE PLAN WAS DESIGNED TO
 INDICATE ON THE PLAN AND SHOW
 COMPLIANCE.
  
 5) PROVIDE THE MINIMUM LIVE LOADS FOR
 NEW FLOOR LOADS TABLE R301.5, DEFLECTION
 OF STRUCTURAL MEMBERS, TABLE R301.7.
  
 6) IDENTIFY GLAZING IN HAZARDOUS AREAS
 SEE R308.4.
  
 7) IDENTIFY THE EMERGENCY ESCAPE AND
 RESCUE OPENINGS FOR SLEEPING ROOMS,
 PROVIDE THE WINDOW TYPE AND SIZE,THE
 OPEN SQ FT VENT AREA.(R310.1)
  
 8) R311.2.2 UNDER STAIR PROTECTION.
 ENCLOSED ACCESSIBLE SPACE UNDER STAIRS
 SHALL HAVE WALLS, UNDER STAIR SURFACE&
 ANY SOFFITS PROTECTED ON THE ENCLOSED
 SIDEWITH 1/2" GGYPSUM BOARD.
  
 9) FIRST FLOOR ENTRY R311.4.3 THE
 LANDING AT AN EXTERIOR DOOR SHALL NOT BE
 MORE THAN 73/4" BELOW THE TOP OF THE
 THRESHOLD.
  
 10) PLANS MISSING SMOKE ALARMS IN
 CERTAIN BEDROOMS, R313.1.
  
 11) R313.1.1 WHEN INTERIOR ALTERATIONS,
 REPAIRS OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS THE INDIVIDUAL DWELLING UNITS
 SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIED FOR NEW DWELLING, THE
 SMOKE ALARMS SHALL BE INTERCONNECTED AND
 HARD WIRED.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-05 Cont ID  
Sent By dpalmer Date 2006-04-05 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2006-04-05 Time 15:28 Sent To  
Notes
2006-04-05 00:00:00******** PLANS REDLINED *********
  
 1) NOTE: PLEASE SEE A "J" BOX IS BEING
 SHOWN IN STAIR CASE EGRESS AREA, PLEASE
 SEE A LT FIXTURE WILL BE REQUIED, NO
 EXCEPTIONS. 210.70, LS101 7.8
  
 2) NOTE: PLEASE SEE FAN/LT "J" BOX IS
 BEING SHOWN IN BEDRMS, HOWEVER EITHER A
 SWITCHED RECEPT IS TO BE ADDED OT THE
 FAN/LT WILL BE REQUIRED, NOT JUST A
 "J-BOX". 210.70,LS101 7.8
  
 3) NOTE: PLEASE SEE SWITCHES AR 2ND FLR
 FOR STAIR LIGHTING WILL BE REQUIRED TO
 BE LOCATED IN CLOSE PROXIMITY TO THE
 EGRESS OF STAIRS IN THE AREA AT THE TOP
 OF STAIRS.
  
 ** PLEASE KNOW, ALL OF THE ABOVE ITEMS
 WERE REDLINED ON PLANS AND DO NOT NEED
 TO BE CORRECTED AT THIS TIME. IF PLANS
 COME BACK FOR ANY OTHER COMMENTS, THESE
 CAN BE REVISED OR THEY WILL BE REQUIRED
 TO BE REVISED AND SUBMITTED BEFORE ROUGH
 ELECTRICAL INSPECTION SHOWING LT
 FIXTURES OF SOME SORT.
 THIS WAS ON PREVIOUS REVIEW AND THE ONLY
 ITEM WHICH WAS DELETED IN MEETING WAS
 NOT TO PORVIDE BATTERY BACK UP AND THE
 10 FT CANDLES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 07:26 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 07:10 Sent To  
Notes
2006-01-30 00:00:00************** UNSAT 2ND REVIEW *******
  
  
 ** PLEASE SEE MANY NOTESFROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES DUE TO CHANGES
 IN PLANS.
  
  
 1) NOTE: NOTE # 1 OK.
  
 2) NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE LOCATIONS
 REDLINED ON PLANS.
  
 ** PLEASE SEE 210.52D, WHICH
 REQUIRES THE GFI RECEPTS WITHIN 3' OF
 SINK'S EGDE. PLEASE SEE MISSING ON
 REDLINED PLANS.PLEASE ALSO SEE THESE MAY
 NOT PLACED AS TOCROSS OVER SINK TO GET
 TO RECEPT.
 PLEASE EITHER ADD ONE OR MOVE EXISTING
 SHOWN.
 PLEASE ALSO INDICATE ALL AS GFI. 210.8A1
  
 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S
 WERE ADDED, HOWEVER, PLEASE SEE SD
 MISSING AT THE TOP OF STATIRWAY AND ON
 LOWER LEVEL.
  
