Plan Review Details - Permit 05100222
Plan Review Stops For Permit 05100222
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-09 Cont ID  
Sent By alange Date 2006-03-09 Time 07:37 Rev Time 0.00
Received By alange Date 2006-03-09 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 13:11 Rev Time 0.50
Received By alange Date 2005-12-05 Time 13:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-14 Cont ID  
Sent By dpalmer Date 2006-03-14 Time 07:33 Rev Time 0.00
Received By dpalmer Date 2006-03-14 Time 07:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 19:36 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 18:44 Sent To B
Notes
2006-03-01 00:00:00********** UNSAT 3RD REVIEW **********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS TWO REVIEWS.
  
  
  
 1)NOTE: NOTE #1 OK
  
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE:NOTE #3 OK/ NO, PLEASE SEE ONLY
 ONE SHEET WAS REVISED AND 2ND FLR PLANS
 ARE THE SAME PLANS FROM PREVIOUS REVIEW.
  
 **PLEASE VERIFY LOCATION OF
 PANELS, BOTH APT UNITS DOWN STAIRS SHOWS
 PANELS INSIDE UNITS, HOWEVER UPSTAIRS
 UNITS DO NOT INDICATE PANELS?
 PLEASE SEE 240.24 FOR LOCATION OF
 ACCESSIBILITY TO OCCUPANTS FOR OCP>.
 215.5
 PLEASE ALSO SHOW LOCATION OF SERVICE ON
 PLANS AS AN ELECTRICAL ROOM IS SHOWN,
 HOWEVER SERVICE IS NOT SHOWN.?
 215.5
  
 4)NOTE:NOTE #4 NO, PLEASE SEE RECEPTS DO
 NOT MEET 210.52C1.
 PLEASE SEE DISPOSAL IS STILL BEING SHOWN
 AS GFI?
  
 ** PLEASE SEE PLANS ONLY INDICATE
 THE DIPOSAL AND DISHWASHER. BOTH OF
 THESE ARE SHOWN AS GFI? PLEASE SEE NO
 APPLIANCE GFI RECEPTS ARE SHOWN, YET
 THESE ARE REQUIRED. 210.52C1, 210.8A6
  
 5)NOTE: NOTE #5 NO, PANEL SCHEDULE NOW
 INDICATES A ARC FAULT CIRCUIT, YET THIS
 IS SHOWING ALL DEVICES IN BOTH BEDRMS,
 LTS, SD'SRECEPTS ONLY ONE ONE CIRCUIT?
 PLEASE SEE PREVIOUS PANEL SCHEDULE AND
 THIS PANEL SCHEDULE INDICATES MORE THAN
 5 GEN LT CIRCUITS??
  
 **PLEASE SEE PLANS INDICATE ARC
 FAULT BEING ADDED TO BEDRMS, HOWEVER
 PANEL SCHEDULE DOES NOT SHOW THIS?
 PLEASE KNOW, RECEPTS DO NOT COME AS
 BEING ARC FAULT TYPE AS GFI'S ARE. THE
 ONLY ARC FAULT PROTECTION AT THIS TIME
 IS THE BRANCH BRKR.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8, OK, THIS SHALL BE FEILD
 VERIFIED.
  
  
 9)NOTE:NOTE #9 NO,PLEASE SEE NOT ALL
 NEW PLANS WERE SUBMITTED. PLEASE ALSO
 SEE THE SET OF OLD/VOIDED SHEETS
 SUBMITTED FOR REFERENCE ARE FROM ANOTHER
 PERMIT AND NOT THIS PROJECT.
 ** PLEASE KNOW, IF ALL COMMENTS ARE NOT
 ADDRESSED A 4X FEE WILL BE ACCESSED.
  
