2006-06-11 00:00:00 | IN ELEC |
| ************ UNSAT 2ND REVIEW********* |
| |
| |
| ** IT IS KNOWN THAT PLANS ARE UNDER THE |
| 2001 FBC, AS THE ELECTRICLA REVIEW WAS |
| DONE UNDER THE 2001FBC AND OTHER ADOPTED |
| CODES UNDER THE 2001 FBC. |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS REVIEW STILL NEED TO BE |
| ADDRESSED AND SOME NEW COMMENTS FOR |
| ITEMS ON PLANS. |
| |
| ************************************ |
| IMPORTANT |
| PLEASE SEE BUILDING REVIEW COMMENTS AND |
| PLEASE KNOW, IT WAS CONFIRMED BY THE |
| ASST BUILDING OFFICAL THAT THIS JOB WILL |
| REQUIRE A MIN OF A RESIDENT INPSECTOR. |
| IN THIS CASE THREE SETS OF ALL PLANS |
| UNDER EACH PERMIT WILL BE REQUIRED ONCE |
| ALL IS READY TO BE ISSUED. IF THERE ARE |
| NAY QUESTIONS, PLEASE CONTACT MR. ROBERT |
| BROWN ASST BUILDING OFFICAL/LICENSE AND |
| PEMRITS MANAGER. |
| *********************************** |
| |
| ** PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW AND NEW |
| NOTE(S) ARE ADDED BELOW. |
| |
| DIXIE MEWS / AQUA TERRACE |
| |
| 1)NOTE: NOTE#1 NO, PLEASE SEE NOTE ALL |
| SHEET COMPLY. PLEASE SEE CIVILS WHICH |
| CONTAIN A RAISED SEAL OVER A |
| PHOTO-COPIED SIGNATURE BY THE ENGINEER. |
| PLEASE SEE THIS IS NOT PERMITTED AND |
| SHALL BE SIGNED WITH AN ORIGINAL |
| SIGNATURE AND DATE. PLANS MAY BE |
| RETAINED. |
| PLEASE SEE LANDSCAPE PLANS WHICH ARE |
| SIGNED WITH WHAT APPEARS TO BE A CRAYON? |
| PLEASE BE SURE THIS IS SIGNED IN INK. |
| PLEASE SEE MEP PLANS APPEAR TO BE SIGNED |
| WITH WHAT APPEARS TO BE "INITIALS"? |
| PLEASE SEE FS 471.025 WHICH REQUIRES A |
| SIGNATURE. THIS SHOULD BE THE DESIGNER'S |
| LEGAL SIGNATURE. IF THIS IS INDEED THE |
| "LEGAL SIGNATURE" OF ENGINEER, PLEASE |
| PROVIDE A SIGNED, DATED, SEALED LETTER |
| FOR ATTESTING TO THIS AS THE LEGAL |
| SIGNATURE. THIS LETTER MUST ALSO BE |
| NOTORIZED PER FS 117.05 |
| THIS LTR WILL THEN BE PLACED IN OUR |
| SIGNATURE FILE FOR ANY FUTURE REFERENCE. |
| |
| ** PREVIOUS NOTE** |
| PLEASE PROVIDE SIGNED, DATED AND |
| SEALED PLANS BY ARCHITECT AND |
| ENGINEER(S) OF RECORD. FS 481.221 AND |
| 471.025. |
| PLEASE SEE PLANS CONTAIN SOME SORT OF |
| "CORPORATE SEAL' WHICH IS NOT |
| ACCEPTABLE. |
| PLEASE KNOW THIS IS REQUIRED OF ALL |
| SHEETS AND FOR ALL TRADE REVIEWS WHETHER |
| OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| |
| 2)NOTE: NOTE #2 NO, PLEASE SEE MISSING |
| FIRM LICENSE NUMBER IN THE TITLE BLOCKS |
| FOR THE ARCHITECTURAL FIRM, LANDSCAPE |
| ARCH FIRM. PLEASE ALSO SEE THE "A" |
| SHEETS SHALL ALSO INDICATE THE |
| ARCHITECT'S PRINTED NAME. PLEASE SEE |
| THIS WAS REQUESTED BY MORE THAN ONE |
| REVIEWER ON PREVIOUS REVIEW AND THE |
| RESPONSE LTR MENTIONS "FIRM NAME ADDED". |
| PLEASE SEE THIS COMMENT WAS FOR ALL |
| REQUIRED INFORMATION. |
| PLEASE KNOW, THIS INFORMATION IS |
| REQUIRED ON ALL TITLE BLOCKS, ALL SHEETS |
| AND FOR ALL TRADES. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE COMPLETE AND INCLUDE ALL |
| INFORMATION ON SAID TITLE BLOCKS FOR |
| ARCHITECTUAL AND ENGINEERING FIRMS. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODES |
| 61G1-16.004 (ARCH) AND 61G15-23.002 |
