Plan Review Details - Permit 05100239
Plan Review Stops For Permit 05100239
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 13:59 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 13:59 Sent To M
Notes
2005-11-15 00:00:00TO "TGORDON" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 08:39 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 08:39 Sent To M
Notes
2005-10-07 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-15 Cont ID  
Sent By tgordon Date 2005-11-15 Time 15:41 Rev Time 0.25
Received By tgordon Date 2005-11-15 Time 15:41 Sent To  
Notes
2005-11-15 00:00:00*** PROVISO ***
 1) MASTER BEDROOM WILL REQUIRE A 155 SQ.
 IN. RETURN AIR TRANSFER GRILL. PER 2004
 FBC/R M1602.4 .T. GORDON

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-13 Cont ID  
Sent By tgordon Date 2005-10-13 Time 13:58 Rev Time 0.25
Received By tgordon Date 2005-10-13 Time 13:58 Sent To  
Notes
2005-10-13 00:00:00*** DENIED ***
 1) RETURN AIR IS REQUIRED IN BEDROOMS,
 YOU MAY ACHIEVE THIS BY TRANSFER GRILLS
 IN WALLS OR DOORS. PER 2004 FBC/R
 M1602.4 .
 2) DRAIN LINES NOT SHOWING ON PLANS. PER
 FBC/R M1411.3 .
 3) PLANS ARE CALLING FOR A 34,000 BTU
 A/C SYSTEM AND MANUAL 'J' IS CALLING FOR
 21,119 BTU'S OF COOLING THE TWO MUST
 COINCIED.
 4) PLEASE SHOW ON PLANS WHERE DOORS AND
 OPENINGS IN WALLS ARE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.