Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-12-25 Cont ID  
Sent By shill Date 2005-12-25 Time 16:01 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 10:02 Rev Time 0.00
Received By shill Date 2006-08-11 Time 10:02 Sent To  
Notes
2006-08-11 00:00:00REVISED A0, A1 DATED 7/17/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-06-06 Cont ID  
Sent By shill Date 2006-06-06 Time 09:26 Rev Time 0.00
Received By shill Date 2006-06-05 Time 12:51 Sent To Z
Notes
2006-06-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE PARKING INFORMATION (TOTAL
 NUMBER OF SPACES, NUMBER OF ACCESSIBLE
 SPACES.)
  
 2.)ACCESSIBLE PARKING REQUIRED IN THE
 REAR OF THE BUILDING.SEE
 FBC11-4.1.6(1)(B), FBC11-4.1.2(5)(A)
 REFERS TO "EACH SUCH PARKING AREA".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-27 Cont ID  
Sent By shill Date 2006-03-27 Time 09:49 Rev Time 0.00
Received By shill Date 2006-03-27 Time 09:32 Sent To  
Notes
2006-03-27 00:00:00FIRE SPRINKLERS SEPARATE PERMIT
 #05100075

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-14 Cont ID  
Sent By shill Date 2006-02-14 Time 09:15 Rev Time 3.00
Received By shill Date 2006-02-13 Time 15:16 Sent To  
Notes
2006-02-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEE PREVIOUS LIST, ITEMS 1 AND 2.
 THEY WERE TO BE CORRECTED ON THE
 UNNUMBERED SHEET WITH BUILDING DATA.
 THIS SHEET WAS NOT REVISED AND
 RESUBMITTED.THIS SHEET PROVIDES
 INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE.SEE THE VOIDED SET.
  
 PLEASE REVISE OCCUPANT LOAD TO 97.
  
 3.)SEE PREVIOUS LIST, ITEM #3.REVISE
 APPLICATION TO REFLECT CORRECT SCOPE OF
 WORK, INCLUDING EXTERIOR STAIR AND
 WHEELCHAIR LIFT.
  
 THIRD REQUEST; PLEASE COMPLY BEFORE
 PERMIT ISSUANCE.
  
 4.)ADDRESSED.
  
 5.)ADDRESSED.
  
 5.)ADDRESSED.
  
 7.)SEE PREVIOUS LIST, ITEM #9.THE
 STAIR HANDRAIL EXTENSIONS ARE TO COMPLY
 WITH FBC11-4.8.5(6), FIGURE 19.AS
 DESIGNED THEY POSE A HAZARD. THEY ARE TO
 BE ROUNDED OR RETURN TO THE FLOOR.NOT
 ADDRESSED.
  
 THIS WAS ADDRESSED BUT A PREVIOUS
 REQUEST FOR THE DIMENSION OF THE RAIL
 LENGTH AT THE TOP OF THE STAIR WAS NOT
 ADDRESSED.PLEASE PROVIDE THAT
 DIMENSION.
  
 8.)ADDRESSED.
  
 9.)SEE PREVIOUS LIST, ITEM 12.
 PROVIDE EITHER AN APPROVED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FOR THE 1
 HOUR WALL, FBC7.
  
 THE UL ASSEMBLY PROVIDED IS NOT VALID.
 NOTE THAT YOU HAVE SPECIFIED D419; THIS
 SHOULD BE A U ASSEMBLY.
  
 10.)PROVIDE A FIRE SPRINKLER PLAN
 FBC*106.3.5.1.1(5).
  
 THIS IS REQUIRED BY FLORIDA STATUE PRIOR
 TO PERMIT ISSUANCE WHEN SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE.PROVIDE A
 SPRINKLER LAYOUT PLAN AS REQUESTED.IT
 IS UNDERSTOOD THAT SPRINKLER DRAWINGS ON
 A SEPARATE PERMIT WILL BE PROVIDED, BUT
 A SPRINKLER PLAN IS REQUIRED AT THIS
 TIME FOR THE RENOVATION PERMIT.
  
 10.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF THE
 ABOVE ITEMS ARE NOT ADDRESSED IN THE
 THIRD REVIEW.
  