| (ENG). |
| PLEASE KNOW THIS IS REQUIRED FOR ALL |
| SHEETS AND FOR ALL TRADES. |
| |
| 3)NOTE: OK |
| |
| 4)NOTE: NOTE #4 OK, DOORS REMOVED TO |
| MEET 110.26, PLEASE SEE BUILDING REVIEW |
| FOR ANY QUESTION FOR EGRESS. |
| PLEASE KNOW, OTHERWISE THIS COMMENT WAS |
| ADDRESSED. |
| |
| **PREVIOUS NOTE ** |
| PLEASE VERIFY CLEARENCES FOR |
| ELECTRICAL SERVICE PER 110.26, |
| APPEARS TO SHOW DOORS WHICH WILL SLIDE |
| OPEN ON EACH SIDE, HOWEVER THIS WILL |
| ALWAYS CREATE A COMMON POINT IN THE |
| CENTER WHICH WOULD NOT MEET CODE. |
| PLEASE PROVIDE AN ELEVATION AS HEIGHT |
| AND WIDTH IS TO BE VERIFIED. |
| PLEASE ALSO VERIFY IT APPEARS THIS |
| ROOM/AREA IS ALSO THE GRESS FROM COMMON |
| STAIR TOWER AND LOBBY AREA? |
| PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE |
| SEPARATION AS STAIRS EXIT INTO THIS AREA |
| AND NO DOORS ARE SHOWN WHICH MAY ALLOW |
| EXITING BACK INTO COMMON LOBBY AREA |
| PLEASE SEE THIS IS SHOWING SWITCHING FOR |
| LTS? |
| PLEASE ALSO SEE NEXT COMMENT WITH |
| RESPECT TO THE CIRCUIT SHOWN. |
| |
| 5)NOTE: NOTE #5 NO, PLEASE SEE THAT THE |
| DEDICATED CIRCUITS PER 620.23,620.24 |
| SHALL NOT FEED ANY OTHER ITEMS. PLEASE |
| SEE THE RECEPT IN ELEV RM, CAN NOT BE ON |
| THE SAME CIRCUIT WITH PIT RECEPT. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE HOUSE CIRCUIT SHOWN |
| FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN |
| FEEDING OTHER AREAS. PLEASE SEE 620.23 |
| WHICH REQUIRES THE BRANCH CIRCUIT FOR |
| LTS AND RECEPTS TO BE DEDICATED. |
| PLEASE ADJUST. |
| |
| 6)NOTE: NOTE #6 NO, PLEASE SEE SOME |
| MENTION OF FC'S ARE NOTED ON PLANS, |
| HOWEVER COMPLETE PHOTO-METRICS ARE |
| NEEDED. |
| PLEASE SUBMIT. |
| |
| ** PREVIOUS NOTE** |
| PLEASE PROVIDE PHOTOMETRICS FOR |
| COMMON AREAS FOR EGRESS LIGHTING. PLEASE |
| SEE THIS WOULD INCLUDE LOBBY AREAS, |
| STAIR TOWERS, SHOW ALL FT CANDLES TO THE |
| EXIT/PUBLIC RIGHT OF WAY. |
| PLEASE SEE 2003 NFPA-101 7.8 AND 7.9 |
| WHICH REQUIRES 10 FT CANDLES UNDER |
| NORMAL POWERE AND A MIN OF 1FT CANDLE |
| UNDER EM POWER. |
| PLEASE ALSO SEE FURTHER COMMENTS WIHT |
| RESPECT TO FIXTURES. |
| |
| 7)NOTE: OK |
| |
| 8)NOTE: OK. |
| |
| 9)NOTE: NOTE #9 OK, HOWEVER SEE NEW |
| NOTES FOR ADDED CONDUCTORS. |
| |
| ** PREVIOUS NOTE** |
| PLEASE SHOW THE CONDUCTORS FROM |
| HOUSE GUTTER TO EACH DISCONNECT. |
| 215.5 |
| |
| 10)NOTE: NOTE #10, THIS HAS NOT YET BEEN |
| CONFIRMED. PLEASE SEE PLANS AND |
| PAPERWORK NOW MENTION BUILDING SHALL |
| CONTAIN NEW "CONDO UNITS" AS SINGLE |
| FANILY RESIDENCES. |
| PLEASE SEE THE SD'S IN THE RES CONDO |
| UNITS MAY BE REQUIRED TO BE 120V WIRED |
| INLINE AND WITH ARC FAULT PROTECTION PER |
| 210.12B |
| CONTACT TO THE FIRE MARSHAL'S OFFICE AND |
| CHIEF CARSILLO WILL BE MADE. |
| IT SEEMS IF THESE ARE NOW SFR CONDO'S, |
| TRIPPING OF THE SD'S IN EACH UNIT UPON |
| SOME COOKING PRACTICES ETC WOULD CREATE |
| TRIPPING OF THE ENTIRE BUILDINGS FIRE |
| ALARM SYSTEM?? |
| |
| |
| ** PREVIOUS NOTE ** |
| PLEASE VERIFY WITH THE FIRE |
| MARSHAL'S OFFICE IF INDEED THE UNIT SD'S |
| WILL BE TIED INTO BASE BLDG PROTECTION |
| SYSTEM. |