 ****PLEASE SEE 553.80(2)(B) IN
 FLORIDA STATUES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 NEW NOTE:
  
 1)NOTE: PLEASE ADJUST NOTE ON PLANS WITH
 RESPECT TO SCOPE OF WORK AND WHAT
 DEVICES ARE BEING REPLACED AND WHAT
 AREAS ARE BEING REMODELED/RE-WIRED.
 PLEASE SEE KITCHEN AREA SHALL MEET ALL
 CURRENTS CODES AS THIS ARE IS BEING
 REPLACED WITH NEW CABINETS.
 PLEASE SEE CENTRAL AIR IS BEING ADDED ,
 IF CEILINGS ARE BEING OPENED, THEN A 20A
 CIRCUIT WILL BE REQUIRED FOR BATHRM
 (210.11C3 AND RECEPT SPACING ON TWO
 INNER WALLS WILL REQUIRE SPACING PER
 210.52.
  
 2)NOTE: PLEASE SEE PLANS ARE BEING SENT
 TO BLDG AS ENERGY CALCULATIONS SUBMITTED
 BACK WITH PLANS ARE NOT COMPLETE, NOT
 FILLED OUT COMPLETELY, SIGNED, DATED
 ETC.
 IF THERE ARE CALCS WHICH WERE DONE
 CORRECTLY AND STAMPED ON PREVIOUS
 REVIEW, PLEASE BRING THOSE BACK IN TO
 THE BLDG REVIEWER ASAP.
  
  
 **PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 09:16 Sent To PC
Notes
2006-01-30 00:00:00******** UNSAT 2ND REVIEW *********
  
 1)NOTE: PLEASE SEE 310.16, 240.4,240.6
 FOR MIN SEC'S TO BE SHOWN. PLEASE SEE
 310.16, 400 MCM IS RATED FOR 335A'S,
 NEXT SIZE OCP PER 240.6, 350A'S. PLEASE
 SEE LOADS EXCEED THIS.
 (500MCM MIN).
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR
 SERVICE. THI SHOWS ALL 4 TYPICAL PANELS
 AT 88A'S, HOWEVER TOTAL FOR ALL FORU
 UNITS IS SHOWN AS 88A'S ALSO??
 310.16,215.5 ETC
  
 3)NOTE: PLEASE VERIFY LOCATION OF
 PANELS, BOTH APT UNITS DOWN STAIRS SHOWS
 PANELS INSIDE UNITS, HOWEVER UPSTAIRS
 UNITS DO NOT INDICATE PANELS?
 PLEASE SEE 240.24 FOR LOCATION OF
 ACCESSIBILITY TO OCCUPANTS FOR OCP>.
 215.5
 PLEASE ALSO SHOW LOCATION OF SERVICE ON
 PLANS AS AN ELECTRICAL ROOM IS SHOWN,
 HOWEVER SERVICE IS NOT SHOWN.?
 215.5
  
 4)NOTE: PLEASE SEE PLANS ONLY INDICATE
 THE DIPOSAL AND DISHWASHER. BOTH OF
 THESE ARE SHOWN AS GFI? PLEASE SEE NO
 APPLIANCE GFI RECEPTS ARE SHOWN, YET
 THESE ARE REQUIRED. 210.52C1, 210.8A6
  
 5)NOTE: PLEASE SEE PLANS INDICATE ARC
 FAULT BEING ADDED TO BEDRMS, HOWEVER
 PANEL SCHEDULE DOES NOT SHOW THIS?
 PLEASE KNOW, RECEPTS DO NOT COME AS
 BEING ARC FAULT TYPE AS GFI'S ARE. THE
 ONLY ARC FAULT PROTECTION AT THSITIME IS
 THE BRANCH BRKR.
  
 6)NOTE: PLEASE SEE MISSING RECEPTS FOR
 CU'S BEING ADDED. 210.63
 PLEASE SEE ONLY TWO CU'S ARE SHOWN?
  
 7)NOTE: PLEASE SEE PLANS AND MECHANICAL
 PLANS SHOWS AHU'S WITH 5KW HEAT STRIPS,
 HOWEVER PLEASE SEE PLANS, PANEL
 SCHEDULE, LOAD CALCUALTIONS ETC DO NOT
 SHOW ANY HEAT LOADS. PLEASE ADJUST ALL .
 PLEASE ALSO SEE SIZE OF SERVICE MAY BE
 AFFECTED.
  