 **SMOKE DETECTORS ARE REQUIRED INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: NFPA-72 11.5.1.1
  
 5) NOTE: NOTE #5 NO, PLEASE SEE MANY
 MISSING.
  
 ** PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE REDLINED PLANS FOR MANY
 MISSING.
  
 6 ) NOTE: NOTE #6 NO.
  
 ** PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 7)NOTE: NOTE #7 OK, HOWEVER PLEASE SEE
 DISC'S NOW SHOWN FOR CU'S DO NOT MEET
 110.26
  
 8 )NOTE: NOTE #8 NO.
  
 ** PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MANY MISSING, PLEASE ALSO SEE
 WHAT APPEARS TO BE ISLAND SHOWS A
 J-BOX??
  
 9)NOTE: NOTE #9 NO,PLEASE SEE THE
 FOLLOWING COMMENTS FOR LIGHTING
 REQUIRED.
  
 ** PLEASE SEE J-BOXES ARE SHOWN IN
 MANY ROOMS, HOWEVER, PLEASE INDICATE IF
 THESE ARE GOING TO BE "FAN" J-BOXES.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE ROOMS
 AND AREAS ARE SHOWN WITH J-BOXES ,
 HOWEVER LT FIXTURES OF SOME SORT WILL BE
 REQUIRED. PLEASE SEE LS 101 7.8.1.3
 WHICH REQUIRES A MIN OF 10FT CANDLES
 DURING NORMAL POWER AND PLEASE SEE
 7.9.1.3 WHICH REQUIRES AN EM FIXTURE TO
 PROVIDE A MIN OF 1FT CANDLE OF LT TO THE
 PUBLIC RIGHT OF WAY.
  
 ** PLEASE SEE MISSING EGRESS LIGHTING AT
 FIRST FLR APT PLANS, APPEARS TO BE SHOWN
 ON 2ND FLR?
 PLEASE ALSO SEE EGRESS CONTROL REQUIRED
 ON MULTI-LEVELS/LANDING.
 210.70
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE # 13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK/ NO, PLEASE SEE
 THESE WERE ADDED , HOWEVER PLEASE SEE
 EQUIPMENT GROUNDING CONDUCTORS ARE NOW
 SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE THESE ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.250.6
  
 ** PLEASE INCLUDE ALL EQUIPMENT
 GROUNDING CONDUCTORS WHERE REQUIRED.
 250.110,250.122, 250.24
  
 16)NOTE: NOTE #16 NO, PLEASE SEE A SIZE
 WAS ADDED FOR GUTTER, HOWEVER PLEASE SEE
 THIS AS BEING SHOWN 8"X 8" AND BY 4"??
  
 **PLEASE INDICATE THE MIN SIZE OF
 GUTTER PER 366
  
 17)NOTE: NOTE #17 OK, HOWEVER PLEASE SEE
 AN ADDITIONAL GRND ROD WILL BE REQUIRED.
  
  
 **PLEASE SEE 250.66 FOR MIN SIZE
 OF THE GROUNDING ELECTRODE CONDUCTOR.
  
 18)NOTE:NOTE #18 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE WATER HEATER ON FIRST
 FLR IS BEING SHOWN WITH A RECEPT FOR THE
 CONNECTION. PLEASE SEE422.31 WHICH
 REQUIRES A DISCONNECT.
  
 2)NOTE: PLEASE SEE DRYER DOES NOT
 INDICATE ANY RECEPT?
 215.5
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT CODE
 COMMENTS 3 OR MORE TIMES.
 PLEASE SEE THIS IS ONLY ATTACHED THIS
 TIME AS A NOTICE.
  
  
 *** PLEASE SEE MOST OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS OF PLANS
 FOR NOTES ABOVE.
  
 **PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 PLANS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-18 Cont ID  
Sent By dpalmer Date 2005-10-18 Time 11:12 Rev Time 2.00
Received By dpalmer Date 2005-10-18 Time 10:51 Sent To P
Notes
2005-10-18 00:00:00************ UNSAT *************
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 2) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12.
  
 3)NOTE: PLEASE SEE 210.52D, WHICH
 REQUIRE STHE GFI RECEPT PLEASE SEE
 MISSING ON REDLINED PLANS.PLEASE ALSO
 SEE THESE MAY NOT PLACED AS TOCROSS
 OVER SINK TO GET TO RECEPT.
 PLEASE EITHER ADD ONE OR MOVE EXISTING
 SHOWN.
 PLEASE ALSO INDICATE ALL AS GFI. 210.8A1
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: NFPA-72 11.5.1.1
  
 5) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE REDLINED PLANS FOR MANY
 MISSING.
  
