Plan Review Details - Permit 05100079
Plan Review Stops For Permit 05100079
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-23 Cont ID  
Sent By mjacobs Date 2005-12-23 Time 08:28 Rev Time 1.50
Received By mjacobs Date 2005-12-23 Time 06:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-08 Cont ID  
Sent By mjacobs Date 2005-12-08 Time 14:47 Rev Time 1.00
Received By mjacobs Date 2005-12-08 Time 12:58 Sent To PC
Notes
2005-12-08 00:00:001) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL: (561) 805-6726
 FAX: (561) 659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-18 Cont ID  
Sent By mjacobs Date 2005-10-18 Time 13:33 Rev Time 1.00
Received By mjacobs Date 2005-10-18 Time 11:45 Sent To PC
Notes
2005-10-18 00:00:001) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2)ALL PLANS SUBMITTED FOR PERMITING
 AFTER SEPTEMBER 30TH SHALL BE DESIGNED
 UNDER THE 2004 FLORIDA BUILDING CODE.
 PLEASE REVISED PLANS ACCORDINGLY. SEE
 COVER SHEET AND SHEET A-3 ETC.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 (561)659-8026
 [email protected].

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-07 Cont ID  
Sent By dpalmer Date 2005-10-07 Time 10:52 Rev Time 0.33
Received By dpalmer Date 2005-10-07 Time 08:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-05 Cont ID  
Sent By nmccray Date 2005-10-05 Time 09:17 Rev Time 0.00
Received By nmccray Date 2005-10-05 Time 09:12 Sent To  
Notes
2005-10-05 00:00:00PROVISO:
  
 1) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 2) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE ALARM REMODEL.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 14:25 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 14:25 Sent To  
Notes
2005-12-22 00:00:00TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-01 Cont ID  
Sent By adarroug Date 2005-12-01 Time 13:13 Rev Time 0.00
Received By adarroug Date 2005-12-01 Time 13:13 Sent To  
Notes
2005-12-01 00:00:00TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-10-18 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 13:28 Sent To  
Notes
2005-10-04 00:00:00TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-17 Cont ID  
Sent By pkrauss Date 2006-02-17 Time 11:11 Rev Time 0.00
Received By pkrauss Date 2006-02-17 Time 11:11 Sent To  
Notes
2006-02-17 00:00:00PROVISO:
 NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By prafter Date 2005-10-06 Time 10:42 Rev Time 1.00
Received By prafter Date 2005-10-06 Time 10:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-02 Cont ID  
Sent By jleech Date 2006-02-02 Time 13:08 Rev Time 0.00
Received By jleech Date 2006-02-02 Time 13:08 Sent To  
Notes
2006-02-02 00:00:00REVISED PLUMBING PLANS REMOVED ONE SINK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-03 Cont ID  
Sent By pschmitz Date 2005-12-03 Time 10:52 Rev Time 0.00
Received By pschmitz Date 2005-12-03 Time 10:52 Sent To  
Notes
2005-12-03 00:00:00RE-SUB COMMENTS PASSED

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By jleech Date 2005-10-05 Time 14:06 Rev Time 2.00
Received By jleech Date 2005-10-05 Time 14:06 Sent To  
Notes
2005-10-05 00:00:00DENIED;
 1.DRINKING FOUNTAIN REQUIRED. FBC-2004
 PLUMBING TABLE 403.1
 2.WHERE ARE BATHROOM FACILITIES FOR
 WOMAN?
 3.SANITARY RISER DIAGRAM KITCHEN SINK
 NOT VENTED.
 4.WATER RISER DIAGRAM; WATER HAMMER
 ARRESTORS TO BE INSTALLED PER.
 MANUFACTORS SPEC'S. ( AS CLOSE TO SOURCE
 OF WATER HAMMER) MOVE TO BOTTOM OF
 DROPS.
 5.WATER HEATER DETAIL; SHOW HOW IT WILL
 BE PIPED TO OUTSIDE.
 6.WATER HEATER DETAIL; SHOW THERMAL
 EXPANSION CONTROL. SEC. 607.3.
 7.ONE OF THE KITCHEN SINKS SHALL MEET
 HANDICAP REQUIRMENTS. (SHOW DETAIL )
 MUST COMPLY WITH FBC-2004 CHAPTER 11
 SEC. 11-4.23.1 THRU 11-4.23.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695