Plan Review Details - Permit 05091637
Plan Review Stops For Permit 05091637
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-11 Cont ID  
Sent By alange Date 2006-08-11 Time 08:44 Rev Time 0.00
Received By alange Date 2006-08-11 Time 08:44 Sent To  
Notes
2006-08-11 00:00:00STRUCTURAL SUBMITTAL OK FOR BEAM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-20 Cont ID  
Sent By alange Date 2006-04-20 Time 11:08 Rev Time 1.25
Received By alange Date 2006-04-20 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-04 Cont ID  
Sent By alange Date 2006-04-04 Time 09:47 Rev Time 1.25
Received By alange Date 2006-04-04 Time 09:46 Sent To Z
Notes
2006-04-05 00:00:004-5/2006APRROVED BY ZONING
  
 CLASS B APPROVED BY ZONING BOARD OF
 APPEALS CASE NO. 3170 MARCH 2, 2006 TO
 REPLACE EXISTING HOME WITH AN INCREASE
 OF 248 SQUARE FEET. -JJP
2006-04-04 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS;
 PRODUCT APPROVALS NEEDED FOR ROOFING AND
 LINTELS.NOTE:SELECT THE ROOFING
 ASSEMBLY USED ON THE PRODUCT APPROVAL.
 CASEMENT WINDOW MISSING STATE PRODUCT
 APPROVAL.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.BUILDING VALUATION IS TOO LOW AND
 HAS BEEN ADJUSTED ACCORDING TO SBCCI
 BUILDING VALUATION DATA $130,850.00
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-27 Cont ID  
Sent By alange Date 2006-01-27 Time 10:26 Rev Time 1.00
Received By alange Date 2006-01-27 Time 10:26 Sent To  
Notes
2006-01-27 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS;
 SIMONTON SINGLE HUNG WINDOW HAS A STATE
 PRODUCT APPROVAL FOR MULLIONS ATTACHED.
 PRODUCT APPROVALS NEEDED FOR ROOFING AND
 LINTELS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 -MAKE TWO COMPLETE SETS INCLUDING STATE
 OVER PAGE OF ALL PRODUCT APPROVALS
  
 4.CLEARLY SHOW THE EXISTING BUILDING
 AND THE DISTANCE TO THE NEW BUILDING SO
 THAT TABLE 600 ISSUES CAN BE ADDRESSED.
 ALSO SHOW OPENINGS THAT FACE TOWARDS THE
 TWO BUILDINGS.
  
 5.SHOW AREA CALCULATION OF NEW
 BUILDING AND SEPERATE BETWEEN A/C AREAS
 AND OTHER COVERED AREAS.
  
 6.BUILDING VALUATION IS TOO LOW AND
 WILL BE ADJUSTED ACCORDING TO SBCCI
 BUILDING VALUATION DATA WHEN AREA CALCS
 ARE SUBMITTED.
  
 NEW COMMENTS;
 A.INCLUDE A DOOR AND WINDOW SCHEDULE
 ON PLANS.
  
 B.SIGN OWNER/AGENT ON ENERGY CALCS AND
 HAVE R-VALUE ON PLANS MATCH ENERGY
 CALCS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By alange Date 2005-12-20 Time 08:19 Rev Time 2.50
Received By alange Date 2005-12-20 Time 08:19 Sent To  
Notes
2005-12-20 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS;
 SIMONTON SINGLE HUNG WINDOW HAS A STATE
 PRODUCT APPROVAL FOR MULLIONS.
 PRODUCT APPROVALS NEEDED FOR ROOFING AND
 LINTELS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.CLEARLY SHOW THE EXISTING BUILDING
 AND THE DISTANCE TO THE NEW BUILDING SO
 THAT TABLE 600 ISSUES CAN BE ADDRESSED.
 ALSO SHOW OPENINGS THAT FACE TOWARDS THE
 TWO BUILDINGS.
  
 5.SHOW AREA CALCULATION OF NEW
 BUILDING AND SEPERATE BETWEEN A/C AREAS
 AND OTHER COVERED AREAS.
  
 6.BUILDING VALUATION IS TOO LOW AND
 WILL BE ADJUSTED ACCORDING TO SBCCI
 BUILDING VALUATION DATA WHEN AREA CALCS
 ARE SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-23 Time 06:57 Rev Time 0.50
Received By btrobaug Date 2006-03-23 Time 06:30 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-02 Cont ID  
Sent By btrobaug Date 2005-12-02 Time 17:56 Rev Time 0.75
Received By btrobaug Date 2005-12-02 Time 17:02 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 17:09 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 17:09 Sent To B
Notes
2006-08-02 00:00:00TO"ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 14:22 Sent To B
Notes
2006-04-15 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 16:57 Sent To E
Notes
2006-03-21 00:00:00TO BT'S DESK. NEW SHEETS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-18 Cont ID  
Sent By adarroug Date 2006-01-18 Time 14:54 Rev Time 0.00
Received By adarroug Date 2006-01-18 Time 14:54 Sent To Z
Notes
2006-01-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-02 Cont ID  
Sent By adarroug Date 2005-12-02 Time 13:18 Rev Time 0.00
Received By adarroug Date 2005-12-02 Time 13:18 Sent To E
Notes
2005-12-02 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 17:21 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 17:21 Sent To Z
Notes
2005-11-17 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-11 Cont ID  
Sent By fgodard Date 2005-10-11 Time 08:38 Rev Time 0.00
Received By fgodard Date 2005-09-30 Time 14:04 Sent To  
Notes
2005-10-11 00:00:00PERMIT NOT LOOKED AT BY PLAN REVIEW/NAT
 HEALY P/UAPP WITH PLANS TO RESUBMITT
 FOR REVIEW OK PER L MARTINEZ
2005-09-30 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-05 Cont ID  
Sent By tgordon Date 2005-12-05 Time 14:35 Rev Time 0.20
Received By tgordon Date 2005-12-05 Time 14:35 Sent To P
Notes
2005-12-05 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-30 Cont ID  
Sent By jleech Date 2006-03-30 Time 07:52 Rev Time 0.00
Received By jleech Date 2006-03-30 Time 07:52 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-07 Cont ID  
Sent By jleech Date 2005-12-07 Time 14:52 Rev Time 0.00
Received By jleech Date 2005-12-07 Time 14:52 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mmclean Date 2006-10-26 Time 14:16 Sent To  
Notes
2006-10-26 14:17:10NAT NEEDS TO MARK WITH DIMENSION OF THE EXISTING
 DRIVEWAY THAT IS TO BE REPLACE.
 SURVEY DOES NOT PROVIDE THE DIMENSION AND DOES NOT
 CLEARLY INDICATE THE LOCATION OF THE PROPOSED WORK.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-04-05 Cont ID  
Sent By mmclean Date 2006-04-05 Time 14:27 Rev Time 0.00
Received By mmclean Date 2006-04-05 Time 14:27 Sent To B
Notes
2006-04-05 00:00:00GIVEN TO JILLIAN PAPA, PLANNER 822-1435
 ZBA CASE# 3170

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-26 Cont ID  
Sent By mmclean Date 2006-01-26 Time 17:01 Rev Time 0.00
Received By mmclean Date 2006-01-26 Time 17:01 Sent To B
Notes
2006-01-26 00:00:00DENIED,
 1. THE PROPSED NSF STRUCTURE MUST BE
 BUILT THE SAME SQUARE FOOTAGE OF THE OLD
 STRUCTURE.CANNOT INCREASE EXISTING
 NONCONFORMITY. ZONED SF7
 2.THE WALL IN REAR OF NSF MUST MEET THE
 6FT BUILDING SEPERATION FROM THE
 ACCESSORY STRUCTURE IN REAR.NEED TO
 REMOVE THE WALL IN REAR OF NSF.
 3. THE ROOF OVERHANG ON TRELLIS CAN ONLY
 ENCROACH 3FT INTO SETBACK.
 4. THE PROPOSED DRIVEWAY & WALKWAY
 EXCEEDS THE REQUIREMENT FOR CONCRETE
 WITHIN THE FRONT SETBACK OF PROPERTY.
 5. CAN ONLY HAVE 312.5SQ FT OF CONCRETE
 WITHIN THE 25FT FRONT SETBACK.NEED TO
 REDUCE THE DRIVEWAY & WALKWAY TO BE A
 TOTAL OF 12.5FT.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 WALL/FENCE/GATE WITH CITY OF WEST PALM
 UTILITY EASMENT APPROVAL.
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK OF PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-11-18 Cont ID  
Sent By mmclean Date 2005-11-18 Time 08:04 Rev Time 0.00
Received By mmclean Date 2005-11-18 Time 08:04 Sent To  
Notes
2005-11-18 00:00:00DENIED,
 1. ZONED SF7, CANNOT REBUILD NEW SINGLE
 HOUSE UPON DEMOLISHING THE EXISTING.
 2. THE PROPOSED TRELLIS ON THE SIDE MUST
 MEET THE TOTAL SIDE SETBACK OF SF7 (5FT
 MIN WITH TOTAL 15FT).
 3. THE PROPOSED WALL IN REAR & GATE DOES
 NOT SHOW THE HEIGHT ON WALL DETAIL.
 4. WALL IN REAR IS ATTACHED TO MAIN
 STRUCTURE MUST MEET THE 6FT SEPERATION
 FROM THE COTTAGE IN REAR OF PROPERTY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720