Plan Review Details - Permit 05100077
Plan Review Stops For Permit 05100077
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-16 Cont ID  
Sent By alange Date 2006-02-16 Time 14:24 Rev Time 0.50
Received By alange Date 2006-02-16 Time 14:24 Sent To  
Notes
2006-02-16 00:00:00REV FOR DOOR AND WALL DETAIL OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-27 Cont ID  
Sent By alange Date 2005-12-27 Time 10:37 Rev Time 0.66
Received By alange Date 2005-12-27 Time 10:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-02 Cont ID  
Sent By alange Date 2005-12-02 Time 12:40 Rev Time 0.75
Received By alange Date 2005-12-02 Time 11:20 Sent To  
Notes
2005-12-02 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 A.ALL PAGES SHALL BE SIGNED AND SEAL
 BY THE ARCHITECT OF RECORD.
  
 ANY QUESTIONS CALL ME
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-20 Cont ID  
Sent By alange Date 2005-10-20 Time 09:37 Rev Time 2.25
Received By alange Date 2005-10-19 Time 10:57 Sent To  
Notes
2005-10-20 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PLANS SHALL BE DESIGNED TO THE 2004
 FBC.
  
 3.FBC 2004 EXISTING BUILDING 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304
 AND 305 OF THIS CODE.
 SHOW HOW COMPLIANCE WITH THE SELECTED
 LEVEL WILL BE OBTAINED.
  
 4.SHOW HOW RECEPTION COUNTER AND
 KITCHEN SINK WILL COMPLY WITH FBC
 CHAPTER 11 FOR ACCESSABILITY.
  
 5. SAFTEY GLAZING REQUIRED AT INTERIOR
 WINDOWS. FBC 2406.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-24 Cont ID  
Sent By dpalmer Date 2006-02-24 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2006-02-24 Time 10:03 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-23 Cont ID  
Sent By dpalmer Date 2005-12-23 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2005-12-23 Time 07:38 Sent To  
Notes
2005-12-23 00:00:00**** REDLINED PLANS*****
  
 PLEASE SEE NEW REVISED E2-1 SHOWS
 TRANSFORMER AND PANELS BEING RELOCATED
 TO HALL WAY AND ABOVE CEILING, HOWEVER
 PLEASE SEE E1.1 WAS NOT REVISED.
  
 PLEASE SEE GROUNDING ATTACHMENT LOCATION
 FOR TRANSFORMER NOT SHOWN, MUST CONNECT
 TO EXISTING GROUNDING ELECTRODE SYSTEM.
 250.30

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-07 Cont ID  
Sent By dpalmer Date 2005-10-07 Time 07:56 Rev Time 0.33
Received By dpalmer Date 2005-10-07 Time 07:50 Sent To  
Notes
2005-10-07 00:00:00REDLINED
  
 110.26 FOR MIN CLEARENCE IN NEW
 ELECTRICAL CLOSET. IF USING SCALE ON
 PLANS, CLEARENCE DOES NOT SEEM TO MET.
  
 REDLINED
  
 GROUNDING OF TRANSFORMER NOT INDICATED.
 PLEASE SEE 250.30

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-02-17 Cont ID  
Sent By mwennerg Date 2006-02-17 Time 09:42 Rev Time 0.00
Received By mwennerg Date 2006-02-17 Time 09:42 Sent To  
Notes
2006-02-17 00:00:00REVISION DATED 1/31/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By nmccray Date 2005-10-06 Time 14:40 Rev Time 0.00
Received By nmccray Date 2005-10-06 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 11:32 Sent To  
Notes
2006-02-14 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 11:09 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 11:09 Sent To P
Notes
2006-01-22 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 14:35 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 14:35 Sent To  
Notes
2005-12-22 00:00:00TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-01 Cont ID  
Sent By adarroug Date 2005-12-01 Time 13:01 Rev Time 0.00
Received By adarroug Date 2005-12-01 Time 13:01 Sent To  
Notes
2005-12-01 00:00:00TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-20 Cont ID  
Sent By alange Date 2005-10-20 Time 09:37 Rev Time 0.00
Received By alange Date 2005-10-04 Time 13:41 Sent To  
Notes
2005-10-04 00:00:00TO "COMM" BD#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By prafter Date 2005-10-06 Time 08:47 Rev Time 1.00
Received By prafter Date 2005-10-06 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-12-23 Cont ID  
Sent By jleech Date 2005-12-23 Time 11:33 Rev Time 0.50
Received By jleech Date 2005-12-23 Time 11:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-07 Cont ID  
Sent By jleech Date 2005-12-07 Time 12:30 Rev Time 0.50
Received By jleech Date 2005-12-07 Time 12:30 Sent To  
Notes
2005-12-07 00:00:00DENIED;
 KITCHEN SINK DETAIL;
 ACCESS PANEL MUST COMPLY WITH FBC CH. 11
 FIG.31 AND 32, COPY INCLOSED WITH
 REVIEW.
 COUNTER TO BE NO HIGHER THAN 34" AND
 MUST HAVE A KNEE CLEARENCE OF AT LEAST
 27" HIGH. SINK CANNOT BE DEEPER THAN 6
 1/2". SEC 11-4.24 COPY OF CODE WITH
 REVIEW NOTES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-07 Cont ID  
Sent By jleech Date 2005-10-07 Time 09:17 Rev Time 1.00
Received By jleech Date 2005-10-07 Time 09:17 Sent To  
Notes
2005-10-07 00:00:00DENIED;
 1.GENERAL NOTES; # 1 PLEASE CHANGE TO
 FBC-2004.
 2.DEMESTIC WATER ISOMETRIC; WATER HAMMER
 ARRESTORS TO BE USED FBC-2004 PLUMBING
 SEC 604.9, TO BE INSTALLED AS CLOSE TO
 SOURCE OF WATER HAMMER AS POSSIBLE.
 3.KITCHEN SINK SHALL COMPLY WITH FBC-
 2004 BUILDING CHAPTER 11 SEC. 11-4.24.1
 THRU 11-4.24.7. (SHOW DETAIL)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695