 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 7)NOTE: PLEASE SEE PLANS ARE MISSING THE
 LOCATION OF CU'S ALONG WITH MISSING
 DISC;S PER 440.11 AND GFI'S PER
 210.8,210.63
  
 8 )NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MANY MISSING, PLEASE ALSO SEE
 WHAT APPEARS TO BE ISLAND SHOWS A
 J-BOX??
  
 9)NOTE: PLEASE SEE J-BOXES ARE SHOWN IN
 MANY ROOMS, HOWEVER, PLEASE INDICATE IF
 THESE ARE GOING TO BE "FAN" J-BOXES.
  
 10)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING AT FIRST FLR APT PLANS, APPEARS
 TO BE SHOWN ON 2ND FLR?
 PLEASE ALSO SEE EGRESS CONTROL REQUIRED
 ON MULTI-LEVELS/LANDING.
 210.70
  
 11)NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE 2002 NEC 210.12, WHICH
 REQUIRES ARC FAULT FOR ALL OUTLETS IN
 BEDRMS.
  
 12)NOTE: PLEASE SIZE SERVICE ENT
 CONDUCTORS FOR SERVICE AND LOAD
 PROVIDED.240.4 SEC'S ARE NOT LARGE
 ENOUGH.
  
 13)NOTE: PLEASE SEE PANELS ARE BEING
 SHOWN AS 150A WITH 158 LOAD, AND BEING
 FED FROM A 125A DISC?????
 PLEASE CORRELATE ALL TO MIN REQUIRED BY
 CODE.
 PLEASE ALSO SEE #4'S SHOWN FROM GUTTER
 TO MAINS. THESE ARE ONLY REATED FOR
 85A'S??
 240.4,310.16, 215.5, 90.7 ETC.
  
 14)NOTE: PLEASE INDICATE WHAT APPEARS TO
 BE ADDITIONAL DISCONNECT SON RISER
 DIAGRAM?? THESE ITEMS ARE NOT LABELED.
  
 15)NOTE: PLEASE INCLUDE ALL EQUIPMENT
 GROUNDING CONDUCTORS WHERE REQUIRED.
 250.110,250.122, 250.24
  
 16)NOTE: PLEASE INDICATE THE MIN SIZE OF
 GUTTER PER 366
  
 17)NOTE: PLEASE SEE 250.66 FOR MIN SIZE
 OF THE GROUNDING ELECTRODE CONDUCTOR.
  
 18)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS.
  
 215.5
  
 **PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 PLANS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2005-12-14 Cont ID  
Sent By mwennerg Date 2005-12-14 Time 15:58 Rev Time 0.00
Received By mwennerg Date 2005-12-14 Time 15:58 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 16:38 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 16:38 Sent To M
Notes
2006-09-23 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 14:36 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 14:36 Sent To M
Notes
2006-09-08 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 18:35 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 18:35 Sent To M
Notes
2006-08-17 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 15:21 Sent To  
Notes
2006-04-05 00:00:00TO "COMM" BD#49
2006-03-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 15:58 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 15:58 Sent To  
Notes
2006-01-26 00:00:00TO "COMM" BD#61
2005-12-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-19 Cont ID  
Sent By mmclean Date 2005-12-19 Time 17:32 Rev Time 0.00
Received By mmclean Date 2005-10-17 Time 15:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 13:36 Rev Time 0.30
Received By tgordon Date 2006-10-02 Time 13:36 Sent To  
Notes
2006-10-02 00:00:00** MECHANICAL REVISION TO PAGE M-1 **
 *** DENIED ***
 1) SEE 12X12 RETURN AIR TRANSFER GRILLS
 GO TO WATER HEATER CLOSET, NOT AIR
 HANDLER CLOSET, PLEASE CORRECT.
  