 A 4X FEE WAS CHARGED BY ELECTRIC.THERE
 ARE ALSO BUILDING COMMENTS WHICH WERE
 NOT ADDRESSED 3X.PLEASE NOTE THAT THE
 FEE WILL BE CHARGED AGAIN IF THE
 COMMENTS ARE NOT ADDRESSED A 4TH TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-25 Cont ID  
Sent By shill Date 2005-12-25 Time 16:07 Rev Time 2.00
Received By shill Date 2005-12-25 Time 16:00 Sent To  
Notes
2005-12-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEE PREVIOUS LIST, ITEMS 1 AND 2.
 THEY WERE TO BE CORRECTED ON THE
 UNNUMBERED SHEET WITH BUILDING DATA.
 THIS SHEET WAS NOT REVISED AND
 RESUBMITTED.THIS SHEET PROVIDES
 INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE.SEE THE VOIDED SET.
  
 3.)SEE PREVIOUS LIST, ITEM #3.REVISE
 APPLICATION TO REFLECT CORRECT SCOPE OF
 WORK, INCLUDING EXTERIOR STAIR AND
 WHEELCHAIR LIFT.
  
 4.)REVISIONS WERE MADE TO SHEET A1 AND
 NOT CLOUDED.OTHER SHEETS MAY BE
 AFFECTED AS WELL.WITHOUT A RESPONSE
 LETTER (OPTIONAL BUT HELPFUL) AND
 CLOUDED CHANGES (REQUIRED) IT MAKES IT
 DIFFICULT TO LOCATE THE ADDRESSED ITEMS.
 PLEASE CLOUD ALL CHANGES.
  
 5.)SEE PREVIOUS LIST, ITEM 4, NOT
 ADDRESSED.THE WHEELCHAIR LIFT IS TO
 COMPLY WITH ASME A17.1, FBC3001.2.
  
 5.)SEE PREVIOUS LIST, ITEM 5, NOT
 ADDRESSED.SHOW COMPLIANCE WITH
 FBC11-4.11.2, FBC11-4.2.4 FOR THE LIFT.
 INDICATE THAT THE SURFACE IS LEVEL.OR,
 PROVIDE OTHER INFORMATION AND SHOW
 COMPLIANCE WITH FBC CHAPTER 11.NOT
 ADDRESSED.
  
 7.)SEE PREVIOUS LIST, ITEM #9.THE
 STAIR HANDRAIL EXTENSIONS ARE TO COMPLY
 WITH FBC11-4.8.5(6), FIGURE 19.AS
 DESIGNED THEY POSE A HAZARD. THEY ARE TO
 BE ROUNDED OR RETURN TO THE FLOOR.NOT
 ADDRESSED.
  
 8.)SEE PREVIOUS LIST, ITEM 11.SHOW
 LANDING AND DOOR DIMENSIONS, FBC1009.4,
 EXCEPTION 2.NOT ADDRESSED.
  
 9.)SEE PREVIOUS LIST, ITEM 12.
 PROVIDE EITHER AN APPROVED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FOR THE 1
 HOUR WALL, FBC7.
  
 10.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF THE
 ABOVE ITEMS ARE NOT ADDRESSED IN THE
 THIRD REVIEW.
  
  
 10.)PROVIDE A FIRE SPRINKLER PLAN
 FBC*106.3.5.1.1(5).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-21 Cont ID  
Sent By shill Date 2005-11-21 Time 18:02 Rev Time 1.00
Received By shill Date 2005-11-21 Time 17:58 Sent To  
Notes
2005-11-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)GOVERNING CODE IS FBC2004 EFFECTIVE
 10/1/2005.
  
 2.)BUILDING DATA (UNNUMBERED SHEET)
 PROVIDES INCORRECT TABLE FOR INTERIOR
 FINISH CLASSIFICATION, FBC TABLE 803.5.
  
 3.)THE APPLICATION STATES THAT THIS IS
 A TENANT IMPROVEMENT.PLANS SHOW A NEW
 EXTERIOR STAIR AND WHEELCHAIR LIFT.
 REVISE THE PERMIT APPLICATION.
  
 4.)THE WHEELCHAIR LIFT IS TO COMPLY
 WITH ASME A17.1, FBC3001.2.
  
 5.)SHOW COMPLIANCE WITH FBC11-4.11.2,
 FBC11-4.2.4 FOR THE LIFT.INDICATE THAT
 THE SURFACE IS LEVEL.
  
