Plan Review Details - Permit 05100090
Plan Review Stops For Permit 05100090
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-05 Cont ID  
Sent By alange Date 2006-01-05 Time 08:27 Rev Time 1.25
Received By alange Date 2006-01-05 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By alange Date 2005-10-06 Time 07:38 Rev Time 1.50
Received By alange Date 2005-10-06 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-06 Cont ID  
Sent By dpalmer Date 2006-01-06 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2006-01-06 Time 08:15 Sent To  
Notes
2006-01-06 00:00:00ARCHITECT'S LTR INFILE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By dpalmer Date 2005-10-06 Time 20:16 Rev Time 0.50
Received By dpalmer Date 2005-10-06 Time 19:58 Sent To  
Notes
2005-10-06 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS ARE MISSING
 REQUIRED TITLE BLOCK AND REQUIRED
 INFORMATION ON TITLE BLOCK AS SET FORTH
 UNDER FAC 61G1-16.004.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SPECIFYNEW OCCUPANCY
 AND USE. PLANS CALL FOR NEW ACTIVITY
 ROOMS YET UNCLEAR WHAT USAGE WILL BE.
  
 3)NOTE: PLEASE SEE PLANS MENTION NEW
 LIGHTING, HOWEVER NO INFORMATION FOR
 FIXTURES, LAYOUT ETC IS SHOWN?
  
 4)NOTE: PLEASE SEE CIRCUITING ON PLANS
 IS TO CORRELATE AND BE IDENTIFIED TO
 PANEL IN WHICH CIRCUIT IS TO BE RUN TO.
 215.5
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
 PLEASE BE SURE ALL EXISTING AS SHOWN IS
 CIRCUITED TO THE LOCAL BRANCH CIRTCUIT
 IN AREA.
  
 5)NOTE: PLEASE SEE PLANS APPEAR TO BE
 SIGNED WITH INITIALS? IF INDEED THIS IS
 THE LEGAL SIGNATURE, PLEASE PROVIDE A
 SIGNED, DATED AND SEALED, NOTORIZED
 LETTER FOR VERIFICATION OF THIS AS LEGAL
 SIGNATURE. PLEASE BE SURE LETTER IS
 PRPOERLY NOTORIZED AS REQUIRED UNDER FS
 117.05
 THIS WILL BE PLACED IN SIGNATURE FILE
 FOR FUTURE REFERENCE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-05 Cont ID  
Sent By nmccray Date 2006-01-05 Time 10:17 Rev Time 0.00
Received By nmccray Date 2006-01-05 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By nmccray Date 2005-10-06 Time 11:16 Rev Time 0.00
Received By nmccray Date 2005-10-06 Time 11:09 Sent To  
Notes
2005-10-06 00:00:00PROVISO:
  
 1) SHALL COMPLY WITH NFPA 241
 DEMOLITION, RENOVATION, AND
 CONSTRUCTION.
  
 2) INTERIOR WALLS AND CEILINGS FINISH
 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN EXIT ACCESS CORRRIDORS.
  
 3) INTERIOR WALLS AND CEILINGS FINISH
 SHALL BE CLASS A, CLASS B, OR CLASS C IN
 ALL OTHER AREAS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-03 Cont ID  
Sent By adarroug Date 2006-01-03 Time 11:56 Rev Time 0.00
Received By adarroug Date 2006-01-03 Time 11:56 Sent To  
Notes
2006-01-03 00:00:00TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-03 Cont ID  
Sent By adarroug Date 2005-10-07 Time 12:00 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 14:44 Sent To  
Notes
2005-10-04 00:00:00TO "BOB"#11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-03 Cont ID  
Sent By tgordon Date 2006-01-03 Time 13:42 Rev Time 0.30
Received By tgordon Date 2006-01-03 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-07 Cont ID  
Sent By prafter Date 2005-10-07 Time 09:25 Rev Time 1.00
Received By prafter Date 2005-10-07 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-07 Cont ID  
Sent By pschmitz Date 2006-01-07 Time 06:17 Rev Time 0.00
Received By pschmitz Date 2006-01-07 Time 06:17 Sent To  
Notes
2006-01-07 00:00:00RE-SUB PER PREVIOUS NOTES

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-07 Cont ID  
Sent By jleech Date 2005-10-06 Time 09:57 Rev Time 0.50
Received By jleech Date 2005-10-06 Time 09:57 Sent To  
Notes
2005-10-06 00:00:00 
 DENIED;
 PLUMBING PERMIT REQUIRED FOR DEMOLITION
 .
 NO DEAD ENDS IN SANITARY LONGER THEN 2'.
 FBC-2004 PLUMBING SEC. 704.5. INSPECTION
 REQUIRED.
 PLANS ARE MISSING REQUIRED TITLE BLOCK
 AND REQUIRED INFORMATION PER. FAC
 61GL-16.004.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695