Plan Review Details - Permit 05091702
Plan Review Stops For Permit 05091702
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 15:32 Rev Time 0.00
Received By alange Date 2006-07-13 Time 15:32 Sent To  
Notes
2006-07-13 00:00:00PLAN REVIEW DENIED
  
 ITEMS NEEDED TO BE INCLUDED WITH PLANS
 FOR BEFORE PERMITTING.
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.PLANS SHALL BE SIGNED, SEALED AND
 DATED BY THE ARCHITECT AND ENGINEERS OF
 RECORD.FS 481.221 AND 471.025SEE
 ELECTRICAL REVIEW REGARDING THIS AND
 TITLE BLOCK ISSSUES.
  
 7.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS FOR THE FOLLOWING, FLAT
 ROOFING AND SELECT THE ASSEMBLY USED
 ALL EXTERIOR EQUIPTMENT DOORS, STRAPS
 AND TIE-DOWNS.
  
 8.SUBMIT THE FOLLOWING STATE PRODUCT
 AND ATTACHE TO THE PRODUCT APPROVALS
 USED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14.SHOW A SPRINKLER SYSTEM COMPLYING
 WITH TABLE 500 NOTE "D".
  
 15.SUBMIT TWO ORIGONALS OF A SOILS
 REPORT SHOWING FOUNDATION AND FOOTING
 RECOMMENDATIONS.
  
 17.ROOF SHEATHING SHALL COMPLY WITH
 FBC 2322.2.5 AND WEST PALM BEACH
 AMMENDMENTS TABLE 2306.1.SHOW ROOF
 FASTENING ZONES ON PLANS.
  
 18.THE 2 HOUR RATED WALL BETWEEN
 GARAGE AND LIVING SPACE SHALL HAVE A
 DOOR RATED IN COMPLIANCE WITH FBC TABLE
 705.1.2.
  
 NEW COMMENTS:
 A.HAND DRAWN CHANGES NOT PERMITTED TO
 PLANS.FBC 2001 WPB AMMENDMENTS
 104.2.1.3
  
 B.PLANS SPEC THAT THEY ARE DESIGNED TO
 THE 2001 FBC YET PAGE SD1.O STILL
 REFLECTS THE 2004 FBC.
  
 IMPORTANT:
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2006-01-18 00:00:00PLAN REVIEW DENIED
  
 ITEMS NEEDED TO BE INCLUDED WITH PLANS
 FOR BEFORE PERMITTING.
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW BUILDING TYPE ON PLANS PER
 2004 FBC 602.
  
 4.PLANS SHALL BE SIGNED, SEALED AND
 DATED BY THE ARCHITECT AND ENGINEERS OF
 RECORD.FS 481.221 AND 471.025
  
 5.PLEASE CLEARIFY IF THE UNITS WILL BE
 FEE SIMPLE OF LEASEHOLD TITLE.
 SHOW WEATHER UNITS WILL BE TOWNHOUSE OR
 CONDO.
  
 6.W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS FOR THE FOLLOWING, ROOFING,
 FLAT AND TILE, ALL EXTERIOR DOORS
 INCLUDING EQUIPTMENT DOORS, STRAPS AND
 TIE-DOWNS, LINTELS AND OVERHEAD GARAGE
 DOORS.
  
 8.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9.PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2004 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 10.2004 FBC11-4.8.2 SLOPE & RISE.
 THE LEAST POSSIBLE SLOPE SHALL BE USED
 FOR ANY RAMP. THE MAXIMUM SLOPE FOR A
 RAMP IN NEW CONSTRUCTION SHALL BE 1 TO
 12. THE MAXIMUM RISE FOR RUN SHALL BE
 30" (SEE FIGURE 16).SHOW DETAILS FOR
 RAMPS USED.
  
 11. 2004 FBC 1607.7.1.1 THE GUARDRAIL
 SYSTEM SHALL BE DESIGNED AND CONSTRUCTED
 TO RESIST A 200 LB CONCENTRATED
 HORIZONTAL LOAD APPLIED ON A 1 SQ FT
 AREA AT ANY POINT IN THE SYSTEM
 INCLUDING INTERMEDIATE RAILS OR OTHER
 ELEMENTS SERVING THIS PURPOSE.SHOW
 DETAILS ON PLANS.
  
 12.ONCE CONSTRUCTION TYPE IS SELECTED
 THE BUILDING VALUATION WILL BE REVISED
 ACCORDING TO ICC BUILDING VALUATION
 DATA.REVISE PERMIT VALUATION TO
 REFLECT THIS TABLE AND PAY ADDITIONAL
 PERMIT FEES.
  
 13.PRODUCT APPROVAL SUBMITTED IS FOR
 AN OUT SWING FRENCH DOOR. SHOW LOCATION
 ON SCHEDULE.
  
 14.SHOW A SPRINKLER SYSTEM COMPLYING
 WITH FBC 903.3.1.1
  
 15.SUBMIT TWO ORIGONALS OF A SOILS
 REPORT SHOWING FOUNDATION AND FOOTING
 RECOMMENDATIONS.
  
 16. A23 A NOTE: *" CMU WALL WITH 3/4"
 PAINTED FINISH? PLEASE SUBMIT MORE
 INFORMATION.
  
 17.ROOF SHEATHING SHALL COMPLY WITH
 FBC 2304.9.1 #31
  
 18.THE 2 HOUR RATED WALL BETWEEN
 GARAGE AND LIVING SPACE SHALL HAVE A
 DOOR RATED IN COMPLIANCE WITH FBC 715.3
  
 19.INSUFFICIENT INFORMATION SUBMITTED
 FOR CLUB HOUSE REVIEW.SUBMIT PLANS TO
 A MINIMUM OF 1/8" SCALE WITH ALL THE
 REQUIRED STRUCTURAL DETAILS FOR REVIEW.
 FBC 106.1.3 AND 106.1.2, 106.3.5 WPB
 AMMENDMENTS TO THE 2004 FBC.
  
 20.SUBMIT BBQ SPECS AND HOOD DETAILS
 FOR CLUB HOUSE.
  
 21.POOL AND FENCING TO BE UNDER A
 SEPERATE PERMIT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-11 Cont ID  
Sent By dpalmer Date 2006-06-11 Time 19:49 Rev Time 0.00
Received By dpalmer Date 2006-06-11 Time 17:35 Sent To  
Notes
2006-06-11 00:00:00IN ELEC
 ************ UNSAT 2ND REVIEW*********
  
  
 ** IT IS KNOWN THAT PLANS ARE UNDER THE
 2001 FBC, AS THE ELECTRICLA REVIEW WAS
 DONE UNDER THE 2001FBC AND OTHER ADOPTED
 CODES UNDER THE 2001 FBC.
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS FOR
 ITEMS ON PLANS.
  
 ************************************
 IMPORTANT
 PLEASE SEE BUILDING REVIEW COMMENTS AND
 PLEASE KNOW, IT WAS CONFIRMED BY THE
 ASST BUILDING OFFICAL THAT THIS JOB WILL
 REQUIRE A MIN OF A RESIDENT INPSECTOR.
 IN THIS CASE THREE SETS OF ALL PLANS
 UNDER EACH PERMIT WILL BE REQUIRED ONCE
 ALL IS READY TO BE ISSUED. IF THERE ARE
 NAY QUESTIONS, PLEASE CONTACT MR. ROBERT
 BROWN ASST BUILDING OFFICAL/LICENSE AND
 PEMRITS MANAGER.
 ***********************************
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTE(S) ARE ADDED BELOW.
  
 DIXIE MEWS / AQUA TERRACE
  
 1)NOTE: NOTE#1 NO, PLEASE SEE NOTE ALL
 SHEET COMPLY. PLEASE SEE CIVILS WHICH
 CONTAIN A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE BY THE ENGINEER.
 PLEASE SEE THIS IS NOT PERMITTED AND
 SHALL BE SIGNED WITH AN ORIGINAL
 SIGNATURE AND DATE. PLANS MAY BE
 RETAINED.
 PLEASE SEE LANDSCAPE PLANS WHICH ARE
 SIGNED WITH WHAT APPEARS TO BE A CRAYON?
 PLEASE BE SURE THIS IS SIGNED IN INK.
 PLEASE SEE MEP PLANS APPEAR TO BE SIGNED
 WITH WHAT APPEARS TO BE "INITIALS"?
 PLEASE SEE FS 471.025 WHICH REQUIRES A
 SIGNATURE. THIS SHOULD BE THE DESIGNER'S
 LEGAL SIGNATURE. IF THIS IS INDEED THE
 "LEGAL SIGNATURE" OF ENGINEER, PLEASE
 PROVIDE A SIGNED, DATED, SEALED LETTER
 FOR ATTESTING TO THIS AS THE LEGAL
 SIGNATURE. THIS LETTER MUST ALSO BE
 NOTORIZED PER FS 117.05
 THIS LTR WILL THEN BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE.
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE SIGNED, DATED AND
 SEALED PLANS BY ARCHITECT AND
 ENGINEER(S) OF RECORD. FS 481.221 AND
 471.025.
 PLEASE SEE PLANS CONTAIN SOME SORT OF
 "CORPORATE SEAL' WHICH IS NOT
 ACCEPTABLE.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADE REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: NOTE #2 NO, PLEASE SEE MISSING
 FIRM LICENSE NUMBER IN THE TITLE BLOCKS
 FOR THE ARCHITECTURAL FIRM, LANDSCAPE
 ARCH FIRM. PLEASE ALSO SEE THE "A"
 SHEETS SHALL ALSO INDICATE THE
 ARCHITECT'S PRINTED NAME. PLEASE SEE
 THIS WAS REQUESTED BY MORE THAN ONE
 REVIEWER ON PREVIOUS REVIEW AND THE
 RESPONSE LTR MENTIONS "FIRM NAME ADDED".
 PLEASE SEE THIS COMMENT WAS FOR ALL
 REQUIRED INFORMATION.
 PLEASE KNOW, THIS INFORMATION IS
 REQUIRED ON ALL TITLE BLOCKS, ALL SHEETS
 AND FOR ALL TRADES.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE AND INCLUDE ALL
 INFORMATION ON SAID TITLE BLOCKS FOR
 ARCHITECTUAL AND ENGINEERING FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODES
 61G1-16.004 (ARCH) AND 61G15-23.002
 (ENG).
 PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES.
  
 3)NOTE: OK
  
 4)NOTE: NOTE #4 OK, DOORS REMOVED TO
 MEET 110.26, PLEASE SEE BUILDING REVIEW
 FOR ANY QUESTION FOR EGRESS.
 PLEASE KNOW, OTHERWISE THIS COMMENT WAS
 ADDRESSED.
  
 **PREVIOUS NOTE **
 PLEASE VERIFY CLEARENCES FOR
 ELECTRICAL SERVICE PER 110.26,
 APPEARS TO SHOW DOORS WHICH WILL SLIDE
 OPEN ON EACH SIDE, HOWEVER THIS WILL
 ALWAYS CREATE A COMMON POINT IN THE
 CENTER WHICH WOULD NOT MEET CODE.
 PLEASE PROVIDE AN ELEVATION AS HEIGHT
 AND WIDTH IS TO BE VERIFIED.
 PLEASE ALSO VERIFY IT APPEARS THIS
 ROOM/AREA IS ALSO THE GRESS FROM COMMON
 STAIR TOWER AND LOBBY AREA?
 PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE
 SEPARATION AS STAIRS EXIT INTO THIS AREA
 AND NO DOORS ARE SHOWN WHICH MAY ALLOW
 EXITING BACK INTO COMMON LOBBY AREA
 PLEASE SEE THIS IS SHOWING SWITCHING FOR
 LTS?
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE CIRCUIT SHOWN.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE THAT THE
 DEDICATED CIRCUITS PER 620.23,620.24
 SHALL NOT FEED ANY OTHER ITEMS. PLEASE
 SEE THE RECEPT IN ELEV RM, CAN NOT BE ON
 THE SAME CIRCUIT WITH PIT RECEPT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE HOUSE CIRCUIT SHOWN
 FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN
 FEEDING OTHER AREAS. PLEASE SEE 620.23
 WHICH REQUIRES THE BRANCH CIRCUIT FOR
 LTS AND RECEPTS TO BE DEDICATED.
 PLEASE ADJUST.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE SOME
 MENTION OF FC'S ARE NOTED ON PLANS,
 HOWEVER COMPLETE PHOTO-METRICS ARE
 NEEDED.
 PLEASE SUBMIT.
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE PHOTOMETRICS FOR
 COMMON AREAS FOR EGRESS LIGHTING. PLEASE
 SEE THIS WOULD INCLUDE LOBBY AREAS,
 STAIR TOWERS, SHOW ALL FT CANDLES TO THE
 EXIT/PUBLIC RIGHT OF WAY.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9
 WHICH REQUIRES 10 FT CANDLES UNDER
 NORMAL POWERE AND A MIN OF 1FT CANDLE
 UNDER EM POWER.
 PLEASE ALSO SEE FURTHER COMMENTS WIHT
 RESPECT TO FIXTURES.
  
 7)NOTE: OK
  
 8)NOTE: OK.
  
 9)NOTE: NOTE #9 OK, HOWEVER SEE NEW
 NOTES FOR ADDED CONDUCTORS.
  
 ** PREVIOUS NOTE**
 PLEASE SHOW THE CONDUCTORS FROM
 HOUSE GUTTER TO EACH DISCONNECT.
 215.5
  
 10)NOTE: NOTE #10, THIS HAS NOT YET BEEN
 CONFIRMED. PLEASE SEE PLANS AND
 PAPERWORK NOW MENTION BUILDING SHALL
 CONTAIN NEW "CONDO UNITS" AS SINGLE
 FANILY RESIDENCES.
 PLEASE SEE THE SD'S IN THE RES CONDO
 UNITS MAY BE REQUIRED TO BE 120V WIRED
 INLINE AND WITH ARC FAULT PROTECTION PER
 210.12B
 CONTACT TO THE FIRE MARSHAL'S OFFICE AND
 CHIEF CARSILLO WILL BE MADE.
 IT SEEMS IF THESE ARE NOW SFR CONDO'S,
 TRIPPING OF THE SD'S IN EACH UNIT UPON
 SOME COOKING PRACTICES ETC WOULD CREATE
 TRIPPING OF THE ENTIRE BUILDINGS FIRE
 ALARM SYSTEM??
  
  
 ** PREVIOUS NOTE **
 PLEASE VERIFY WITH THE FIRE
 MARSHAL'S OFFICE IF INDEED THE UNIT SD'S
 WILL BE TIED INTO BASE BLDG PROTECTION
 SYSTEM.
 PLEASE KNOW, IF THESE ARE 120V WIRED
 INLINE IN UNITS, THEN CIRCUITING WILL BE
 REQUIRED ALONG WITH ARC FAULT
 PROTECTION.
 215.5,210.12
 THIS WOULD ALSO BE AFFECTED BY THE
 "TOWNHOUSE" DECLARATION.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE: NOTE #17 NO, ALMOST ALL WERE
 DONE HOWEVER PLEASE SEE WALL SPACE 2' OR
 MORE EVEN BEHIND DOORS WILL BE REQUIRED
 TO HAVE A RECEPT. PLEASE SEE TWO
 REDLINED IN PH UNITS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.52 FOR RECEPTS
 MISSING FOR 2' OR MORE OF WALL SPACE.
 PLEASE SEE MOST IF THESE LOCATIONS ARE
 REDLINED ON PLANS. (SEE MOSTLY 3RD FLR.
  
 18)NOTE: OK.
  
 19)NOTE: OK, HOWEVER SEE NEW NOTES FOR
 DINGIN CIRCUITS ADDED.
  
 20)NOTE: OK.
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: NOTE #25 NO, COULD NOT FIND?
 RESPONSE MENTIONS THIS WAS ADDED?
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON PLANS FOR
 ALL SD'S TO BE INSTALLED PER 2002
 NFPA-72 11.8.3.5
  
 26)NOTE: NOTE #26 NO, AND NO RESPONSE
 WAS GIVEN FOR THE NOTE.
 THIS SHOULD BE ADDED TO NOTES ON E-10
  
 **PREIVOUS NOTE **
 PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
  
 *********** NEW NOTES ***********
  
 27) NOTE: PLEASE SEE DINING RM CIRCUITS
 AND THE LIKE SHALL BE SHOWN WITH THE MIN
 VA FIGURED FOR THE CIRCUIT AT 1.5VA.
 PLEASE SEE 210.52B1,210.11C1, 220.16
  
 28) NOTE: PLEASE SEE THE FOLLOWING CODES
 SHALL BE PRINTED ON ELECTRICAL PLANS.
 NFPA-101 2003,NFPA-72 2002, NFPA-70
 2002.
  
 29) NOTE: PLEASE SEE RISER IS NOW
 SHOWING "EQUIPMENT GROUNDING CONDUCTORS"
 FOR SEC'S FROM GUTTER TO MAINS FOR
 HOUSE.
 PLEASE SEE 250.6,250.24B , THESE ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 30) NOTE: PLEASE SEE WHAT APPEARS TO BE
 A MISPRINT FOR THE RISER NOTE #5,
 MENTIONS "MLB" , SHOULD THIS BE "MCB"?
  
 31) NOTE: PLEASE SEE CIRCUITS FOR GEN
 LTS AND RECEPTS SHALL BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THESE CIRCUITS
 ARE FEEDING. IE: MASTER BEDRM RECEPTS.
 BATH #2 LTS, KITCHEN LTS ETC.
 408.4
  
 32) NOTE: PLEASE KNOW, AS PLANS WERE
 INDEED SUBMITTED FOR PERMIT, PLEASE SEE
 COPY OF FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS THREE OR MORE TIMES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 *** IMPORTANT**
  
 WHEN RESUBMITTING PLANS, PLEASE BE SURE
 TO SUBMIT ONE COPY OF THE OLD PLANS FOR
 REFERENCE.
  
 ** PLEASE SEE ONE SET OF PLANS HAS MUCH
 OF THE ABOVE REDLINED FOR AREAS OF
 COMMENTS. THIS MAY HELP IN AREAS AS
 NOTED. (RECEPTS ETC)
  
 ** PLEASE KNOW, A RESPONSE LETTER WITH
 RESPECT TO COMMENTS AND WHAT ACTIONS
 WERE TAKEN WOULD GREATLY HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS.
 PLEASE KEEP IN MIND TO CLOUD/TRIANGLE
 ANY REVISED LOCATIONS ON PLANS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-25 Cont ID  
Sent By dpalmer Date 2005-12-25 Time 09:08 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 18:25 Sent To  
Notes
2005-12-25 00:00:00************ UNSAT *************
  
  
 DIXIE MEWS / AQUA TERRACE
  
 1)NOTE: PLEASE PROVIDE SIGNED, DATED AND
 SEALED PLANS BY ARCHITECT AND
 ENGINEER(S) OF RECORD.
 FS 481.221 AND 471.025
 PLEASE SEE PLANS CONTAIN SOME SORT OF
 "CORPORATE SEAL' WHICH IS NOT
 ACCEPTABLE.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADE REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE COMPLETE AND INCLUDE ALL
 INFORMATION ON SAID TITLE BLOCKS FOR
 ARCHITECTUAL AND ENGINEERING FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODES
 61G1-16.004 (ARCH) AND 61G15-23.002
 (ENG).
 PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES.
  
 3)NOTE: PLEASE SEE THERE IS REFERENCE TO
 BLDGS AS "TOWNHOUSES", PLEASE SEE THESE
 DO NOT APPEAR TO BE FEE SIMPLE?
 PLEASE SEE BUILDING AND ZONING COMMENTS
 AS THIS WILL COMPLETELY CHANGE
 ELECTRICAL DESIGN IF INDEED FEE SIMPLE
 "TOWNHOUSES".
  
 4)NOTE: PLEASE VERIFY CLEARENCES FOR
 ELECTRICAL SERVICE PER 110.26,
 APPEARS TO SHOW DOORS WHICH WILL SLIDE
 OPEN ON EACH SIDE, HOWEVER THIS WILL
 ALWAYS CREATE A COMMON POINT IN THE
 CENTER WHICH WOULD NOT MEET CODE.
 PLEASE PROVIDE AN ELEVATION AS HEIGHT
 AND WIDTH IS TO BE VERIFIED.
 PLEASE ALSO VERIFY IT APPEARS THIS
 ROOM/AREA IS ALSO THE GRESS FROM COMMON
 STAIR TOWER AND LOBBY AREA?
 PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE
 SEPARATION AS STAIRS EXIT INTO THIS AREA
 AND NO DOORS ARE SHOWN WHICH MAY ALLOW
 EXISTING BACK INTO COMMON LOBBY AREA
 PLEASE SEE THIS IS SHOWING SWITCHING FOR
 LTS?
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE CIRCUIT SHOWN.
  
 5)NOTE: PLEASE SEE HOUSE CIRCUIT SHOWN
 FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN
 FEEDING OTHER AREAS. PLEASE SEE 620.23
 WHICH REQUIRES THE BRANCH CIRCUIT FOR
 LTS AND RECEPTS TO BE DEDICATED.
 PLEASE ADJUST.
  
 6)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR
 COMMON AREAS FOR EGRESS LIGHTING. PLEASE
 SEE THIS WOULD INCLUDE LOBBY AREAS,
 STAIR TOWERS, SHOW ALL FT CANDLES TO THE
 EXIT/PUBLIC RIGHT OF WAY.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9
 WHICH REQUIRES 10 FT CANDLES UNDER
 NORMAL POWERE AND A MIN OF 1FT CANDLE
 UNDER EM POWER.
 PLEASE ALSO SEE FURTHER COMMENTS WIHT
 RESPECT TO FIXTURES.
  
 7)NOTE: PLEASE PROVIDE A FIXTURE
 SCHEDULE FOR ALL FIXTURES. PLEASE SEE
 COMPLIANCE FOR STAIR TOWERS, CLOSETS ETC
 NEED TO BE VERIFIED.
 215.5
  
 8)NOTE: PLEASE COMPLETE A/C CU LAYOUT ON
 ROOFTOP PLANS FOR ALL UNITS. 8 SHOWN
 WHICH SHOULD SHOW A TOTAL OF 16 UNITS TO
 CORRELATE WITH PANEL SCHEDULES AND
 UNITS.
 PLEASE ALSO CLARIFY CU DETAIL WHICH IS
 SHOWING THEDISCONNECTS BEING MOUNTED
 TO THE CU?
 PLEASE VERIFY OCP SHOWN AT 40A'S?(TYP)
 PLEASE SEE M-SHEETS WHICH SHOW MORE THAN
 ONE TYPE OF UNIT. 15A'S, 30A'S ETC.
 PLEASE ADJUST DISCONNECT DETAIL AS
 NEEDED.
 PLEASE SEE IF CHANGING OUT UNIT, UNIT
 WOULD STILL HAVE POWER COMING TO UNIT.
  
 9)NOTE: PLEASE SHOW THE CONDUCTORS FROM
 HOUSE GUTTER TO EACH DISCONNECT.
 215.5
  
 10)NOTE: PLEASE VERIFY WITH THE FIRE
 MARSHAL'S OFFICE IF INDEED THE UNIT SD'S
 WILL BE TIED INTO BASE BLDG PROTECTION
 SYSTEM.
 PLEASE KNOW, IF THESE ARE 120V WIRED
 INLINE IN UNITS, THEN CIRCUITING WILL BE
 REQUIRED ALONG WITH ARC FAULT
 PROTECTION.
 215.5,210.12
 THIS WOULD ALSO BE AFFECTED BY THE
 "TOWNHOUSE" DECLARATION.
  
 11)NOTE: PLEASE PROVIDE ALL AREA AND
 ROOM DESIGNATIONS ON PLANS FOR UNITS.
 NEED TO VERIFY CIRCUITING.
 215.5
  
 12)NOTE: PLEASE INCLUDE ELECTRICAL
 CONNECTION FOR JACUZZI, WILL THIS BE A
 HARDWIRED UNIT WITH A DISCONNECTING
 MEANS OR A RECEPT?
 PANEL SCHEDULE SHOWS THE GFI PROTECTION.
 PLEASE ALSO SEE ONLY THE CIRCUIT IS
 SHOWN ON PLANS.
 PLEASE SHOW THE ACCESS, PLEASE SEE SOME
 CIRCUIT #'S SHOWN APPEAR TO BE LOCATED
 AT THE REAR OF THE UNIT. IS THERE A
 CLOSET ACCESS.?
  
 13)NOTE: PLEASE VERIFY IN SOME UNITS A
 RECEPT IS BEING SHOWN IN CLOSET? CIRCUIT
 #1.
 PLEASE KNOW, IF THIS IS FOR A PLUG IN
 TYOE TRANSFORMER, THE LOCATION OF THE
 RECEPT WOULD ONLY BE PERMITTED DIRECTLY
 ABOVE THE DOOR OR RECEPT FOR ANY
 TRANSFORMER WOULD BE REQUIRED TO BE
 MOVED.
 PLEASE KNOW, THE PLUG IN TYPE
 TRANSFORMERS, MANY CONTAING OCP ETC
 BECOME EXTREMELY HOT AND HAVE MELTED IN
 THIS AND OTHER JURISTICTIONS CUASING
 FIRES.
 THE COMBUSTIBLES IN CLOSET AREA WOULD
 ONLY ACT AS AN ACCELERANT.
  
 14)NOTE: PLEASE SEE OTHER CLOSETS,
 MOSTLY IN UPPER UNITS ARE SHOWING LTS
 WHICH DO NOT MEET MIN CLEARENCE
 REQUIREMENTS PER 410.8. PLEASE ALSO SEE
 PREVIOUS COMMENT WITH RESPECT TO THE
 FIXTURE SCHEDULE TO BE PROVIDED FOR
 REVIEW.
  
 15)NOTE: PLEASE SEE SOME UNITS APPEAR TO
 SHOW SOME SORT OF CEILING LINE , AS IF
 THE HALL AREA CEILING MAY BE LOWER THAN
 ACTUAL BEDRM CEILING HEIGHTS?
 PLEASE SEE NFPA-72 11.8.3.5 WHICH
 REQUIRES ALL SD'S TO BE LOCATED AT THE
 HIGHEST POINT POSSIBLE ON A FLAT
 CEILING.
 IF WALL MOUNTED, THEN THIS WOULD REQUIRE
 THESE TO BE LOCATED WITHIN 12" OF
 CEILING BUT NOT CLOSER THAN 4" IF INDEED
 THE CEILINGS IN BEDRMS ARE HIGHER,
 PLEASE MOVE SD'S TO BE LOCATED TO MEET
 CODE.
  
 16)NOTE: PLEASE SEE A "NOTE" ON E-4
 WHICH MENTIONS A "CONTINUOUS ROW OF
 FLOUR LTS" ETC TO BE MOUNTED IN COVE?
 PLEASE KNOW, THESE COULD NOT BE LOCATED
 ON 2ND FLR OF UNITS AS NOTED.
 ONLY LOCATED ON E-3 2ND FLR COMMON AREA.
  
 17)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 MISSING FOR 2' OR MORE OF WALL SPACE.
 PLEASE SEE MOST IF THESE LOCATIONS ARE
 REDLINED ON PLANS. (SEE MOSTLY 3RD FLR.
  
 18)NOTE: PLEASE CLARIFYLOCATIONS OF
 WASHER/DRYERS ON 3RD FLR UNITS. PLANS
 SHOW THE LOCATION OF RECEPT FOR DRYERS,
 HOWEVER WITH THE LAYOUT AS SHOWN, THE
 DRYER WOULD NOT FIT IN THESE LOCATIONS??
  
 19)NOTE: PLEASE SEE 3RD FLR UNITS WHICH
 SHOW LIGHTING BEING CIRCUITED TO THE
 DINING RM / SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210.52B1 WHICH ONLY PERMITS
 THE RECEPTS WITH SOME EXCEPTIONS,
 HOWEVER LTS AS SHOWN MAY NOT BE ON THIS
 CIRCUIT. PLEASE ADJUST.
  
 20)NOTE: PLEASE SEE TOP FLR UNIT, WHICH
 DOES NOT SEEM TO SHOW A FIXTURE AT THE
 END OF THE SW LEG IN WHAT APPEARS TO BE
 A BEDRM.
 (MISPRINT).
  
 21)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED FORALL BUT
 HOUSE MAIN DISCONNECT.
  
 22)NOTE: PLEASE VERIFY THE CONNECTION
 POINT AS NOTED FOR GROUNDING ELECTRODE
 CONDUCTOR TO THE REBAR/FOOTER STEEL.
 IT IS UNCLEAR WHAT "THREE SETS OF WRAP
 TO BOND"? THIS METHOD IS UNLCEAR AND NOT
 KNOWN.
 PLEASE PROVIDE THE PERMITTED CONNECTION
 AS SET-FORTH IN THE NEC. 250.50 OR
 PROVIDE FUTHER DETAIL FOR THIS.
 ABOVE IS NOTED AS ALL CONNECTIONS BEING
 EXOTHERMIC, IS THIS FOR THIS LOCAITON
 ALSO?
  
 23)NOTE: PLEASE SEE PANEL "P" WHICH
 SHOWS THE LOAD FOR GEN LT AND RECEPTS,
 HOWEVER THEER SEEMS TO BE SOME SORT OF
 NUMERICAL NOTE ADDED TO THE CIRCUITS 2
 AND 4?
 MISPRINT? CLARIFY.
  
 24)NOTE: PLEASE SEE "CLUBHOUSE" PERMIT
 #05091714 FOR REVIEW.
  
 25)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL SD'S TO BE INSTALLED PER 2002
 NFPA-72 11.8.3.5
  
 ** PLEASE SEE ONE SET OF PLANS HAS MUCH
 OF THE ABOVE REDLINED FOR AREAS OF
 COMMENTS. THIS MAY HELP IN AREAS AS
 NOTED. (RECEPTS ETC)
  
 ** PLEASE KNOW, A RESPONSE LETTER WITH
 RESPECT TO COMMENTS AND WHAT ACTIONS
 WERE TAKEN WOULD GREATLY HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS.
 PLEASE KEEP IN MIND TO CLOUD/TRIANGLE
 ANY REVISED LOCATIONS ON PLANS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
2005-12-24 00:00:00IN ELEC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By rchokshi Date 2006-08-11 Time 11:42 Rev Time 0.00
Received By rchokshi Date 2006-08-11 Time 11:16 Sent To  
Notes
2006-08-11 00:00:00FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE RESPOND EACH ITEM LISTED BY M.
 AMINI ON OCT 14, 2005 IN HIS NOTES.
 2. DRAWINGS ARE NOT READABLE YOU
 SUBMITTED TO STEVE S. ON AUG 1, 06.
 3. NEED GEOTECHNICAL ENG. REPORT, HOW
 MANY CONTROL STRUCTURES ARE IN THE PLAN?
 PLEASE SHOW THE BLEEDING ELEVATIONS,
 OVERFLOW ELEVATIONS, & GEOMETRY ETC.
 4. NEED A FENCE AROUND THE SITE DURING
 CONSTRUCTION TIME FOR POLLUTION
 PREVENTION, ALSO ALL NOTES ON DRAWINGS
 FOR POLLUTION PREVENTION.
  
 PLEASE RESPOND EACH ITEM SO, WE CAN
 CLOSE THE PROJECT AS SOON AS POSSIBLE,
 THANKS, RASIK CHOKSHI 8056723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date 2005-10-14 Cont ID  
Sent By mamini Date 2005-10-14 Time 15:20 Rev Time 0.00
Received By mamini Date 2005-10-14 Time 15:20 Sent To  
Notes
2005-10-14 00:00:00FAILED:
  
 1. CIVIL PLANS MUST BE REVIEWED AND
 APPROVED FOR ALL THE CONNECTIONS TO THE
 CITY' SERVICES, 494-1085 ATT; MANNY
 GONZALEZ.
 2. PLEASE SUBMIT STORM WATER
 CALCULATIONS FOR OUR REVIEW AND
 APPROVAL.NOTE THAT SITE MUST BE
 DESIGNED PER CITY' REQUIREMENTS AND
 CRITERIA.CALC. MUST BE SIGNED AND
 SEALED BY THE C.E.O.R
 3. POLLUTION PREVENTION PLANS MUST BE
 INCLUDED IN CIVIL PLANS, SILT FENCE,
 TURBIDITY BARRIER, ECT..
 4.PLEASE SUBMIT A COPY OF THE SFWMD
 PERMIT, FOR OUR RECORD.
 5. PLEASE REFER TO ARCHITECTURAL PLANS
 FOR DUMPSTER ENCLOSURE'S DIMENSIONS.
 NOTE THAT, THEY MUST BE SIZED PER CITY
 REQUIREMENTS IF CITY PICK-UP.
 6. STREETSCAPING AND SIDEWALKS, ETC.
 MUST BE COORDINATED WITH LATEST FDOT
 PLANS FOR RECONSTRUCTION OF DIXIE AND
 GREGORY RD.
 7. CIVIL PLANS MUST BE INCLUDED IN ALL
 THREE SETS, ONLY ONE SET HAS THE CIVIL.
 8. NOTE THAT CITY'S STANDARDS AND
 DETAILS CAN BE OBTAINED FROM PUBLIC
 UTILITIES AND ENGINEERING , 494-1085.
 9.FIRE HYD. MUST BE PROVIDED
 THROUGHOUT THE PROPOSED SITE.
 10. DOMESTIC WATER SYS. AS PROPOSED;
 METERS AND DDCV LOCATIONS ECT. MUST BE
 VERIFIED WITH PUBLIC UTILITIES AND
 ENGINEERING.
 11. ALL VERTICAL CLEARANCES FOR
 UNDERGROUND UTILITIES MUST BE SHOWN.
 12. A SEPARATE R.O.W PERMIT FOR ALL THE
 WORKS WITHIN PUBLIC R.O.W IS REQUIRED;
 CONTACT PUBLIC UTILITIES AND ENGINEERING
 AT MIN. 48HR PRIOR TO ANY WORK BEGINS,
 494-1086, WINDEL PALMER. NOTE TO G.C
 13. ACCESS RAMP PER INDEX 304 FDOT TO
 THE SITE MUST BE PROVIDED.
 14. DETAILS FOR THE STOP AND HANDICAP
 SIGNS SHOULD BE INCLUDED IN CIVIL, AND
 NOTE THAT PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WIDE, DETAILS SHOULD BE
 SHOWN.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2006-07-18 Time 14:30 Sent To  
Notes
2006-07-18 00:00:00***DENIED***
  
 PLEASE NOTE THAT A RESPONSE LETTER
 ADDRESSING THE FIRE REVIEW WAS NOT FOUND
 WITH THIS SUBMITTAL. PLEASE BE ADVISED
 THAT THIS WILL HELP EXPEDITE THE PLAN
 REVIEW PROCESS.
  
 1) COMPLETE CIVIL DRAWINGS ARE TO BE
 SUBITTED ILLUSTRATING FIRE HYDRANTS AND
 WATER AND FIRE MAIN SIZES. ALL BACK FLOW
 PREVENTION DEVICES ARE TO BE SHOWN.
  
 2) FIRE HYDRANT SPACING IS NOT TO EXCEED
 300-500' APART.
  
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 4) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR EMERGENCY
 EQUIPMENT.
  
 5) BUILDING ADDRESSES ARE REQUIRED. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 6) ALL FIRE HYDRANTS ARE TO BE PROVIDED
 WITH PROPER CLEARANCES TO THE FRONT AND
 SIDES OF THEM.
  
 7) ALL HANDRAILS AND GUARDS ARE TO MEET
 PRESCIPTIVE STRENGTH REQUIREMENTS PER
 THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 8) PLEASE EXPLAIN STORAGE AREAS NEAR
 EXIT STAIRS LOCATED ON THE SECOND FLOOR,
 CENTER CORE.
  
 9) A COMPLETE AUTOMATIC SUPERVISED FIRE
 SPRINKLER SYSTEM IS REQUIRED IN ALL (3)
 STORY BUILDINGS. PLEASE COMPLETE PLANS
 AND PERMITS AS REQUIRED.
  
 10) THE FIRE ALARM SYSTEM IS TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE. COMPLETE PLANS AND
 PERMITS REQUIRED PRIOR TO INSTALLATION.
  
 11) FIRE LINE BACKFLOW DEVICE SHALL BE
 EQUIPPED WITH TAMPER SWITCHES, CHAIN AND
 LOCK.
  
 12) A REVIEW OF THE CIVIL DRAWINGS
 INDICATE THAT ADDITIONAL FIRE HYDRANTS
 ARE NEEDED. FIRE DEPARTMENT SPRINKLER
 CONNECTIONS SHALL BE LOCATED NO FURTHER
 THAN 150' FROM A FIRE HYDRANT.
  
 13) THERE APPEARS TO BE NO FIRE HYDRANTS
 LOCATED ON THE APPROACH OR INTO THE
 COMPLEX.
  
 14) ALL SMOKE DETECTORS ARE TO BE
 INSTALLED A MINIMUM OF (3)' FROM HVAC
 DIFFUSERS.
  
 15) FIRE ALARM VISIBLE SIGNALS SHALL BE
 PROVIDED IN ROOMS DESIGNED FOR THE
 HEARING IMPAIRED.
  
 16)PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 17) ALL RESIDENTIAL BUILDINGS ARE TO
 COMPLY WITH CHAPTER 30, NFPA 101, 2003
 EDITION.
  
 18) ALL COMMON BUILDING STAIRS ARE TO BE
 PROVIDED WITH EMERGENCY LIGHTING
 EQUIPMENT.
  
 19) PLEASE EXPLAIN EXIT DISCHARGE FROM
 COMMON STAIRS. IT APPEARS THAT BOTH
 EMPTY INTO THE BUILDING. PLEASE EXPLAIN
 WHAT ALLOWS THIS TO OCCUR.
  
 20) EMERGENCY INSTRUCTIONS FOR RESIDENTS
 OR GUESTS ARE REQUIRED.
  
 21) KNOX BOXES WILL BE REQUIRED FOR THE
 COMMON ELEMENTS OF THE BUILDING.
  
 22) PORTABLE FIRE EXTINGUISHERS WITH BE
 REQUIRED.
  
 23) ARE THE GARAGE DOORS PROPERLY RATED?
 IT APPEARS THAT THE DOOR SCHEDULE
 DISPLAYS 45 MINUTES BUT THE GARAGE WALL
 IS OF GREATER VALUE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 16:29 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 11:45 Sent To  
Notes
2006-05-01 00:00:00WAITING FOR "COMM" BD
2005-10-05 00:00:00TO "COMM" BD#23/PLANS ON RACK/1 ROLL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-05 Cont ID  
Sent By pkrauss Date 2006-07-05 Time 15:08 Rev Time 0.00
Received By pkrauss Date 2006-07-05 Time 15:08 Sent To  
Notes
2006-07-05 00:00:00DENIED:2001 FBC/BUILDING #3
 RESPONSE TO COMMENTS DATED 1/13/06
  
 COMMENT #1 - OK
 COMMENT #2 - OK
 COMMENT #3 - OK
 COMMENT #4 - OK PLEASE CLARIFY PLAN
 SHEET M-8 EXHAUST DUCT ROOF CAP DETAIL.
 WILL EACH TOILET EXHAUST TERMINATE TO
 THE OUTDOORS OR WILL THIS BE A
 'SUB-DUCT' METHOD?
 COMMENT #5 - OK
 COMMENT #6 - OK
 COMMENT #7 - PLEASE DNOTE, THE 2001 FMC
 DOES NOT GIVE THE OPTION FOR THE
 INSTALLATION OF BOOSTER FANS ON THE
 DRYER EXHAUST.THIS MUST BE SUBMITTED
 TO THE BUILDING OFFICAL UNDER "ALTERNATE
 MATERIALS & METHODS" 2001 AMENDMENTS TO
 THE 2001 FBC 103.7.1.PLEASE PROVIDE
 SUBMITTAL FOR THE BOOSTER FAN.NOTE #3
 ON M-3 INDICATES THE BOOSTER FAN IS
 "MANUFACTURER'S RECOMMENDED" UL LISTED
 BOOSTER FAN.PLEASE ALSO PROVIDE A
 LETTER FROM AN ENGINEER EMPLOYED BY THE
 MANUFACTURER GIVING THE MANUFACTURER'S
 APPROVAL FOR THIS INSTALLATION.
 COMMENT #8 - OK
 COMMENT #9- PLEASE NOTE, SHAFT
 ENCLOSING THE REFRIGERANT LINES SHALL BE
 VENTED IN ACCORDANCE WITH ASHRAE 15-1992
 SECTUIB 11.12.3 (B).
 COMMENT #10 - OK
 COMMENT #11 - AHU-L DUCT SHALL BE IN A
 RATED SHAFT IN ACCORDANCE WITH 2001 FMC
 607.4.
 COMMENT #12 - OK
 COMMENT #13 - RESPONSE INDICATES PRODUCT
 APPROVAL FOR THE CONDENSING UNIT STANDS
 IS ATTACHED TO THE PLANS.PLEASE NOTE,
 PRODUCT APPROVAL IS NOT ATTACHED TO
 PERMIT APPLICATION OR PLAN.PLEASE
 PROVIDE FLORIDA STATE PRODUCT APPROVAL.
 COMMENT #14 - OK
 COMMENT #15 - OK
 COMMENT #16 - OK
 COMMENT #17 - OK
 COMMENT #18 - RESPONSE INDICATES FLOAT
 SWITCH FOR OVERFLOW PROTECTION.PLEASE
 INDICATE LOCATION OF THE FLOAT SWITCH.
 PLEASE NOTE, FLOAT SWITCH IS NOT TO BE
 INSTALLED IN THE PRIMARY DRAIN PAN.IT
 SHALL BE INSTALLED IN THE OVERFLOW OR
 SECONDARY DRAIN SHOULD THIS UNIT BE A
 BOTTOM RETURN. SHOULD THE RETURN BE
 LOCATED IN THE SIDE AN AUXILIARY DRAIN
 PAN WILL BE REQUIRED.
  
 ****************NEW COMMENTS************
 19. PLAN SHEET M-3 NOTE 2 INDICATES
 RETURN AIR THROUGH LOUVERED DOOR AT THE
 AHU CLOSET.PLEASE NOTE, LOUVERED DOOR
 & FRAME SHALL BE NON-COMBUSTIBLE AS
 REQUIRED PER 2001 FMC 602.2.1.
  
 20. PLAN SHEET M-5 SHOWS REFRIGERANT
 LINES THROUGH THE STAIRWELL.PER 2001
 FBC 1006.1.3.1 THIS IS PROHIBITED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATT KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-13 Cont ID  
Sent By pkrauss Date 2006-01-13 Time 09:58 Rev Time 0.00
Received By pkrauss Date 2006-01-13 Time 09:58 Sent To  
Notes
2006-01-13 00:00:00DENIED:
 PLANS REVIEWED UNDER THE 2004 FBC.
 PLANS DO NOT INDICATE WHICH CODE THE
 BUIDLINGS ARE DESIGNED.
  
 1.PROVIDE BUILDING TYPE, INDICATE
 PROTECTED OR UNPROTECTED.
  
 2.PLAN SHEET A2 SEPARATION BETWEEN THE
 GARAGE AND THE RESIDENCE IS INDICATED AS
 A 2 HOUR SEPARATION ACCORDING TO THE
 WALL TYPE LISTED ON PLAN SHEET A-26.
 MECHANICAL PLAN M1 INDICATES DUCTWORK
 PENETRATING RATED WALL WITHOUT
 PROTECTION.PLEASE INDICATE ON THE
 PLANS COMPLIANCE WITH ALL THE
 REQUIREMENTS LISTED UNDER 2004 FMC
 607.5.3 EXCEPTIONS 1 AND 2.
  
 3.PLANS SHEET M-1 INDICATES BATHROOM
 EXHAUST PENETRATING THROUGH 2ND & 3RD
 FLOORS TO THE ROOF.PLEASE INDICATE
 PROTECTION THROUGH RATED FLOOR.
  
 4.PLAN SHEET M-3 & M-5 INDICATES
 REFRIGERANT LINES & EXHAUST DUCT IN A
 "CHASE".PLEASE CLARIFY IN THE "CHASE"
 IS RATED.SHOW COMPLIANCE WITH 2004 FMC
 607.5.5.1.PLEASE NOTE, FIRE DAMPERS &
 ACCESS DOORS ARE REQUIRED TO BE
 INDENTIFFIED ON PLANS PER 2004 FMC
 607.8.
  
 5.PLEASE NOTE, EXHAUST DUCT SHALL
 COMPLY WITH 2004 FMC 501.4.
  
 6.PLAN SHEET M-1 INDICATES "MATCH
 LINE" M-2.M-2, M-4 & M-6 WERE NOT
 SUBMITTED FOR
 REVIEW.
  
 7.PLAN SHEET M-3, DRYER EXHAUST
 APPEARS TO EXCEED THE 25FT REQUIREMENT
 IN 504.6 OF THE 2004 FMC.
  
 8.PLAN SHEET M-3 & M-5 INDICATES
 REFRIGERANT LINES & EXHAUST DUCT IN A
 "CHASE".PLEASE CLARIFY IF THE "CHASE"
 IS RATED.SHOW COMPLIANCE WITH 2004 FMC
 607.5.5.1.PLEASE NOTE, FIRE DAMPERS &
 ACCESS DOORS ARE REQUIRED TO BE
 IDENTIFIED ON PLANS PER 2004 FMC 607.8.
  
 9.PLEASE PROVIDE A DETAIL OF THE
 TERMINATION OF REFRIGERANT LINES &
 EXHAUST DUCT LOCATED ON THE ROOF IN THE
 HVAC EQUIPMENT ROOM.
  
 10. PER 2004 FMC 501.2, EXHAUST AIR
 SHALL BE DISCHARGED TO THE OUTDOORS AT A
 POINT WHERE IT WILL NOT CREATE A
 NUISANCE OR CANNOT BE READLY DRAWN IN BY
 THE VENTILATING SYSTEM.
  
 11. PLAN SHEET M-3 AHU-L DUCT PENETRATES
 FLOOR AND CEILING PLEASE SHOW COMPLIANCE
 WITH 2004 FMC 607.6.
  
 12. PLEASE CLARIFY THE HVAC EQUIPMENT
 ROOMS LOCATED ON THE ROOF.THE
 CONDENSING UNITS ARE LOCATED IN THE
 EQUIPMENT ROOMS.WILL THIS BE ENCLOSED?
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 FOR THE CONDENSERS INDICATING THEY ARE
 PERMITTED TO BE INSTALLED IN AN ENCLOSED
 AREA WHICH ESSENTIALLY IS INDOORS.
  
 13. PLEASE PROVIDE DETAIL OF THE
 MOUNTING OF THE CONDENSING UNITS.
  
 14. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 403.3.
  
 15. PLAN SHEET M-3 RETURN AIR FROM THE
 BEDROOM AREAS ARE NOT SIZED PROPERLY.
 RETURN AIR "JUMPERS" SHALL COMPLY WITH
 2004 FMC 601.4 EXCEPTION #1.
  
 16. PLAN SHEET M-3 THE MASTER SUITE
 SHALL BE SIZED IN ACCORDANCE WITH 2004
 FMC 601.4 EXCEPTION 1 AND 3.PLEASE
 REVISE.
  
 17. PLAN SHEET M-5 RETURN AIR FROM THE
 BOTH BEDROOMS SHALL COMPLY WITH 2004 FMC
 601.4 EXCEPTION 1 AND 3.
  
 18. AUH DETAIL DOES NOT INDICATE
 OVERFLOW PROTECTION PER 2004 FMC
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-16 Cont ID  
Sent By pschmitz Date 2006-07-16 Time 09:41 Rev Time 0.00
Received By pschmitz Date 2006-07-16 Time 09:40 Sent To  
Notes
2006-07-16 00:00:00PAUL SCHMITZ
 FBC 2001 FUEL GAS CODE PLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
  
 UNSAT
 THE FOLLOWING COMMENTS HAVE NOT BEEN
 ADDRESSED, FROM PREVIOUS PLAN REVIEW
 DATED 01-25-06 BY KEN STEVENS.
  
 3. SHT 1 & 2 OF 7 AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE OF EACH
 BUILDING. SECTION 608.13.2.
  
 6. SHT A.18 LAVS IN THE POWDER ROOMS OF
 THE TOWNHOUSES SHALL BE COVERED PER FHA
 DESIGN MANUAL PAGES 7, 7.33, & 7.35
 EXCEPTION. LAV SHALL BE CENTERED ON THE
 48" LENGTH OF THE PARALLEL CLEAR FLOOR
 SPACE, OR BE A FRONTAL APPROACH. PAGE
 7.47. LAVS SHALL BE 34" TO RIM PER PAGE
 7.52. (SEE DETAIL #2).
  
 7. SHT A.18 FIRST DETAIL #3, SHOWER
 CLEAR FLOOR SPACE SHALL BE PARALLEL TO
 THE FIXTURE AND FLUSH WITH THE CONTROL
 WALL. PAGE 7.56. LAV PARALLEL CLEAR
 FLOOR SPACE SHALL BE CENTERED ON THE LAV
 A MINIMUM OF 2' OFF THE WALL. INDICATE
 MEASUREMENT FROM WALL TO CENTER OF LAV
 FOR ALL DETAILS.
  
 9. SHT A.19 ALL BATHROOM DETAILS, SHOW
 HEIGHT OF LAVS. ALL W/C'S TO BE 18" OFF
 WALL TO CENTER OF FIXTURE & MEASUREMENTS
 FOR ALL W/C OPENINGS TO SHOWN ON PLANS.
 MINIMUM 33" REQUIRED. SEE PAGES 7.43,
 7.44, 7.45, & 7.46.
  
 16. SHTS P-9 & P-10 WATER RISER DIAGRAM
 ISOMETRICS, AIR CHAMBERS ARE NOT
 APPROVED. AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9, (W/M, ICE
 MAKER, DISHWASHER), SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 18. SUBMIT A WATER HEATER DETAIL SHOWING
 ALL PIPE SIZES, VALVES, THERMAL
 EXPANSION CONTROL, P/T VALVE SHOWING
 PIPING AND INDICATING THE TERMINATION
 POINT. SECTIONS 104.2.1, 504.7.1, AND
 607.3.2.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-26 Cont ID  
Sent By kstevens Date 2006-01-26 Time 07:28 Rev Time 0.00
Received By kstevens Date 2006-01-26 Time 07:28 Sent To  
Notes
2006-01-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS 1 THRU 7 (CIVIL) SHEETS, THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED
 ON THE TITLE BLOCK OF EACH SHEET. FAC
 61G15-23.003 & FS 471.025.
 2. SHT 1 OF 7 PROPOSED CLUBHOUSE SHOWS
 NO SANT. OR WATER SERVICE. PLEASE
 CLARIFY. SECTION 104.2.1.
 3. SHT 1 & 2 OF 7 AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE OF EACH
 BUILDING. SECTION 608.13.2.
 4. SHT SP-1, SP-2, A1 THRU A.28
 ARCHITECTS BUSINESS NUMBER IS REQUIRED
 IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219.
 5. SHT A-7 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SF OF EACH DRAINED AREA, WITH 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND AREA OFF ROOFS THAT DRAIN
 ONTO THE ROOF AREAS FROM ABOVE IN
 CALCULATIONS. SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS/SCUPPERS. INDICATE
 THE SF OF STAIR ROOF, AND SHOW THE SIZE
 OF THE GUTTERS, SIZE OF DOWNSPOUTS,
 SLOPE OF GUTTERS AND INDICATE HIGH POINT
 OF GUTTERS. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 6. SHT A.18 LAVS IN THE POWDER ROOMS OF
 THE TOWNHOUSES SHALL BE COVERED PER FHA
 DESIGN MANUAL PAGES 7, 7.33, & 7.35
 EXCEPTION. LAV SHALL BE CENTERED ON THE
 48" LENGTH OF THE PARALLEL CLEAR FLOOR
 SPACE, OR BE A FRONTAL APPROACH. PAGE
 7.47. LAVS SHALL BE 34" TO RIM PER PAGE
 7.52. (SEE DETAIL #2).
 7. SHT A.18 FIRST DETAIL #3, SHOWER
 CLEAR FLOOR SPACE SHALL BE PARALLEL TO
 THE FIXTURE AND FLUSH WITH THE CONTROL
 WALL. PAGE 7.56. LAV PARALLEL CLEAR
 FLOOR SPACE SHALL BE CENTERED ON THE LAV
 A MINIMUM OF 2' OFF THE WALL. INDICATE
 MEASUREMENT FROM WALL TO CENTER OF LAV
 FOR ALL DETAILS.
 8. SHT A.18 DETAIL #4, A 60" DIAMETER
 TURNING CIRCLE IS REQUIRED IN A "U"
 SHAPED KITCHEN THAT HAS A SINK, RANGE,
 OR COOKTOP AT ITS BASE. THIS IS IN
 ADDITION TO THE CLEAR FLOOR SPACE. PAGE
 7.9.
 9. SHT A.19 ALL BATHROOM DETAILS, SHOW
 HEIGHT OF LAVS. ALL W/C'S TO BE 18" OFF
 WALL TO CENTER OF FIXTURE & MEASUREMENTS
 FOR ALL W/C OPENINGS TO SHOWN ON PLANS.
 MINIMUM 33" REQUIRED. SEE PAGES 7.43,
 7.44, 7.45, & 7.46.
 10. ALL E,M & P SHEETS. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER ON EACH SHEET. FAC
 61G15-23.002(2) & FAC 471.025.
 11. SHTS P-3 & P-4 SHOWS 4" UP TO THE
 3RD FLOOR FOR THE SANT. RISER. P-5 & P-6
 SHOW 3" ON ALL. PLEASE CORRELATE SECTION
 104.2.1.
 12. SHT P-7 SHOW 3" RWLS ROOF DRAINS
 ISOMETRIC AS "3" RWL BELOW SLAB" PLEASE
 CLARIFY. SECTION 104.2.1.
 13. SHT P-7 SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS/SCUPPERS. SHOW THE
 SIZE OF EACH DRAIN OR THE HEIGHT & WIDTH
 OF EACH SCUPPER, PIPING WITH SIZING,
 MEASUREMENT OFF THE ROOF TO THE FLOW
 LINE ETC. SECTIONS 104.2.1, 1106, & 1107
 14. SHT P-8 SANT. RISER DIAGRAM
 ISOMETRIC DOES NOT REFLECT THE FLOOR
 PLANS. THE RISER NUMBERS ARE OPPOSITE OF
 THE FLOOR PLANS. THE LAYOUTS OF SOME
 UNITS ON THE 1ST FLOOR DO NOT REFLECT
 THE FLOOR PLAN. THE SECOND FLOOR RISER
 DOES NOT REFLECT THE FLOOR PLAN AS THEY
 ARE OPPOSITE OF THE FLOOR PLAN ON MOST
 RISERS, AND SOME RISERS ARE MISSING
 FIXTURES & RISERS. 3RD FLOOR RISERS ARE
 OPPOSITE OF FLOOR PLAN. CORRELATE THE
 RISER DIAGRAMS WITH THE FLOOR PLANS,
 CHECK ALL PIPE SIZES WITH FLOOR PLANS.
 INDICATE DFUS AS THEY ACCUMULATE IN THE
 SYSTEM.SECTION 104.2.1 AND TABLE
 710.1(1).
 15. SHTS P-9 & P-10 WATER RISER DIAGRAM
 ISOMETRIC DOES NOT REFLECT THE FLOOR
 PLAN. RISER SHOWS 1" COLD WATER SERVICE
 UP TO PENTHOUSE LEVEL, BUT FLOOR PLAN
 SHOWS 1-1/2" COLD WATER SERVICE UP TO
 PENTHOUSE LEVEL ON SHTS P-1 THRU P-4.
 PLEASE CORRELATE FLOOR PLANS AND RISER
 DIAGRAMS.
 16. SHTS P-9 & P-10 WATER RISER DIAGRAM
 ISOMETRICS, AIR CHAMBERS ARE NOT
 APPROVED. AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9, (W/M, ICE
 MAKER, DISHWASHER), SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 17. SHT P-9 SHOWN THE WATER HEATERS IN
 AN EMERGENCY PAN, WHERE AS P-10 SHOWS NO
 PAN. W/H'S ON THE FIRST FLOOR ARE DO NOT
 REQUIRE A HEATER PAN UNLESS THEY ARE ON
 A SHELF. PLEASE CLARIFY. SECTIONS
 104.2.1. & 504.8.
 18. SUBMIT A WATER HEATER DETAIL SHOWING
 ALL PIPE SIZES, VALVES, THERMAL
 EXPANSION CONTROL, P/T VALVE SHOWING
 PIPING AND INDICATING THE TERMINATION
 POINT. SECTIONS 104.2.1, 504.7.1, AND
 607.3.2.
 19. SHT P-11 PLUMBING GENERAL NOTES:
 E-22 AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM REFERENCE. SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By eschneid Date 2006-07-20 Time 19:24 Rev Time 0.00
Received By eschneid Date 2006-07-20 Time 19:24 Sent To  
Notes
2006-07-20 00:00:001) THE CLUBHOUSE SIZE ON THE ENGINEERING
 PLAN DOES NOT MATCH THE CLUBHOUSE SIZE
 ON THE SITE AND LANDSCAPE PLANS. REPEAT
 COMMENT.
  
 2) SHOW DIMENSION LINES FOR ALL DRIVE
 AISLES AND DRIVEWAYS ON THE ENGINEERING
 PLANS.THE GREGORY ROAD ENTRY SCALES AT
 24 FEET WIDE ON THE ENGINEERING PLANS
 AND IS DIMENSIONED AT 22 FEET ON THE
 SITE PLAN. REPEAT COMMENT.
  
 3) PLEASE NOTE THAT WHEEL STOPS SHALL BE
 24 INCHES FROM THE ENDS OF THE PARKING
 SPACE.DISABLED LOGO SHALL BE 24 INCHES
 FROM THE PARKING SPACE ENTRANCE.
  
 4) PLEASE SHOW ELEVATION MARK FOR THE
 BUILDINGS ON ALL OF THE ELEVATION
 SHEETS.THE ADDITIONAL ELEVATION MARKS
 SHALL SHOW THE HIGHEST RIDGE HEIGHT AND
 THE HEIGHT TO THE TOP OF THE ROOFTOP
 MECHANICAL ROOM. REPEAT COMMENT.
  
 5) PLEASE NOTE THAT A RECORDED BOUNDARY
 PLAT IS REQUIRED PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT. REPEAT COMMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-03 Cont ID  
Sent By eschneid Date 2006-02-03 Time 16:18 Rev Time 0.00
Received By eschneid Date 2006-02-03 Time 16:18 Sent To  
Notes
2006-02-03 00:00:001) THE CLUBHOUSE SIZE ON THE ENGINEERING
 PLAN DOES NOT MATCH THE CLUBHOUSE SIZE
 ON THE SITE AND LANDSCAPE PLANS.
  
 2) SHOW DIMENSION LINES FOR ALL DRIVE
 AISLES AND DRIVEWAYS ON THE ENGINEERING
 PLANS.THE GREGORY ROAD ENTRY SCALES AT
 24 FEET WIDE ON THE ENGINEERING PLANS
 AND IS DIMENSIONED AT 22 FEET ON THE
 SITE PLAN.
  
 3) THE APPROVED ELEVATIONS REQUIRE A
 SINGLE GARAGE DOOR FOR EACH INTERIOR
 PARKING SPACE.THE PLANS SUBMITTED FOR
 PLAN REVIEW SHOW DOUBLE GARAGE DOORS.
 THIS NEEDS TO BE CORRECTED.
  
 4) PLEASE SHOW ELEVATION MARK FOR THE
 BUILDINGS ON ALL OF THE ELEVATION
 SHEETS.THE ADDITIONAL ELEVATION MARKS
 SHALL SHOW THE HIGHEST RIDGE HEIGHT AND
 THE HEIGHT TO THE TOP OF THE ROOFTOP
 MECHANICAL ROOM.
  
 5) PLEASE NOTE THAT A RECORDED BOUNDARY
 PLAT IS REQUIRED PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.