| PLEASE KNOW, IF THESE ARE 120V WIRED |
| INLINE IN UNITS, THEN CIRCUITING WILL BE |
| REQUIRED ALONG WITH ARC FAULT |
| PROTECTION. |
| 215.5,210.12 |
| THIS WOULD ALSO BE AFFECTED BY THE |
| "TOWNHOUSE" DECLARATION. |
| |
| 11)NOTE: OK. |
| |
| 12)NOTE: OK. |
| |
| 13)NOTE: OK. |
| |
| 15)NOTE: OK. |
| |
| 16)NOTE: OK. |
| |
| 17)NOTE: NOTE #17 NO, ALMOST ALL WERE |
| DONE HOWEVER PLEASE SEE WALL SPACE 2' OR |
| MORE EVEN BEHIND DOORS WILL BE REQUIRED |
| TO HAVE A RECEPT. PLEASE SEE TWO |
| REDLINED IN PH UNITS. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE 210.52 FOR RECEPTS |
| MISSING FOR 2' OR MORE OF WALL SPACE. |
| PLEASE SEE MOST IF THESE LOCATIONS ARE |
| REDLINED ON PLANS. (SEE MOSTLY 3RD FLR. |
| |
| 18)NOTE: OK. |
| |
| 19)NOTE: OK, HOWEVER SEE NEW NOTES FOR |
| DINGIN CIRCUITS ADDED. |
| |
| 20)NOTE: OK. |
| |
| 21)NOTE: OK. |
| |
| 22)NOTE: OK. |
| |
| 23)NOTE: OK. |
| |
| 24)NOTE: OK. |
| |
| 25)NOTE: NOTE #25 NO, COULD NOT FIND? |
| RESPONSE MENTIONS THIS WAS ADDED? |
| |
| ** PREVIOUS NOTE ** |
| PLEASE PLACE NOTE ON PLANS FOR |
| ALL SD'S TO BE INSTALLED PER 2002 |
| NFPA-72 11.8.3.5 |
| |
| 26)NOTE: NOTE #26 NO, AND NO RESPONSE |
| WAS GIVEN FOR THE NOTE. |
| THIS SHOULD BE ADDED TO NOTES ON E-10 |
| |
| **PREIVOUS NOTE ** |
| PLEASE MAKE NOTE FOR ALL MIN |
| FAIR HOUSING ACT REQUIREMENTS FOR DEVICE |
| HEIGHTS. |
| 24 CFR 100.205 |
| |
| *********** NEW NOTES *********** |
| |
| 27) NOTE: PLEASE SEE DINING RM CIRCUITS |
| AND THE LIKE SHALL BE SHOWN WITH THE MIN |
| VA FIGURED FOR THE CIRCUIT AT 1.5VA. |
| PLEASE SEE 210.52B1,210.11C1, 220.16 |
| |
| 28) NOTE: PLEASE SEE THE FOLLOWING CODES |
| SHALL BE PRINTED ON ELECTRICAL PLANS. |
| NFPA-101 2003,NFPA-72 2002, NFPA-70 |
| 2002. |
| |
| 29) NOTE: PLEASE SEE RISER IS NOW |
| SHOWING "EQUIPMENT GROUNDING CONDUCTORS" |
| FOR SEC'S FROM GUTTER TO MAINS FOR |
| HOUSE. |
| PLEASE SEE 250.6,250.24B , THESE ARE |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 30) NOTE: PLEASE SEE WHAT APPEARS TO BE |
| A MISPRINT FOR THE RISER NOTE #5, |
| MENTIONS "MLB" , SHOULD THIS BE "MCB"? |
| |
| 31) NOTE: PLEASE SEE CIRCUITS FOR GEN |
| LTS AND RECEPTS SHALL BE SPECIFIC TO |
| ROOMS AND AREAS IN WHICH THESE CIRCUITS |
| ARE FEEDING. IE: MASTER BEDRM RECEPTS. |
| BATH #2 LTS, KITCHEN LTS ETC. |
| 408.4 |
| |
| 32) NOTE: PLEASE KNOW, AS PLANS WERE |
| INDEED SUBMITTED FOR PERMIT, PLEASE SEE |
| COPY OF FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS THREE OR MORE TIMES. |
| THIS IS ONLY A NOTICE GIVEN AT THIS |
| TIME. |
| |
| *** IMPORTANT** |
| |
| WHEN RESUBMITTING PLANS, PLEASE BE SURE |
| TO SUBMIT ONE COPY OF THE OLD PLANS FOR |
| REFERENCE. |
| |
| ** PLEASE SEE ONE SET OF PLANS HAS MUCH |
| OF THE ABOVE REDLINED FOR AREAS OF |
| COMMENTS. THIS MAY HELP IN AREAS AS |
| NOTED. (RECEPTS ETC) |
| |
| ** PLEASE KNOW, A RESPONSE LETTER WITH |
| RESPECT TO COMMENTS AND WHAT ACTIONS |
| WERE TAKEN WOULD GREATLY HELP IN |
| EXPEDITING THE PLAN REVIEW PROCESS. |
| PLEASE KEEP IN MIND TO CLOUD/TRIANGLE |
| ANY REVISED LOCATIONS ON PLANS. |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| |