 6.)SHOW COMPLIANCE WITH ALL
 REQUIREMENTS OF FBC11-4.27.
  
 7.)PROVIDE A DETAIL FOR THE BREAKROOM
 SINK, FBC11-24.PLEASE NOTE THE
 REQUIREMENT FOR KNEE CLEARANCE,
 FBC11-24.3.
  
 8.)SHOW MANEUVERING CLEARANCE FOR DOOR
 106, PUSH SIDE, FBC11 FIGURE 25.
  
 9.)THE STAIR HANDRAIL AT THE BOTTOM OF
 THE STAIR IS TO COMPLY WITH
 FBC11-4.8.5(6), FIGURE 11-19.
  
 10.)SHOW THE DIMENSION OF THE HANDRAIL
 EXTENSION AT THE TOP OF THE STAIR,
 FBC1009.11.5.
  
 11.)SHOW LANDING AND DOOR DIMENSIONS,
 FBC1009.4, EXCEPTION 2.
  
 12.)PROVIDE EITHER AN APPROVED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FOR THE 1 HOUR WALL, FBC7.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 19:51 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 19:42 Sent To  
Notes
2006-07-28 00:00:00REV'S OK, STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 06:54 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 06:47 Sent To  
Notes
2006-06-02 00:00:00**** UNSAT *****
  
 1) NOTE: PLEASE SEE PREVIOUS PLANS WERE
 REDLINED FOR FBC CHAPTER 13, HOWEVER
 COMPLIANCE FOR THIS NOT YET FULLY
 IMPLEMENTED ON PLANS.
 PLEASE SEE 13-415.1.ABC.1.1 , .2,.3
 PLEASE ADJUST PLANS AND SUBMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-27 Cont ID  
Sent By dpalmer Date 2006-03-27 Time 07:15 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 21:56 Sent To  
Notes
2006-03-27 00:00:00PLANS ARE REDLINED FOR FBC 2004,
 13-415.1.ABC.1.1&.2
  
  
 PASSED PENDING SUBMITTALS FOR UPS TO BE
 BROUGHT IN FOR REVIEW.
 CALLED ARCHITECT'S OFFICE AND LEFT
 MESSAGE 7:10AM 3/27.
  
  
  
  
 *** PLEASE KNOW, ALL REVISIONS/OPTIONS
 MUST BE SUBMITTED FOR REVIEW BEFORE
 ROUGH ELECTRICLA INSPECTION.
2006-03-24 00:00:00IN ELEC FOR REVIEW, ELECTRICALREVIEW
 TO BE COMPLETED ON 3/27/06

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 21:34 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 21:09 Sent To  
Notes
2006-02-08 00:00:00******** UNSAT 3RD REVIEW **********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 TWO REVIEWS ARE NOT ADDRESSED.
 PLEASE SEE NEW NOTE FOR CHANGE IN PLANS.
 PLEASE SEE NOTES BELOW WHICH ARE
 DIRECTLY TAKEN FROM PREVIOUS REVIEW.
  
 *** UNSAT 2ND REVIEW ***
  
 PLEASE SEES SOME NOTES FROM PREVIOUS
 REVEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE BELOW NOTES ARE TAKEN
 DIRECTLY FROM THOSE NOTES.
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE:NO. PLEASE SEE PANEL SCHEDULES
 OR LOAD CALCUALTIONS DO NOT INDICATE ANY
 CONTINUOUS OR LARGEST MOTOR LOADS??
  
 ** NOTE #3 NO, PLEASE SEE THAT ALL
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: OK
  
 5)NOTE: OK
  
 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALLED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.PER 110.9/215.5
 ** IT IS NOTED THAT THE AIC RATINGS WERE
 SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN
 DISCONNECT RATING ALSO.
  
 NEW NOTE:
 7)NOTE:NO, PLEASE SEE THE FEE AS
 REQUIRED UNDER FLORIDA STATUE HAS NOW
 BEEN ACCESSED AND IS REQUIRED TO BE PAID
 BEFORE PLANS CAN BE RESUBMITTED.
 A FEE OF $4,293.60 IS NOW OWED.
 PLEASE SEE ONE SET OF PLANS ARE NOW
 BEING RETAINED FOR FILE.
 IT IS STRONGLY RECOMMEDED A MEETING BE
 HELD BEFORE RESUBMITTING PLANS TO
 ALLEAVIATE ANY FURTHER DELAYS OR FINES.
 PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS. THIS
 IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ******* NEW NOTE ********
  
 1)NOTE: PLEASE SEE RISER NOW INDICATES A
 NEW UPS SYSTEM BEING INSTALLED HOWEVE NO
 INFORMATION HAS BEEN SUBMITTED FOR THIS
 SYSTEM. PLEASE ALSO BE SURE VALUE FOR
 THIS SCOPE OF WORK IS ADJUSTED EVEN IF
 OWNER SUPPLIED. FBC 108.3 ADMINISTRATIVE
 SECTION OF THE LOCAL ADMINISTRATIVE
 CODE.
 UNABLE TO REVIEW AS NOT ENOUGH
 INFORMATION IS SUBMITTED.
 PLEASE ALSO SEE ROOM IS NOW BEING LABLED
 AS A "NETWORK ROOM"?? PLEASE CLARIFY USE
 AS IF THIS ROOM IS AN IT ROOM,
 REQUIREMENTS OF 645 AND NFPA-75 MAY
 APPLY.
 THIS MAY ALSO AFFECT MECHANICAL, AND
 BLDG SHEETS.
  
 2)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1ABC.1.1,.2
 PLEASE KNOW, THIS WAS NOT ON PREVIOUS
 REVIEW, HOWEVER IS REQUIRED UNDER THE
 2004 FBC WHICH PLANS ARE NOW SHOWN TO BE
 DESIGNED UNDER.
  
  
 ** ONE COPY OF ALL OLD VOIDED SHEETS
 WERE NOT SUBMITTED AS REQUESTED.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD VOIDED SHEETS
 NEED TO BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-23 Cont ID  
Sent By dpalmer Date 2005-12-23 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2005-12-23 Time 06:33 Sent To  
Notes
2005-12-23 00:00:00*** UNSAT 2ND REVIEW ***
  
 PLEASE SEES SOME NOTES FROM PREVIOUS
 REVEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE BELOW NOTES ARE TAKEN
 DIRECTLY FROM THOSE NOTES.
  
 1)NOTE: NOTE #1 NO, PLEASE KNOW THAT ALL
 DESIGNS/PLANS SUBMITTED FOR PERMIT AFTER
 OCT 1ST, 2005 SHALL FALLUNDER THE 2004
 FBC.
 PLEASE ADJUST ALL SHEETS CONTAINING
 REFERENCE TO THE 2001 FBC. PLEASE ALSO
 SEE ALL MEP'S ,PLEASE SEE NOTES ON THESE
 SHEETS WITH REFERENCE TO THE 2001.
 PLEASE SEE SOME SHEETS HAD THESE CHANGES
 MADE. PLEASE SEE ELECTRICAL SHEET NOW
 HAS MISSING NOTES, PLEASE BE SURE TO
 SPECIFY THE NEC CURRENTLY IN
 EFFECT.(2002), NFPA-101 2003, NFPA-72,
 2002
  
 2)NOTE: NOTE #2 NO/YES,PLEASE SEE
 MISSSING CONDUCTORS FROM GUTTER TO
 METER. PLEASE SEE OTHER TO PANEL FROM
 TENANT DISCONNECT WERE ADDED.
 215.5, 310.16,240.4 ETC.
  
 3)NOTE:NOTE #3 NO, PLEASE SEE THAT ALL
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: NOTE #4 NO, PLEASE INDICATE
 ATTACHMENT LOCATION FOR TRANSFORMER PER
 250.30
 PLEASE SEE THIS IS REQUIRED TO BE SHOWN
 BACK TO THE EXISTING GROUNDING ELECTRODE
 SYSTEM.(NOTES, ONE LINE) ETC
  
 5)NOTE: NOTE #5 NO, PLEASE SEE MAIN IS
 LABLED 1OF 1, HOWEVER RISER SHOWS TWO
 MAINS. THE OTHER IS SHOWN 2 OF 2. , THE
 OTHER SHOULD BE LABLED 1 OF 2.
  
 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALLED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.PER 110.9/215.5
 ** IT IS NOTED THAT THE AIC RATINGS WERE
 SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN
 DISCONNECT RATING ALSO.
  
 NEW NOTE:
 7)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS. THIS
 IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD VOIDED SHEETS
 NEED TO BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2005-11-15 Time 13:53 Rev Time 1.00
Received By dpalmer Date 2005-11-15 Time 12:31 Sent To  
Notes
2005-11-15 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE KNOW THAT ALL
 DESIGNS/PLANS SUBMITTED FOR PERMIT AFTER
 OCT 1ST, 2005 SAHLL FALLUNDER THE 2004
 FBC.
 PLEASE ADJUST ALL SHEETS CONTAINGIN
 REFERENCE TO THE 2001 FBC. PLEASE ALSO
 SEE ALL MEP'S ,A-SHEETS WITH RESPECT TO
 REFERENCED CODES, TABLES ETC.
  
 2)NOTE: PLEASE SEE MISSSING CONDUCTORS
 ON RISER DIAGRAM FROM GUTTER TO METER,
 METER TO MAIN AND TO SUB PANEL.
 215.5, 310.16,240.4 ETC.
  
 3)NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS ARE SHOWN
 AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: PLEASE INDICATE ATTACHMENT
 LOCATION FOR TRANSFORMER PER 250.30
  
 5)NOTE: PLEASE SEE MAIN IS LABLED 1OF 1,
 HOWNER RISER SHOWS TWO MAINS. THE OTHER
 IS SHOWN 2 OF 2. , THE OTHER SHOULD BE
 LABLED 1 OF 2.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IT IS NOTED THAT THE AIC RATINGS WERE
 SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN
 DISCONNECT RATING ALSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 13:12 Rev Time 0.00
Received By mwennerg Date 2006-08-31 Time 13:12 Sent To  
Notes
2006-08-31 00:00:00REVISION DATED 7/17/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-06-02 Cont ID  
Sent By mwennerg Date 2006-06-02 Time 11:14 Rev Time 0.00
Received By mwennerg Date 2006-06-02 Time 11:14 Sent To  
Notes
2006-06-02 00:00:00NEW SHEETS
  
 ALL WORK SHALL COMPLY WITH APPLICABLE
 BUILDING CODES, AND NFPA 101, 2003
 EDITION, SECTION 7.5.4 (ACCESSIBLE MEANS
 OF EGRESS).
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-03-29 Cont ID  
Sent By mwennerg Date 2006-03-29 Time 10:15 Rev Time 0.00
Received By mwennerg Date 2006-03-29 Time 10:15 Sent To  
Notes
2006-03-29 00:00:00PASSED ON 11/10/05 BY M. CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-02-15 Cont ID  
Sent By mcarsill Date 2006-02-15 Time 17:03 Rev Time 0.00
Received By mcarsill Date 2006-02-15 Time 17:03 Sent To  
Notes
2006-02-08 00:00:00NEW SHEETS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-23 Cont ID  
Sent By mcarsill Date 2005-12-23 Time 09:21 Rev Time 0.00
Received By mcarsill Date 2005-12-23 Time 09:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 13:25 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 13:25 Sent To  
Notes
2005-11-10 00:00:001. PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED. THEY ARE TO BE TYPE 2A 10BC
 PORTABLE FIRE EXTINGUISHERS CURRENTLY
 SERVICE TAGGED AND MOUNTED.
  
 2. AISLES BETWEEN THE WORK STATIONS
 LOCATED IN THE OPEN WORK AREA SHALL BE
 ARRANGED TO PROVIDE FOR THE MINIMUM
 CLEARNCE OF 44 INCHES. THE PLANS SEEM TO
 REFLECT MORE WHICH IS ACCEPTABLE.
  
 3. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 4. DEBRIS SHALL BE REMOVED DAILY FROM
 THE SITE.
  
 5. EXISTING HANDRAILS AND GUARDRAILS ARE
 TO MEET THE PRESCRIPTIVE STRENGTH
 REQUIREMENTS OF THE BUILDING AND FIRE
 CODES.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER.
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-09-13 Cont ID  
Sent By ptjomsto Date 2006-09-13 Time 13:23 Rev Time 0.00
Received By ptjomsto Date 2006-09-13 Time 13:23 Sent To  
Notes
2006-09-13 00:00:00SUBMITTAL/RESTAMP GIVEN DIRECTLY TO
 PATTY KRAUSS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 18:29 Sent To  
Notes
2006-07-28 00:00:00TO COMM BOARD #23

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 15:17 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 15:17 Sent To  
Notes
2006-07-14 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 13:01 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 13:01 Sent To B
Notes
2006-07-14 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 13:53 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 13:53 Sent To M
Notes
2006-06-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 14:37 Rev Time 0.00
Received By shill Date 2006-05-18 Time 14:37 Sent To  
Notes
2006-06-02 00:00:006/2/06-TAKEN FROM "COMM" BD TO BLDG AND
 FIRE.
 GAVE TO MR FOR FIRE REVIEW
 ON SMH DESK
  
2006-05-26 00:00:00TO "COMM" BD#1-REV
2006-05-18 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 19:58 Sent To  
Notes
2006-03-23 00:00:00TO COMM BOARD SPACE #, 48, NEEDS B,
 F(FOR FIRE SPRINKLER LAYOUT), E, AND
 M(NEW SHEETS).

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 16:01 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 16:01 Sent To  
Notes
2006-03-02 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 18:57 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 18:57 Sent To  
Notes
2006-02-07 00:00:00TO "COMM" BD#11
2006-01-17 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 18:57 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 18:57 Sent To  
Notes
2005-12-22 00:00:00TO "COMM" BD#53
2005-11-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-11-21 Time 16:20 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 13:32 Sent To  
Notes
2005-10-13 00:00:00TO "COMM" BD#10
2005-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-09-13 Cont ID  
Sent By pkrauss Date 2006-09-13 Time 13:25 Rev Time 0.00
Received By pkrauss Date 2006-09-13 Time 13:25 Sent To  
Notes
2006-09-13 00:00:00RE-STAMP

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 16:13 Rev Time 0.30
Received By tgordon Date 2006-06-19 Time 16:13 Sent To  
Notes
2006-06-19 00:00:00REVISION TO MECH. PLANS PAGE M1.1 AND
 M3-1.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-03-29 Cont ID  
Sent By pkrauss Date 2006-03-29 Time 07:42 Rev Time 0.00
Received By pkrauss Date 2006-03-29 Time 07:00 Sent To  
Notes
2006-03-29 00:00:00PROVISO FROM 2-8-06 WAS NOT ADDRESSED.
 AIR FROM BATHROOM AREAS SHALL NOT BE
 RECIRCULATED IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
2006-03-22 00:00:00NEEDS MECH REVIEW, NEW/ REVISED SHEETS
 IN SETS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-08 Cont ID  
Sent By pkrauss Date 2006-02-08 Time 15:03 Rev Time 0.00
Received By pkrauss Date 2006-02-08 Time 15:03 Sent To  
Notes
2006-02-08 00:00:00PROVISO:
 PLAN SHEET M1.1, RETURN AIR FROM RTU-2
 IS INDICATED IN THE RESTROOM AREAS.
 PLEASE NOTE, AIR FROM BATHROOMS SHALL
 NOT BE RECIRCULATED, EXHAUST ONLY IN
 ACCORDANCE WITH 2004 FMC TABLE 403.3.
 PLEASE REMOVE RETURN AIR FROM THE
 BATHROOM AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-01-05 Cont ID  
Sent By pkrauss Date 2006-01-05 Time 09:04 Rev Time 0.00
Received By pkrauss Date 2006-01-05 Time 08:57 Sent To  
Notes
2006-01-05 00:00:00DENIED:
 SEE COMMENTS FROM REVIEW DATED 11-15-05
 (ATTACHED).PLANS ARE OTHERWISE CODE
 COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-11-15 Cont ID  
Sent By pkrauss Date 2005-11-15 Time 15:23 Rev Time 0.30
Received By pkrauss Date 2005-11-15 Time 15:23 Sent To  
Notes
2005-11-15 00:00:00DENIED:
 PLEASE REVISE PLANS TO REFERENCE CURRENT
 CODE.2004 FLORIDA BUILDING CODE WENT
 INTO EFFECT 1 OCTOBER 2005.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By prafter Date 2005-10-06 Time 10:11 Rev Time 1.00
Received By prafter Date 2005-10-06 Time 10:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By pschmitz Date 2006-02-03 Time 12:40 Rev Time 0.00
Received By pschmitz Date 2006-02-03 Time 12:40 Sent To  
Notes
2006-02-03 00:00:00PROVISO: VENTS ADDED TO URINALS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-04 Cont ID  
Sent By jleech Date 2006-01-04 Time 13:48 Rev Time 1.00
Received By jleech Date 2006-01-04 Time 13:48 Sent To  
Notes
2006-01-04 00:00:00DENIED;
 1.SECOND REQUEST; SHOW COMPLIANCE TO
 FBC-2004 PLUMBING TABLE 403.1. SHOW
 OCCUPANCY CLASSIFICATION, NUMBER OF
 EMPLOYEES
 2.WATER RISER; WATER HAMMER ARRESTORS
 ARE REQUIRED BY MANUFACTOR'S
 INSTALLATION INSTRUCTIONS TO BE AS CLOSE
 TO THE SORCE OF HAMMER. PLEASE INSTALL
 WHA'S AT THE BOTTOM OF DROPS.
 3.BREAK ROOM SINK DOES NOT COMPLY WITH
 FBC-2004 CHAPTER 11 SEC.11-4.24.3 KNEE
 CLEARANCE; 19" REQUIRED.
 4.SANITARY RISER DIAGRAM; PLEASE INSTALL
 URINALS USING SANITARY TEE'S (ONE SET OF
 PLANS MARKED IN RED)
  
 DO NOT SHOW TRAPS ON URINALS TRAPS
 BUILT INTO FIXTURE.
 5.SANITARY RISER DIAGRAM; 3" PIPE
 REQUIRED TO WET VENT BOTH FLOOR DRAINS
 IN BATHROOMS FBC-2004 PLUMBING TABLE
 909.3 WET VENT SIZE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By jleech Date 2005-10-06 Time 12:56 Rev Time 1.50
Received By jleech Date 2005-10-06 Time 12:56 Sent To  
Notes
2005-10-06 00:00:00DENIED;
 1.PLUMBING NOTES; NOTE #1 CHANGE TO 2004
 CODE.
 2.SHOW COMPLIANCE TO FBC-2004 PLUMBING
 TABLE 403.1. SHOW CAULK'S ON PLUMBING
 PAGE.
 3.WATER RISER; BREAK SINK DROP NOT
 SHOWN. PLEASE SHOW WATER HAMMER
 ARRESTORS AT THE BOTTOM OF DROPS.
 MANUFACTOR INSTALLATION INSTRUCTIONS, TO
 BE INSTALLED AS CLOSE TO THE SOURCE OF
 THE HAMMER.
 4.BREAK ROOM SINK MUST COMPLY WITH
 FBC-2004 BUILDING CHAPTER 11 SEC.
 11-4.24.1 THRU 11-4.24.7. (SHOW DETAIL)
 5.SANITARY ISOMETRIC; BREAK SINK NOT
 VENTED. URINALS ARE "S" TRAPED. USE
 SANITARY TEE'S OFF OF VENT STACK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-08 Cont ID  
Sent By jroach Date 2006-08-08 Time 16:25 Rev Time 0.00
Received By jroach Date 2006-08-08 Time 16:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-30 Cont ID  
Sent By jroach Date 2006-07-30 Time 14:14 Rev Time 0.00
Received By jroach Date 2006-07-30 Time 14:14 Sent To  
Notes
2006-07-30 00:00:007/30/2006 ***FAILED***
  
 1) REVISIONS SUBMITTED DO NOT MATCH THE
 LATEST MINOR AMENDMENT APPROVAL, WHICH
 PROVIDES FOR THE LOCATION OF A HC SPACE
 AT THE REAR OF THE BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-07 Cont ID  
Sent By jroach Date 2006-06-07 Time 13:54 Rev Time 0.00
Received By jroach Date 2006-06-07 Time 13:54 Sent To  
Notes
2006-06-07 00:00:006/7/2006 ***FAILED***
  
 1) MODIFICATIONS TO THE PARKING AND
 LANDSCAPING REQUIRE SUBMISSION AND
 APPROVAL OF A MINOR PLANNED DEVELOPMENT
 (PD) AMENDMENT APPLICATION TO THE
 PLANNING AND ZONING DEPARTMENT.THIS
 MUST BE DONE PRIOR TO BUILDING PERMIT.
  
 FOR INFORMATION PERTAINING TO THIS
 REQUIREMENT, PLEASE CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.