 2) PLEASE PROVIDE RETURN AIR FOR THE
 LIVING ROOM AND KITCHEN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 14:06 Rev Time 0.20
Received By tgordon Date 2006-09-12 Time 14:06 Sent To  
Notes
2006-09-12 00:00:00MECH/REV. TO PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-08-18 Cont ID  
Sent By tgordon Date 2006-08-18 Time 08:19 Rev Time 0.30
Received By tgordon Date 2006-08-18 Time 08:19 Sent To  
Notes
2006-08-18 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) MECHANICAL PLANS ON FILE WERE DONE BY
 A ENGINEER (THOMAS TWOMEY) AND SEALED SO
 ONLY HE CAN MAKE REVISIONS TO THEM.
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-04-12 Cont ID  
Sent By pkrauss Date 2006-04-12 Time 11:39 Rev Time 0.00
Received By pkrauss Date 2006-04-12 Time 11:39 Sent To  
Notes
2006-04-12 00:00:00PLANS APPROVED BY HAROLD MOSER ON
 1/25/06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-25 Cont ID  
Sent By hmoser Date 2006-01-25 Time 17:57 Rev Time 0.00
Received By hmoser Date 2006-01-25 Time 17:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-30 Cont ID  
Sent By tgordon Date 2005-11-30 Time 16:37 Rev Time 0.30
Received By tgordon Date 2005-11-30 Time 16:37 Sent To FIRE
Notes
2005-11-30 00:00:00*** DENIED ***
 1) 1ST. FLOOR SUPPLY AIR DUCT TO BOLTH
 BATHROOMS ARE NOT SIZED.
 2) 1ST. FLOOR SUPPLY AIR DUCT TO KITCHEN
 NOT SIZED.
 3) 1ST. FLOOR NO RETURN AIR IN LIVING
 AREA.
 4) 2ND. FLOOR MASTER BATHROOM SUPPLY AIR
 DUCT AND GRILL NOT SIZED AND ON CFM'S..
 5) 2ND. FLOOR NO RETURN AIR TO MAIN
 LIVING AREA.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-11 Cont ID  
Sent By jleech Date 2006-04-11 Time 09:49 Rev Time 0.00
Received By jleech Date 2006-04-11 Time 09:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-04 Cont ID  
Sent By pschmitz Date 2006-02-04 Time 13:00 Rev Time 0.00
Received By pschmitz Date 2006-02-04 Time 14:05 Sent To  
Notes
2006-02-04 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2001
 \DENIED 2ND TIME
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PREVIOUS PLAN REVIEW NOTES BY JOHN LEECH
 DATED 11-30-05 NOT ADDRESSED.
 DENIED;
 1.SHOW WATER RISER DIAGRAM, SIZE ALL
 PIPES.
 2.IF BOTH APTS. ON SAME WATER SERVICE A
 BACKFLOW PROVENTOR IS REQUIRED, IF NOT
 2ND FLOOR APT. NEEDS A WATER HEATER.
 3.SHOW DIAMETER OF WATER HEATER AND THE
 OPENING. MUST BE ABLE TO REMOVE W/H FOR
 REPLACEMENT.
 4.SANITARY RISER DIAGRAM NOT TO CODE.
 (MARKED IN RED)
 A.WET VENT SIZE SEE TABLE 909.3
 B.W/M MUST BE DOWN STREAM OF BATH-
 ROOM GROUP SEC.909.1
 C. CLEANOUT ON W/M STACK TO BE
 48" AFF.
 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR
 USES? SEE TABLE 403.1(7)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
 ADDITIONAL COMMENTS
 1) PERMIT APPLICATION.DISCRIPTION OF
 WORK, AND PLANS SUBMITTED APTS #1,2
 SHOULD INCLUDE BUILDING #1 ON THE
 APPLICATION.
 2)ENERGY CALCULATIONS SUBMITTED ARE FOR
 SIX UNITS,THREE BUILDINGS. PLEASE
 CLARIFY.OR REMOVE FROM SUBMITTED PLANS.
 3)VOIDED SHT.M-2, WAS REMOVED FROM RED
 LINED PACKAGE. THIS IS REFERENCED IN
 NOTE (4) PREVIOUS COMMENTS.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-30 Cont ID  
Sent By jleech Date 2005-11-30 Time 11:46 Rev Time 1.00
Received By jleech Date 2005-11-30 Time 11:46 Sent To M
Notes
2005-11-30 00:00:00DENIED;
 1.SHOW WATER RISER DIAGRAM, SIZE ALL
 PIPES.
 2.IF BOTH APTS. ON SAME WATER SERVICE A
 BACKFLOW PROVENTOR IS REQUIRED, IF NOT
 2ND FLOOR APT. NEEDS A WATER HEATER.
 3.SHOW DIAMETER OF WATER HEATER AND THE
 OPENING. MUST BE ABLE TO REMOVE W/H FOR
 REPLACEMENT.
 4.SANITARY RISER DIAGRAM NOT TO CODE.
 (MARKED IN RED)
 A.WET VENT SIZE SEE TABLE 909.3
 B.W/M MUST BE DOWN STREAM OF BATH-
 ROOM GROUP SEC.909.1
 C. CLEANOUT ON W/M STACK TO BE
 48" AFF.
 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR
 USES? SEE TABLE 403.1(7)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved