Plan Review Details - Permit 05091674
Plan Review Stops For Permit 05091674
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-10-25 Cont ID  
Sent By lursu Date 2006-10-25 Time 13:11 Rev Time 0.00
Received By lursu Date 2006-10-25 Time 13:11 Sent To PC
Notes
2006-10-25 13:12:03ADDRESS HAD BEEN CHNAGED FROM 955 28TH ST TO 955
 SERVICE ST , SINCE THE MAIN ENTRANCE FOR THIS PROJECT
 IS FROM SERVICE ST.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 13:40 Rev Time  
Received By shill Date   Time 11:30 Sent To  
Notes
2006-08-04 00:00:00PARCEL WILL BE CONDO PER CONTRACTOR; NO
 EXTENSIONS GIVEN TO BAYS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 09:48 Rev Time 0.00
Received By shill Date 2008-08-04 Time 09:48 Sent To  
Notes
2008-08-04 09:48:39REVISION, SHEET C1

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-07-15 Cont ID  
Sent By shill Date 2008-07-15 Time 08:58 Rev Time 0.00
Received By shill Date 2008-07-15 Time 08:58 Sent To ENG
Notes
2008-07-15 09:00:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.FBC11-4.6.2, IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES. BOTH PARKING SPACES ARE SHOWN IN
 ONE ADJACENT PARKING AREA, BUT THERE ARE SEVERAL OTHER
 ADJACENT PARKING AREAS.PARKING IS TO BE DISPERSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-02-20 Cont ID  
Sent By shill Date 2008-02-20 Time 15:51 Rev Time 0.00
Received By shill Date 2008-02-20 Time 15:51 Sent To  
Notes
2008-02-20 15:54:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.A SEPARATE PERMIT IS REQUIRED FOR AWNINGS.
  
 2.PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1.THE INSTRUCTIONS SHOULD
 CONSIST OF A SERIES OF PHOTOGRAPHS AS WELL AS WRITTEN
 INSTRUCTIONS.THIS IS TO BE APPROVED BY THE BUILDING
 OFFICIAL.
  
 3.AWNING ENGINEERING IS TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-27 Cont ID  
Sent By shill Date 2007-08-27 Time 08:29 Rev Time 0.00
Received By shill Date 2007-08-27 Time 08:29 Sent To  
Notes
2007-08-27 08:29:28REVISION; CLARIFICATION LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-18 Cont ID  
Sent By shill Date 2006-10-18 Time 13:08 Rev Time 0.00
Received By shill Date 2006-10-18 Time 11:57 Sent To  
Notes
2006-10-18 13:09:57NO ROOFING PRODUCT APPROVALS, SEPARATE PERMIT, PAS TO
 BE REVIEWED BY DOR PRIOR TO SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 11:27 Rev Time 0.00
Received By shill Date 2006-08-04 Time 11:27 Sent To  
Notes
2006-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED
 IS EXPIRED; OVER 90 DAYS WITHOUT
 COMMENCING WORK, FS713.13(2).
  
 2.)SEPARATE PERMITS FOR EACH BUILDING
 AND THE DUMPSTER WILL BE REQUIRED FOR
 INSPECTION PURPOSES.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 3.)ADDRESSED.
  
 4.)PER HAROLD PISKURA, THIS WILL NOT
 BE A RESIDENT INSPECTOR JOB AT THIS
 TIME.
  
 5.)ADDRESSED.
  
 6.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR PERMITTING, FBC*106.3.3.
  
 NEW COMMENT: FIRST REVIEW WAS IN
 JANUARY. IN FEBRUARY THE STATE OF
 FLORIDA INFORMED ME THAT THE 2001
 FLORIDA STATE PRODUCT APPROVALS WERE NO
 LONGER GRANDFATHERED IN. PLEASE PRINT
 THE 2004 FLORIDA STATE PRODUCT
 APPROVALS.
  
 7.-15.)ADDRESSED.
  
 16.)FOR THE ROOF, INDICATE WHICH
 APPROVED ASSEMBLY YOU ARE USING IN THE
 PRODUCT APPROVAL.
  
 2ND REVIEW - YOU HAVE HIGHLIGHTED ONE OF
 THE COMPONENTS.PLEASE CHOOSE AN
 APPROVED ASSEMBLY, BETWEEN PAGES 9-16.
  
 NEW COMMENT:
  
 17.)YOU HAVE DECLARED A TYPE VA IN
 RESPONSE TO ANOTHER COMMENT.THIS
 REQUIRES 1 HOUR FOR STRUCTURAL ELEMENTS
 LISTED IN FBC TABLE 601.PROVIDE
 CALCULATED FIRE RESISTANCE OR APPROVED
 ASSEMBLY, DETAILS, AND NOTE ON THE PLAN.
 SHOW ALL REQUIRED OPENING PROTECTIVES
 AND DETAILS FOR PENETRATIONS.
  
 18.) IF YOU CHANGE THE BUILDING TYPE,
 PLEASE SHOW COMPLIANCE WITH FBC TABLE
 602 AS WELL AS FBC TABLE 503.
  
 19.)SP1, NOTE DISTANCE FROM THE
 PROPERTY LINE FOR BUILDING 2 AND
 BUILDING 3.ALSO PLEASE MARK BUILDING
 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 11:19 Rev Time 0.00
Received By shill Date 2006-08-04 Time 11:19 Sent To  
Notes
2006-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED
 IS EXPIRED; OVER 90 DAYS WITHOUT
 COMMENCING WORK, FS713.13(2).
  
 2.)SEPARATE PERMITS FOR EACH BUILDING
 AND THE DUMPSTER WILL BE REQUIRED FOR
 INSPECTION PURPOSES.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 3.)ADDRESSED.
  
 4.)FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, 805-6711.
 ARESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT, DUE TO ONE OR
 MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 5.)ADDRESSED.
  
 6.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR PERMITTING, FBC*106.3.3.
  
 NEW COMMENT: FIRST REVIEW WAS IN
 JANUARY. IN FEBRUARY THE STATE OF
 FLORIDA INFORMED ME THAT THE 2001
 FLORIDA STATE PRODUCT APPROVALS WERE NO
 LONGER GRANDFATHERED IN. PLEASE PRINT
 THE 2004 FLORIDA STATE PRODUCT
 APPROVALS.
  
 7.-15.)ADDRESSED.
  
 16.)FOR THE ROOF, INDICATE WHICH
 APPROVED ASSEMBLY YOU ARE USING IN THE
 PRODUCT APPROVAL.
  
 2ND REVIEW - YOU HAVE HIGHLIGHTED ONE OF
 THE COMPONENTS.PLEASE CHOOSE AN
 APPROVED ASSEMBLY, BETWEEN PAGES 9-16.
  
 NEW COMMENT:
  
 17.)YOU HAVE DECLARED A TYPE VA IN
 RESPONSE TO ANOTHER COMMENT.THIS
 REQUIRES 1 HOUR FOR STRUCTURAL ELEMENTS
 LISTED IN FBC TABLE 601.PROVIDE
 CALCULATED FIRE RESISTANCE OR APPROVED
 ASSEMBLY, DETAILS, AND NOTE ON THE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-13 Cont ID  
Sent By shill Date 2006-01-13 Time 11:36 Rev Time 3.00
Received By shill Date 2006-01-13 Time 11:36 Sent To  
Notes
2006-01-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED
 IS EXPIRED; OVER 90 DAYS WITHOUT
 COMMENCING WORK, FS713.13(2).
  
 2.)SEPARATE PERMITS FOR EACH BUILDING
 AND THE DUMPSTER WILL BE REQUIRED FOR
 INSPECTION PURPOSES.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 3.)LANDSCAPE PLAN IS TO BE SIGNED AND
 SEALED IN ACCORDANCE WITH FS481.306,
 FAC61G10-11.010.
  
 4.)FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, 805-6711.
 ARESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT, DUE TO ONE OR
 MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 5.)GOVERNING CODE EFFECTIVE OCTOBER 1,
 2005 IS FBC2004.REVISE ALL REFERENCES.
 SOME STATE FBC2001, A1 STATES SBC.
  
 6.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR PERMITTING, FBC*106.3.3.
  
 7.)THE SOILS REPORT IS TO HAVE THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 THE FIRM, ALLTERRA, PRINTED ON EACH
 SHEET, FAC61G15-23.002.
  
 8.)SHEET SP1, BUILDING DATA, DECLARES
 S1 OCCUPANCY, ORDINARY HAZARD.SEE
 FBC311.S1 IS MODERATE-HAZARD STORAGE.
  
 9.) SHEET SP1, BUILDING DATA, DECLARE
 BUILDINGS AS TYPE VA OR VB, SO THAT
 COMPLIANCE WITH FBC TABLE 503, FBC TABLE
 601 CAN BE DETERMINED.
  
 10.)INDICATE ON SHEET SP1, BUILDING
 DATA, WHETHER THE BUILDINGS ARE
 SPRINKLED OR UNSPRINKLED.
  
 11.)SHEET S1, UPLIFT CALCS, SHOW AN
 OVERHANG OF 6 FT, HALF TRUSS SPAN OF 1.2
 FT.PLEASE CLARIFY.
  
 12.)BAR JOIST PLANS MAKE REFERENCE TO
 WOOD TRUSSES AND CONNECTORS.PLEASE
 CLARIFY.NO WOOD TRUSSES SHOWN ON ROOF
 FRAMING PLAN OR WALL SECTIONS.
  
 13.)ROOF DRAINAGE CALCS ARE TO COMPLY
 WITH FBC2004, S7.
  
 14.)DECLARE AN OCCUPANT LOAD FOR EACH
 UNIT.
  
 15.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.2(1).SHOW MAXIMUM SLOPE.
  
 16.)FOR THE ROOF, INDICATE WHICH
 APPROVED ASSEMBLY YOU ARE USING IN THE
 PRODUCT APPROVAL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 09:31 Sent To  
Notes
2006-10-15 09:41:14***** REDLINED ******
  
 1) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 FOR EACH BLDGS 1 AND 2 IS NOT LARGE ENOUGH PER TABLES
 IN 250.66. REDLINED MIN SIZE FOR EACH OF THESE SHALL BE
 2/0 MIN. THERE IS NO NEED TO REVISE PLANS UNLESS THERE
 ARE OTHER REVISIONS DURING THE CONSTRUCTION AND BEFORE
 SLAB/FOOTER ELECTRICAL INSPECTION.
 THIS HOWEVER SHALL BE A MIN OF 2/0 TO THE FOOTER
 STEEL.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-20 Cont ID  
Sent By jleahy Date 2005-11-20 Time 16:18 Rev Time 1.00
Received By jleahy Date 2005-11-20 Time 16:18 Sent To P
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2008-07-16 Cont ID  
Sent By rchokshi Date 2008-07-16 Time 08:57 Rev Time 0.00
Received By rchokshi Date 2008-07-16 Time 08:57 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-06-25 Cont ID  
Sent By rchokshi Date 2008-06-25 Time 14:23 Rev Time 0.00
Received By rchokshi Date 2008-06-25 Time 14:15 Sent To  
Notes
2008-06-25 14:23:46FAILED
  
 THE DRAWING SUBMITTED TO US WAS REVISED ON 06/12/06 AS
 REV 4.THIS DRAWING SHOULD INCLUDE THE NEW CHANGES AS
 YOU DESCRIBEDON PLAN/PERMIT REVISION AND SUBMITTALS
 FORM.PLEASE INCLUDE THE CHANGES IN THE DRAWING.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-07-31 Cont ID  
Sent By rchokshi Date 2006-07-31 Time 14:49 Rev Time 0.00
Received By rchokshi Date 2006-07-31 Time 14:45 Sent To  
Notes
2006-07-31 00:00:00PASSED WITH FOLLOWING CONDITIONS:
  
 DUPSTER ENCLOSURES MUST MEET CITY OF WPB
 STANDARDS,CODES,& REQUIREMENTS ETC.,
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-20 Cont ID  
Sent By mamini Date 2005-10-20 Time 11:02 Rev Time 0.50
Received By mamini Date 2005-10-20 Time 11:02 Sent To  
Notes
2005-10-20 00:00:00FAILED:
  
 1. PLEASE INCLUDE CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL.NO CIVIL PLANS IN
 THIS SUBMITTAL PACKAGE.
 2. PLEASE NOTE THAT THE PROPOSED SITE
 MUST BE DESIGNED FOR STORM WATER, PER
 CITY OF WPB' REQUIREMENTS AND CRITERIA.
 2. CITY' PUBLIC UTILITIES AND
 ENGINEERING MUST BE NOTIFIED FOR ALL THE
 CONNECTIONS TO THE CITY SERVICES, PLEASE
 SUBMIT CIVIL PLANS, ATT; MANNY GONZALEZ
 494-1085.
 3. DUMPSTER ENCLOSURES MUST BE SIZED PER
 CITY OF WEST PALM BEACH' REQUIREMENTS
 IF, GARBAGE TO BE PICKED UP BY THE CITY.
 SHEET SP-1 AND SHEET L-1 SHOW DIFFERENT
 SIZE AND LOCATIONS, PLEASE VERIFY.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By mwennerg Date 2006-10-23 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2006-10-23 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By mwennerg Date 2006-08-10 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2006-08-10 Time 10:36 Sent To  
Notes
2006-08-10 00:00:00***PROVISO***
  
 1) PLANS SHOW A NEW FIRE HYDRANT, THAT
 SHALL BE OPERATIONAL PRIOR TO, DURING
 AND AFTER CONSTRUCTION.
  
 2) KNOX BOX APPLICATIONS MAY BE OBTAINED
 AT THE BUREAU OF FIRE PREVENTION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By mwennerg Date 2005-11-17 Time 13:06 Rev Time 0.00
Received By mwennerg Date 2005-11-17 Time 13:06 Sent To  
Notes
2005-11-17 00:00:00******DENIED******
  
 1) SHTS A-1, A-2 AND A-3 INDICATE
 INCORRECT CODE REFERENCE. NFPA 101, 2003
 EDITION SHALL BE REFERENCED.
  
 2) ADDRESS NUMBERS ARE REQUIRED ON THE
 BUILDINGS, TO BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING WITH THE
 BACKGROUND.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND MOUNTED AT DISTANCES TO
 SATISFY THE 75' TRAVEL REQUIREMENT.
  
 4) PLEASE ILLUSTRATE ALL EXISTING WATER
 SUPPLIES PERTINENT TO THIS PROPERTY.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241 AND
 OTHER APPLICABLE CODES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 09:15 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 09:15 Sent To Z
Notes
2008-08-01 09:15:45TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 15:35 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 15:35 Sent To Z
Notes
2008-07-01 15:35:52TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 11:29 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 11:29 Sent To Z
Notes
2008-06-16 11:29:42TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 14:22 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 14:22 Sent To P
Notes
2008-04-03 14:23:04TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 09:31 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 09:31 Sent To B
Notes
2008-02-19 09:31:46TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 14:50 Sent To P
Notes
2008-02-01 14:50:41TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 12:58 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 12:58 Sent To B
Notes
2007-10-19 12:58:51TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 09:41 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 09:41 Sent To B
Notes
2007-08-23 09:42:17TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 10:00 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 10:00 Sent To P
Notes
2007-04-18 10:00:30TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 16:33 Sent To P
Notes
2007-03-14 16:33:36TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 13:50 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 13:50 Sent To P
Notes
2007-01-23 13:50:42TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 14:46 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 14:46 Sent To  
Notes
2006-10-11 15:29:34TO "COMM" BD#23
2006-09-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 16:28 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 16:28 Sent To  
Notes
2006-07-05 00:00:00TO "COMM" BD#18
2006-06-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-01-13 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 10:34 Sent To  
Notes
2005-10-13 00:00:00TO "COMM" BD#52
2005-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-18 Cont ID  
Sent By tgordon Date 2006-08-18 Time 11:11 Rev Time 0.25
Received By tgordon Date 2006-08-18 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By hmoser Date 2005-11-14 Time 07:21 Rev Time 0.00
Received By hmoser Date 2005-11-14 Time 07:21 Sent To  
Notes
2005-11-14 00:00:00NO PLANS NEED PLANS FOR BATHROOM
 VENTILATION.NEED TO SHOW TERMINATION OF
 EXHAUST DUCT ON MECHANICAL PLANS.PLAESE
 SHOW METERIALS USED FOR DUCT,CFM OF FAN.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 8 Status P Date 2008-04-04 Cont ID  
Sent By mperson Date 2008-04-04 Time 10:03 Rev Time 0.00
Received By mperson Date 2008-04-04 Time 10:03 Sent To PC
Notes
2008-04-04 10:10:24REVISION: SHEETS P-1 & P-2 (NOTE: SUBMITTED SHEETS ARE
 8-1/2" X 11". THREE SANITARY RISER DIAGRAMS FOR SHEET
 P-1 AND ONE WATER SERVICE DIAGRAM FOR SHEET P-2).

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-02-19 Cont ID  
Sent By mperson Date 2008-02-19 Time 09:34 Rev Time 0.00
Received By mperson Date 2008-02-19 Time 09:34 Sent To PC
Notes
2008-02-19 09:49:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 NOTE: THE PLUMBING SUBMITTAL FROM 2/1/08 SHOULD HAVE
 BEEN SUBMITTED AS A PLUMBING REVISION TO THE MASTER
 PERMIT #05091674. ANY FUTURE REVISIONS SHALL BE
 SUBMITTED WITH FEES PAID BEFORE PLAN REVIEW. THE
 FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. ORIGINAL PLUMBING SHEETS P-1 AND P-2 WERE SIGNED
 AND SEALED BY ARCHITECT STEPHAN A. YECKES (AR#7444).
 ANY REVISIONS TO THESE PLUMBING SHEETS SHALL BE BY THE
 DESIGN PROFESSIONAL OF RECORD WITH THE REQUIRED TITLE
 BLOCK INFORMATION. PER CHAPTER 481, FLORIDA
 STATUTES,PART 1.
  
 2. SHEET BUILDING (1) 12 UNITS TOTAL, SANITARY RISER
 DIAGRAM:
  
 A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR
 ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES.
 PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS.
  
 B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE
 CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER
 FBC PLUMBING SECTION *701.1 SCOPE.
  
 3. SHEET BUILDING (2) 17 UNITS TOTAL, SANITARY RISER
 DIAGRAM:
  
 A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR
 ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES.
 PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS.
  
 B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE
 CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER
 FBC PLUMBING SECTION *701.1 SCOPE.
  
 C} THE 3" HORIZONTAL DRY VENT IN LAST UNIT IS NOT
 ALLOWED. PER FBC PLUMBING SECTION *905.3 VENT
 CONNECTION TO DRAINAGE SYSTEM.
  
 4. SHEET BUILDING (3) 3 UNITS, SANITARY RISER
 DIAGRAM:CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS
 FOR ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND
 LAVATORIES. PER FBC PLUMBING SECTION *1002.1 FIXTURE
 TRAPS.
  
 5. SHEET WATER SERVICE 32 UNITS:
  
 A} PLEASE CLEARLY INDICATE THE SIZING TO ALL MAINS AND
 BRANCHES, THE WAY ITS BEING INDICATED IS CONFUSING. PER
 FBC PLUMBING SECTION *601.1 SCOPE.
  
 B} PLEASE CLARIFY IF IT IS THE INTENT TO DELETE ALL
 FULL-OPEN VALVES AND INTERIOR WATER PIPING TO THE
 FIXTURES AS IS APPROVED ON SHEET P-2. PER CITY OF WPB
 AMENDMENTS TO CHAPTER 1, SECTION *106.1.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-06-02 Cont ID  
Sent By kstevens Date 2007-06-02 Time 08:42 Rev Time 0.00
Received By kstevens Date 2007-06-02 Time 08:42 Sent To  
Notes
2007-06-02 08:43:42 
  
  
 PASSED/PROVISO
  
 REVISIONS REQUIRED FOR ALL RISER DIAGRAMS THAT DO NOT
 REFLECT THE INSTALLATION.
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-03-17 Cont ID  
Sent By kstevens Date 2007-03-17 Time 14:43 Rev Time 0.00
Received By kstevens Date 2007-03-17 Time 14:43 Sent To  
Notes
2007-03-17 15:00:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEWS****
  
 A. OK
 1. OK
 2. OK
 3. OK
  
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF
 THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 ****RESPONSE NOTED, BUT BAYS 9, 10, 13,
 17, 20 DO NOT REFLECT THE FLOOR PLANS.
 THE FIXTURES ARE TURNED TO THE WRONG
 SIDE OF THE VENT PIPING. SEE FLOOR PLAN.
 - SHOW ALL PIPE SIZES.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN
 CHANGED FOR ALL UNITS. THE 1-1/4" SANITARY TO THE
 LAUNDRY SINK DOES NOT MEET CODE. TABLE 709.1.-BAYS
 3, 7, 11, 15, 19, & 21 THE BRANCH LINES DO NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT. BAYS 9 THRU 21 THE PIPING
 TO THE FIXTURES ARE FACING THE WRONG WAY. - NOT ALL
 PIPE SIZES ARE SHOWN. SECTION 104.2.1, TABLES 710.1(1)
 & 710.1(2).THE LAVS IN BAYS 1, 5, 9, 13, 17, & 20 ARE
 NOT VENTED AS SHOWN AND INDICATES THAT THE TRAP IS
 UNDERGROUND. SECTIONS 104.2.1 AND 901.2.1.THE FLOOR
 PLAN ON SHT S-1 SHOWS CLEANOUTS UPSTREAM OF THE W/C'S.
 THESE ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CLARIFY.
 **********RESPONSE NOTED, BUT BAY #3 STILL DOES NOT
 REFLECT THE FLOOR PLAN, AND NOW BAY #'S 9, 13, 17, & 20
 DO NOT REFLECT THE FLOOR PLAN. ALSO THE BUILDING DRAIN
 DOES NOT REFLECT THE FLOOR PLAN IN THATTHE FLOOR PLAN
 INDICATES ONE DRAIN FOR EVERY TWO BAYS, WHEREAS THE
 RISER SHOWS EACH BAY EXITING THE BUILDING SEPARATELY.
 PLEASE CORRELATE FLOOR PLAN & RISER DIAGRAM.
  
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN
 CHANGED FOR ALL UNITS. ALL BAYS, THE 1-1/4" SANT. TO
 THE LAUNDRY SINK DOES NOT MEET CODE. ALL BAYS, THE LAV
 IS NOT VENTED AS SHOWN, AND THE TRAP IS INDICATED AS
 BEING UNDERGROUND AS SHOWN.SECTIONS 104.2.1, 901.2.1
 AND TABLE 709.1. SHT S-2 INDICATES CLEANOUTS UPSTREAM
 OF THE W/C'S. THE SANT. RISER DIAGRAM DOES NOT REFLECT
 THIS. PLEASE CLARIFY.
 **********RESPONSE NOTED, BUT THE RISER DIAGRAM STILL
 DOES NOT REFLECT THE FLOOR PLAN. ALSO THE BUILDING
 DRAIN ON THE FLOOR PLAN SHOWS THE BUILDING DRAIN
 EXITING THE BAYS 2 THRU 18 TO THE EAST SIDE AND THE
 OTHER BAYS EXITING ON THE WEST SIDE OF THE BUILDING,
 WHEREAS THE RISER SHOWS ALL UNITS EXITING THE WEST SIDE
 OF THE BUILDING. PLEASE CORRELATE FLOOR PLAN & RISER
 DIAGRAM.
  
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
 ******RESPONSE NOTED, BUT THE 1-1/4" SANT. TO THE
 LAUNDRY SINKS DOES NOT MEET CODE. TABLE 709.1. THE LAVS
 ARE NOT VENTED AS SHOWN AND THE TRAPS ARE UNDERGROUND
 AS PIPED. SECTION 901.2.1. SHT S-3 SHOWS CLEANOUTS
 UPSTREAM OF THE W/C'S ON THE FLOOR PLAN BUT THE SANT.
 RISER DOES NOT REFLECT THIS. PLEASE CLARIFY.
 *********RESPONSE NOTED, BUT THE BUILDING DRAIN ON THE
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN LAYOUT.
  
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE FIXTURES ARE LOCATED EAST TO WEST IN
 THE TOILET ROOM AND THE FIXTURE LAYOUT
 ON THE RISER IS FROM SOUTH TO NORTH.
 WATER SERVICE IS NOT AS SHOWN ON THE C-1
 SHEET. SEPARATE BACKFLOW REQUIRED FOR
 EACH BUILDING. SHOW ALL PIPE SIZES.
 INDICATE PIPING MATERIAL.
 ******RESPONSE NOTED, BUT NO MENTION OF THE MATERIAL
 FOR THE WATER PIPING WAS INDICATED. ALL BAYS ALL
 BUILDINGS SHOW A VALVE ABOVE THE FLOOR DOWNSTREAM OF
 ALL W/C'S. PLEASE INDICATE WHAT THAT VALVE IS FOR.
 SECTION 104.2.1. - BLDGS 2 & 3 WATER RISER DIAGRAMS DO
 NOT REFLECT THE FLOOR PLAN FIXTURE LAYOUT. INDICATE
 WHATE THE VALVE DOWNSTREAM OF ALL WATER CLOSETS IS FOR.
 SECTION 104.2.1.
 **********RESPONSE NOTED, BUT ONLY THE WATER MAIN PIPE
 SIZE IS INDICATED. PLEASE SHOW ALL PIPE SIZES. AT THE
 VERY LEAST SHOW A TYPICAL BAY PIPING WILL ALL SIZES
 INDICATED.
  
 8. OK
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
  
 **************NEW COMMENT**************
  
 1C. INFORMATIONAL - SEPARATE IRRIGATION PLANS AND
 PERMIT ARE REQUIRED. SECTION 104.3.1.1.
  
 ************NEW COMMENTS************
  
 1D. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B)AND
 THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE.
  
 2D. PLANS SHALL BE SUBMITTED IN TWO OR MORE SETS OF
 PLANS. PLEASE INSERT ALL PLUMBING PLANS IN THE SETS OF
 PLANS WHEN SUBMITTING. SECTION 106.1.
  
 3D. SHT SP-1 DRAWING INDEX DOES NOT INDICATE SHT P-2.
 PLEASE CORRELATE INDEX AND SHEETS SUBMITTED. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-02-08 Cont ID  
Sent By jleech Date 2007-02-08 Time 13:29 Rev Time 0.00
Received By jleech Date 2007-02-08 Time 13:29 Sent To  
Notes
2007-02-08 14:07:47DENIED;
 1. BUILDING # 1
 A) FLAT DRAWINGS ON PAGE S-1 DOES NOT MATCH SANITARY
 RISER DIAGRAM ON PAGE P-1 FOR BAYS3,7,11,15,19, AND
 21.
 B) WATER SEVICE IS NOT LARGE ENOUGH. USE FBC-2004
 PLUMBING APPENDIX E TO HELP SIZE WATER SERVICE TO
 BUILDING.
 C) SUBMIT MANUFACTURE'S CUT SHEET ON VALVE BOX TO BE
 USED. IS IT RATED FOR TRAFFIC?
 D) MINIMUM SERVICE IS 3/4" AND 1/2" TO FIXTURES.
 E) WATER RISER DIAGRAM SHOWS VALVE ABOVE FLOOR, WHAT
 IS THAT USED FOR?
 2. BUILDING # 2;
 A) FLAT DRAWING ON PAGE S-2 DOES NOT MATCH SANITARY
 RISER DIAGRAM ON PAGE P-1 FOR BAYS
 2,4,6,8,10,12,14,16,18, & 31.
 ALSO B THRU ENOTES UNDER BUILDING # 1.
 3.BUILDING # 3
 A) UNITS 22,24, & 26.
 ALSO B THRU E FROM BUILDING # 1.
 4. ADD NOTE TO DRAWINGS, ALL PIPES RUNNING THROUGH OR
 UNDER A FOOTING OR WALL SHALL BE SLEEVED PER SECTION
 305.2,3,4, & 5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-20 Cont ID  
Sent By kstevens Date 2006-10-20 Time 13:49 Rev Time 0.00
Received By kstevens Date 2006-10-20 Time 13:49 Sent To  
Notes
2006-10-20 16:45:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 A. OK
 1. OK
 2. OK
 3. OK
  
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF
 THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 ****RESPONSE NOTED, BUT BAYS 9, 10, 13,
 17, 20 DO NOT REFLECT THE FLOOR PLANS.
 THE FIXTURES ARE TURNED TO THE WRONG
 SIDE OF THE VENT PIPING. SEE FLOOR PLAN.
 - SHOW ALL PIPE SIZES.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN
 CHANGED FOR ALL UNITS. THE 1-1/4" SANITARY TO THE
 LAUNDRY SINK DOES NOT MEET CODE. TABLE 709.1.-BAYS
 3, 7, 11, 15, 19, & 21 THE BRANCH LINES DO NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT. BAYS 9 THRU 21 THE PIPING
 TO THE FIXTURES ARE FACING THE WRONG WAY. - NOT ALL
 PIPE SIZES ARE SHOWN. SECTION 104.2.1, TABLES 710.1(1)
 & 710.1(2).THE LAVS IN BAYS 1, 5, 9, 13, 17, & 20 ARE
 NOT VENTED AS SHOWN AND INDICATES THAT THE TRAP IS
 UNDERGROUND. SECTIONS 104.2.1 AND 901.2.1.THE FLOOR
 PLAN ON SHT S-1 SHOWS CLEANOUTS UPSTREAM OF THE W/C'S.
 THESE ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CLARIFY.
  
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN
 CHANGED FOR ALL UNITS. ALL BAYS, THE 1-1/4" SANT. TO
 THE LAUNDRY SINK DOES NOT MEET CODE. ALL BAYS, THE LAV
 IS NOT VENTED AS SHOWN, AND THE TRAP IS INDICATED AS
 BEING UNDERGROUND AS SHOWN.SECTIONS 104.2.1, 901.2.1
 AND TABLE 709.1. SHT S-2 INDICATES CLEANOUTS UPSTREAM
 OF THE W/C'S. THE SANT. RISER DIAGRAM DOES NOT REFLECT
 THIS. PLEASE CLARIFY.
  
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
 ******RESPONSE NOTED, BUT THE 1-1/4" SANT. TO THE
 LAUNDRY SINKS DOES NOT MEET CODE. TABLE 709.1. THE LAVS
 ARE NOT VENTED AS SHOWN AND THE TRAPS ARE UNDERGROUND
 AS PIPED. SECTION 901.2.1. SHT S-3 SHOWS CLEANOUTS
 UPSTREAM OF THE W/C'S ON THE FLOOR PLAN BUT THE SANT.
 RISER DOES NOT REFLECT THIS. PLEASE CLARIFY.
  
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE FIXTURES ARE LOCATED EAST TO WEST IN
 THE TOILET ROOM AND THE FIXTURE LAYOUT
 ON THE RISER IS FROM SOUTH TO NORTH.
 WATER SERVICE IS NOT AS SHOWN ON THE C-1
 SHEET. SEPARATE BACKFLOW REQUIRED FOR
 EACH BUILDING. SHOW ALL PIPE SIZES.
 INDICATE PIPING MATERIAL.
 ******RESPONSE NOTED, BUT NO MENTION OF THE MATERIAL
 FOR THE WATER PIPING WAS INDICATED. ALL BAYS ALL
 BUILDINGS SHOW A VALVE ABOVE THE FLOOR DOWNSTREAM OF
 ALL W/C'S. PLEASE INDICATE WHAT THAT VALVE IS FOR.
 SECTION 104.2.1. - BLDGS 2 & 3 WATER RISER DIAGRAMS DO
 NOT REFLECT THE FLOOR PLAN FIXTURE LAYOUT. INDICATE
 WHATE THE VALVE DOWNSTREAM OF ALL WATER CLOSETS IS FOR.
 SECTION 104.2.1.
  
 8. OK
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
  
 **************NEW COMMENT**************
  
 1C. INFORMATIONAL - SEPARATE IRRIGATION PLANS AND
 PERMIT ARE REQUIRED. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By kstevens Date 2006-08-05 Time 17:29 Rev Time 0.00
Received By kstevens Date 2006-08-05 Time 17:29 Sent To  
Notes
2006-08-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 A. OK
 1. OK
 2. OK
  
 3. SHT A-7 DETAIL "A" SHOW THE FLUSH
 CONTROLS. 11-4.16.5 FOR THE W/C AND
 FAUCET TYPE 11-4.19.5 FOR THE LAV.
 ****RESPONSE NOTED, BUT PER 11-4.16.5
 THE FLUSH CONTROLS SHALL BE ON THE WIDE
 SIDE OF THE W/C.
  
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF
 THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 ****RESPONSE NOTED, BUT BAYS 9, 10, 13,
 17, 20 DO NOT REFLECT THE FLOOR PLANS.
 THE FIXTURES ARE TURNED TO THE WRONG
 SIDE OF THE VENT PIPING. SEE FLOOR PLAN.
 - SHOW ALL PIPE SIZES.
  
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
  
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
  
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE FIXTURES ARE LOCATED EAST TO WEST IN
 THE TOILET ROOM AND THE FIXTURE LAYOUT
 ON THE RISER IS FROM SOUTH TO NORTH.
 WATER SERVICE IS NOT AS SHOWN ON THE C-1
 SHEET. SEPARATE BACKFLOW REQUIRED FOR
 EACH BUILDING. SHOW ALL PIPE SIZES.
 INDICATE PIPING MATERIAL.
  
 8. OK
 **************NEW COMMENTS**************
  
 1B. DRINKING FOUNTAINS ARE REQUIRED.
 WATER BOTTLES NOT APPROVED FOR OVER 50%
 OF THE FIXTURES REQUIRED. TABLE 403.1.
  
 2B. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 INCLUDING 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 3B. SHT A-4 TYPICAL GUTTER DRAIN DETAIL.
 INDICATE WIDTH OF OPENING TO DETERMINE
 THE OPENING SIZE TO COMPLY WITH TABLE
 1106.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-18 Cont ID  
Sent By kstevens Date 2006-01-18 Time 16:27 Rev Time 0.00
Received By kstevens Date 2006-01-18 Time 16:27 Sent To  
Notes
2006-01-18 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 A. PLANS TO BE DESIGNED & REVIEWED PER
 THE FBC-2004 EDITION. PLEASE INDICATE ON
 PLANS.
 1. SHTS S-7, S-8, S-9 ROOF CALCULATIONS
 ARE NOT CLEAR AND CAN NOT BE VERIFIED.
 INDICAE THE SQUARE FEET OF EACH BAY ROOF
 AREA, SHOW 1/2 AREA OF THE VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. THE ROOF INDICATES SLOPE ON SOME
 BAYS, BUT NOT ALL. INDICATE SLOPE OF
 EACH BAY. SOME BAYS SHOW DRAINS ON
 EITHER SIDE OF THE BUILDING SO PLEASE
 INDICATE IF THE ROOF SLOPES TO EITHER
 SIDE OF THE BUILDING. IF SO PLEASE SHOW
 THE HIGH SPOT OF THE ROOF AND INDICATE
 THE SQUARE FOOTAGE DRAINING TO EACH
 DRAIN. NOTE INDICATES GUTTERS, BUT
 GUTTERS ARE NOT SHOWN ON THE ROOF PLANS
 NOR ARE THEY SHOWN ON THE BUILDING
 ELEVATIONS. CALCULATIONS INDICATE 6"
 GUTTERS & 7" DOWNSPOUTS, BUT ROOF PLAN
 SHOWS NO GUTTERS AND 5" CAST IRON
 DOWNSPOUTS AND ALSO 5" PVC DOWNSPOUTS.
 PLEASE CLARIFY. - GUTTER SIZING
 CALCULATIONS ONLY POINT TO BAYS 5, 14,
 20 & 28. WHAT ARE THE CALCULATIONS FOR
 THE OTHER BAYS? PLEASE CLARIFY. NO BAYS
 SHOWN FOR BUILDING 3. - NO SECONDARY
 ROOF DRAINS OR SCUPPERS ARE SHOWN.
 PLEASE CLARIFY. SECTIONS 106.1.1, 1106 &
 1107.
 2. SHTS A-4, A-5, & A-6, INDICATE THE
 ELEVATION OF THE ROOF LEVEL. THE TOP OF
 THE PARAPET FOR EAST ELEVATIONS
 BUILDINGS 1 & 2 AND WEST ELEVATION DOES
 NOT INDICATE THE HEIGHT OF THE HIGH
 PARAPET SECTIONS.- NO GUTTERS SHOWN.
 SECTION 106.1.1.
 3. SHT A-7 DETAIL "A" SHOW THE FLUSH
 CONTROLS. 11-4.16.5 FOR THE W/C AND
 FAUCET TYPE 11-4.19.5 FOR THE LAV.
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT
 DOWNSTREAM OF THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 8. SUBMIT A HORIZONTAL PIPING LAYOUT
 FLOOR PLAN SHEET FOR EACH BUILDING
 SHOWING ALL PIPE SIZES. SECTION
 106.3.5.1.3(3)(4)(8)(9)(10) - SHOW WHERE
 THE SANT., STORM EXIT THE BUILDING AND
 WHERE THE WATER ENTERS THE BUILDING. -
 SUBMIT A STORM BUILDING DRAIN ISOMETRIC
 AND STORM RISER DIAGRAM. SHOW ALL PIPE
 SIZES, OFFSETS SQUARE FOOTAGE OF EACH
 RISER AND SHOW SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. INDICATE THE
 TERMINATION POINT OF STORM SYSTEM.
 SECTION 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2008-08-04 Cont ID  
Sent By kdfreema Date 2008-08-04 Time 08:08 Rev Time 0.00
Received By kdfreema Date 2008-08-04 Time 08:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2008-07-08 Cont ID  
Sent By kdfreema Date 2008-07-08 Time 14:38 Rev Time 0.00
Received By kdfreema Date 2008-07-08 Time 14:38 Sent To B
Notes
2008-07-08 14:39:54FAILED PER DISCUSSION WITH R. BROWN AND N. MELICK ON
 7/8/08. PLANS DO NOT MEET ADA REQUIREMENTS FOR
 DISPERSAL OF ACCESSIBLE SPACES.
  
 KELLY FREEMAN, 822-1435

Review Stop Z ZONING
Rev No 4 Status F Date 2008-06-18 Cont ID  
Sent By kdfreema Date 2008-06-18 Time 15:12 Rev Time 0.00
Received By kdfreema Date 2008-06-18 Time 15:12 Sent To  
Notes
2008-06-18 15:18:20***FAILED***
  
 AS DISCUSSED ON-SITE WITH JON COLANERI 6/17/08, PLEASE
 REVISE THE AS-BUILT DRAWINGS TO REFLECT THE ACTUAL SITE
 CONDITIONS INCLUDING, BUT NOT LIMITED TO:
  
 1. LOCATION AND CONFIGURATION OF ALL CURBING AND
 LANDSCAPE ISLANDS.
 2. FENCING AND GATES.
 3. CONFIGURATION OF PARKING SPACES AND LOADING ZONES.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1458 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-12-06 Cont ID  
Sent By kdfreema Date 2006-12-06 Time 13:11 Rev Time 0.00
Received By kdfreema Date 2006-12-06 Time 13:11 Sent To  
Notes
2006-12-06 13:16:03PROVISO: THE CHAINLINK FENCE ALONG THE SOUTH PROPERTY
 LINE SHALL NOT EXTEND BEYOND SAID PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By kdfreema Date 2006-07-20 Time 16:18 Rev Time 0.00
Received By kdfreema Date 2006-07-20 Time 16:18 Sent To  
Notes
2006-07-21 00:00:00SITE PLAN APPLICATION HAS NOT BEEN
 APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT.
  
 NEITHER RESPONSES NOR REVISED PLANS HAVE
 BEEN SUBMITTED ADDRESSING THE PPRC
 COMMENTS.
  
 COMMENTS REGARDING SITE PLAN REVIEW WILL
 BE PROVIDED.
  
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER AT
 822-1435 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-02 Cont ID  
Sent By ebowers Date 2005-12-02 Time 15:04 Rev Time 0.00
Received By ebowers Date 2005-12-02 Time 15:03 Sent To I
Notes
2005-12-02 00:00:00INFORMAL SITE PLAN APPROVAL HAS NOT BEEN
 ISSUED. PLANS AND PLATS REVIEW COMMITTEE
 (PPRC) COMMENTS HAVE NOT BEEN
 SATISFACTORILY ADDRESSED AND REVISED IN
 THE PLANS. PLEASE CONTACT EDNASHA
 BOWERS, PLANNER AT 561-822-1435 FOR
 QUESTION. SEE ATTACHED PPRC COMMENTS.