 8)NOTE: PLEASE VERIFY THE LOCATION OF
 WATER HEATER AS DISCONNECTING MEANS AND
 ACCESSIBILITY MAY BE AN ISSUE ION THE
 LOCATION SHOWN.
  
 9)NOTE: PLEASE SEE 553.80(2)(B) IN
 FLORIDA STATUES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 **PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By dpalmer Date 2005-11-17 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2005-11-17 Time 18:50 Sent To  
Notes
2005-11-17 00:00:00**** UNSAT ******
  
 1)NOTE: PLEASE SUBMIT MIN PLANS FOR 2002
 NEC CODE COMPLIANCE.
  
 PLEASE SEE:
 210.52 FOR RECEPTS,
 210.52C1, 210.8A6 FOR KITCHEN RECEPTS
 210.52D,210.11C3, 210.8A FOR BATH RMS.
 310.16 MIN CONDUCTORS FOR SERVICE, PANEL
 CHANGE.
 110.9 AIC RATINGS
 440.11 DISCONNECTS
 210.63 GFI(S)
 215.5 PANEL SCHEDULE MIN CIRCUITS.
 21012 ARC FAULT.
 215.5 RISER DIAGRAM
 250.50
 ETC
  
 PLEASE ALSO SEE THAT THERE IS NOT ENOUGH
 INFORMATION FOR REVIEW OF CODE COMPIANCE
 OF PANEL CHANGE OUT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 13:08 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 13:00 Sent To  
Notes
2005-11-10 00:00:001. PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED. TYPE 2A 10BC PORTABLE FIRE
 EXTINGUISHERS ARE REQUIRED.
  
 2. BUILDING ADDRESS IS REQUIRED ON THE
 PROPER ELEVATION. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 3. ENSURE THAT EXISTING STAIR AND
 HANDRAILS ARE IN GOOD CONDITION.
  
 4. INTERIOR FINISH FOR WALLS AND
 CEILINGS SHALL COMPLY WITH BUILDING AND
 FIRE CODE REQUIREMENTS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 15:35 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 15:35 Sent To E
Notes
2006-03-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 14:10 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 14:10 Sent To E
Notes
2006-02-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 15:59 Sent To  
Notes
2006-01-26 00:00:00TO "COMM" BD#61
2005-12-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-12-14 Time   Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 11:49 Sent To  
Notes
2005-10-20 00:00:00TO "COMM" BD#29
2005-10-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By hmoser Date 2006-01-23 Time 18:45 Rev Time 0.00
Received By hmoser Date 2006-01-23 Time 18:45 Sent To  
Notes
2006-01-23 00:00:00PASS PRIVISO
 1) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 2) PLEASE REFER TO SECTION 402.3.1
 BATHROOM EXHAUEST EXCEPTION 3 SQ.FT.
 OPEN WINDOW.
 3) PLEASE REFER TO SECTION 602.2.1
 MATERIALS EXPOSED WITHIN PLENUMS.
 SHALL BE NONCOMBUSTIBLE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-13 Cont ID  
Sent By hmoser Date 2005-11-13 Time 21:01 Rev Time 0.00
Received By hmoser Date 2005-11-13 Time 21:01 Sent To  
Notes
2005-11-13 00:00:00PLAN DENIED
 1) PLEASE SHOW TERMINATION OF BATHROOM
 EXHAUST DUCTON MECHANICAL PLANS.
 2) PLEASE REFER TO SECTION 601.4 2004
 FBC(M)BALANCED RETURN AIR.
 3) PLEASE SHOW TERMINATION OF CONDENSATE
 LINE ON MECHANICAL PLANS.
 4) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.2004 FBC(M)
 5) EQUIPMENT ON PLANS AND ANERGY
 CALCULATIONS DO NOT MATCH.(SEER)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-12-14 Cont ID  
Sent By dpalmer Date 2005-12-14 Time 12:05 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-12-14 00:00:00NO PLUMB WORK SHOWN ON PLANS, NO
 CONTRACTOR SIGNED ON.